Radwin RW2025 Outdoor radio unit operating in the 2.5-2.7 GHz (BRS) band User Manual STW

Radwin Ltd. Outdoor radio unit operating in the 2.5-2.7 GHz (BRS) band STW

Contents

User Manual Part 2

Configuring the GSU Chapter 11RADWIN 2000 User Manual Release  2.5.40 11-8Site Configuration: GPS Sync UnitThis window is the main GSU configuration tool:Figure 11-8: Site Configuration: GPS Sync Unit1. Setting the RFP for HSSThe GSU is automatically configured as HSS Master (HSM). If the hub site consists only of WinLink 1000 units, then any suitable RFP may be chosen. If there are one or more RADWIN 2000 units, you must use RFP B or E.The permitted RFPs are also dependent on channel bandwidth and are color coded as fol-lows:NoteThe 1000 and 2000 labels refer to WinLink 1000 and RADWIN 2000 radios, respectively. The actual annotation seen may vary, but the intention should be clear.NoteEnsure that no other collocated ODU is configured as HSM.You May use RFP/Channel Bandwidth combinations with this colorFor these collocated radiosWinLink 1000 onlyRADWIN 2000 onlyWinLink 1000 and RADWIN 2000 togetherNone - unavailable
Configuring the GSU Chapter 11RADWIN 2000 User Manual Release  2.5.40 11-9There is a further restriction: If there are two distributed sites transmitting to each other, they must both use the same RFP. This requirement, together with use of shifted transmis-sion phase (item 3 below), ensures that communicating distributed sites to not interfere with each other by transmitting simultaneously.Two GSU managed sites transmitting with shifted transmission phase and using the same RFP, transmit one half a RFD apart (see Figure 11-3 above).2. Setting the Tx Transmission RatioSince the GSU is always HSM, it must be able to cater for hub site RADWIN 2000 C based links. (See the RADWIN 2000 User Manual, Chapter 5). If you use asymmetric allocation, shifted transmission phase becomes unavailable and you cannot “cascade” links as described in step 1.3. Choosing the Transmission PhaseChose the Transmission Phase in accordance with considerations in step 1 above. If you choose Shifted Phase then the Asymmetric Ratio selector is disabled.Site Configuration: ManagementFigure 11-9: Site Configuration: ManagementHere you set the GSU IP address, subnet mask and gateway. You also set trap addresses here. It is identical to the corresponding panel for WinLink 1000.
Configuring the GSU Chapter 11RADWIN 2000 User Manual Release  2.5.40 11-10Site Configuration: InventoryFigure 11-10: Site Configuration: InventorySite Configuration: SecurityYou can only change the SNMP Community stings:Figure 11-11: Site Configuration: SecuritySite Configuration: Date and TimeODU Recent events, alarms and traps are time-stamped from the time method chosen here (NTP, managing computer, ODU default).
Configuring the GSU Chapter 11RADWIN 2000 User Manual Release  2.5.40 11-11Figure 11-12: Setting the date and time for trap reportingSite Configuration: OperationsThe only available action here is Restore System Defaults:Figure 11-13: Site Configuration: Operations
GSU Preferences Chapter 11RADWIN 2000 User Manual Release  2.5.40 11-12GSU PreferencesThe Preferences window adds a new tab for the GSU:Figure 11-14: Site Configuration: OperationsYou may chose the units for latitude/longitude coordinates.GSU Monitoring and DiagnosticsThe monitoring and diagnostic reports are similar to those of WinLink 1000.GSU Telnet SupportTo configure the GSU with Telnet, start a Telnet session, usingtelnet <GSU_ipaddr>.For example, if you run Telnet as follows,telnet 192.168.222.20you will be asked for a user name and password. You must log on with administrator privilege under user name, admin and password netman.The available commands are the same as for WinLink 1000 with the addition of four addi-tional display commands and three additional set commands. The additional display commands are display rfpdisplay ratiodisplay tx_phasedisplay gpsinfoThe last one display gpsinfo, is the most interesting:admin@192.168.222.20-> display gpsinfoCurrent GPS time                        102941.000
Software Update for GSUs Chapter 11RADWIN 2000 User Manual Release  2.5.40 11-13Current GPS latitude                   51.500000Current GPS N\S Indicator           NCurrent GPS longitude                0.000000Current GPS E\W Indicator           ECurrent GPS number of satellites   09Current GPS altitude                    84.0Command "display gpsinfo" finished OK.The three additional set commands are    set rfp <index> (2-6)    set ratio <ratio>    set tx_phase <mode:1=normal,2=shifted>Software Update for GSUsAll GSUs in a distributed site can be updated simultaneously. Use an IP list as described in Chapter 15.
RADWIN 2000Broadband Wireless Transmission SystemUSER MANUALRELEASE 2.5.40Part 3: Advanced InstallationUM 2000-2540/02.11
RADWIN 2000 User Manual Release  2.5.40 12-1Chapter 12Monitored Hot StandbyInstallation ProcedureWhat is a RADWIN Monitored Hot StandbyThe RADWIN Monitored Hot Standby (MHS a.k.a 1+1) is a duplicated link set up as a primary link and a secondary link in hot standby mode as shown in Figure 12-1 below.Figure 12-1: RADWIN Monitored Hot Standby
What RADWIN MHS provides Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-2RADWIN MHS provides redundancy and backup to TDM services. It is designed to provide high reliability high-capacity Point-to-Point links. The RADWIN MHS is -• Designed to provide redundancy and high reliability for carrier class operators• Optimized for high capacity links operating in license-free bands• A comprehensive solution providing protection against both equipment failure and loss of air interface, by simple connectivity between a primary link and a secondary linkThe main service redundancy features of the RADWIN MHS are – • TDM service cut-over from the primary to the secondary link is completely automatic• TDM service cut-over time no more than 50 ms• Automatic restore to primary link as soon as it becomes available• Support for up to sixteen TDM channels for RADWIN 2000 and four TDM channels for WinLink 1000.MHS is supported between - • two WinLink 1000 links• two RADWIN 2000 links• a WinLink 1000 link and a RADWIN 2000 link. What RADWIN MHS providesEquipment ProtectionEquipment protection is provided for the electrically-active network elements, ODU and IDU.The primary IDU and the secondary IDU are connected by a cable to monitor failure and to control protection switching. Switching time is less than 50ms. When connecting two WinLink 1000 links as 1+1, one dual-polarization antenna can be shared by the primary link and the secondary link.Air-Interface ProtectionAir-Interface protection is unique to RADWIN and is optimized for wireless links operating in license-free bands.The primary link and the secondary link use different frequency channels. If the air-interface of the primary link is disturbed and cannot carry the required TDM service, then the system automatically switches to the secondary link.In addition, improved robustness and frequency planning flexibility is achieved, as the pri-mary and secondary air interfaces can operate in the same frequency band or in different fre-quency bands.Automatic Channel Selection (ACS) can be configured for each link to add additional robust-ness.The primary and secondary links are synchronized using Hub Site Synchronization (HSS).It is recommended that both sites be installed with HSS cables. If HSS fails at one site, it can be operated from the other site by remote configuration.
Purpose of this Chapter Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-3Purpose of this ChapterThis chapter is an installation and maintenance guide for RADWIN MHS. It applies to all RAD-WIN radio products able to support the Monitored Hot Standby operational mode.Who Should Read thisThis chapter is intended for persons responsible for the installation and maintenance of RAD-WIN MHS. To use it you need to know how to -• Install a WinLink 1000 radio link• Install a RADWIN 2000 radio link• Use the RADWIN Manager softwareRADWIN MHS Kit Contents• One Y-Connection Patch Panel• One MHS cableFigure 12-2: RADWIN Y-Connection Patch PanelInstalling a RADWIN MHSFigure 12-1 above is a schematic of a RADWIN MHS. Figure 12-3 shows how to connect the IDUs to the Patch Panel.NoteThe following procedure is substantially generic to all RADWIN radio products. Differences between WinLink 1000 and RADWIN 2000 class products will be stated explicitly. What you see on your running RADWIN Manager may differ in some details from the screen captures used to illustrate this chapter.
Installing a RADWIN MHS Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-4Figure 12-3: How to connect the IDUs to the Patch PanelIn what follows, it will be assumed that – 1. We will depart from our usual Site A / Site B conventions. Sites A and B on the primary link will be Sites 1.2 and 1.4 respectively. The corresponding sites on the secondary link will be Sites 2.2 and 2.4. The site names reflect their IP addresses. This is a useful convention and is reflected in the screen captures below.2. The link will be managed from Site 1.2; Site 1.4 may be a remote site.3. The links intended as the primary and secondary will be referred to their respective names, Primary Link and Secondary Link as shown in Figure 12-1 above, despite their having yet to be installed.To install a Hot Standby Link:1. Set up Primary Link in the usual way. Ensure that it is fully operational in accordance with the relevant instructions in Part 1 of the User Manual.2. Connect user equipment to Site 1.4.3. At Site 1.2, disconnect the TDM cables from the external equipment or disconnect external equipment from the Hot Standby Patch Panel.4. The HSS cable (connecting the ODUs) should be connected at Site 1.2. The ODU belonging to the primary link should be configured as HSM, whereas the ODU belonging to the secondary link should be configured as HSC-CT.5. Establish Secondary Link in the usual way, with HSS enabled. The two link fre-quencies should be at least 5MHz apart.Note•With RADWIN 2000 links you can protect up to 16 TDM ports. To pro-tect more than eight TDM ports use two Patch Panels at each site.• Ethernet services are carried independently by primary and second-ary links. Each link carries different Ethernet traffic. MHS does not protect Ethernet traffic.NoteDo not proceed unless this condition is fully met!
Installing a RADWIN MHS Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-56. Connect the MHS cables at Sites A and B as shown in Figure 12-1 and Figure 12-3 above.7. Run the Configuration Wizard for Primary Link. Activate TDM services in the usual way. Navigate to the Hot Standby tab, in the Services Configuration panel:Figure 12-4: Services Configuration Panel: Hot Standby mode selectionCheck the Primary button to configure Primary Link as the primary link.8. Complete the Wizard, and then move to Secondary Link.9. Repeat step 7 for Secondary Link. For the Services Hot Standby tab, this time, check the Secondary button.10. Complete the Wizard.11. At Site 1.2, reconnect the Hot Standby Patch panel to the external equipment.From this point on, we will simply refer to primary and secondary link (no capitalized names).At the end of the process, the RADWIN Manager main windows should look like this:
Installing a RADWIN MHS Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-6Figure 12-5: The primary link under normal operation
Installing a RADWIN MHS Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-7Figure 12-6: The secondary link under normal operationTo see what happens following a cut-over from the primary link to the secondary link, you need to have running two copies of the RADWIN Manager – one logged into the primary link, and one logged into the secondary link.Here then, is the situation after a cut-over to the secondary link:For the primary link, the following window will appear for a few seconds:
Installing a RADWIN MHS Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-8Figure 12-7: Primary link a few seconds before regular No-Link displayIt will then revert to the standard No-Link-available window.On the secondary link Manager window, you will see a window like this:
Maintaining a RADWIN MHS Link Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-9Figure 12-8: Secondary Link operating as the Hot Standby linkNotice that the active link notice is highlighted in red, so that there is no mistaking which link is operational.Maintaining a RADWIN MHS LinkIDU ReplacementThere are two situations, which must be treated differently.Situation 1:To replace either of the IDUs at Site 1.4 or the IDU at Site 2.2, nothing special is required. Simply disconnect the IDU to be replaced – and replace it with a new one. Replacing a sec-ondary link IDU obviously has no effect on the TDM service. Disconnecting the Site 1.4 pri-mary IDU activates Hot Standby. After the Site 1.4 primary IDU is replaced, the Link will detect the change and switch back to the primary link.If you replaced the Site 2.2 IDU, remember to reconnect the MHS cable.Situation 2:Replacing the Site 1.2 IDU is different, and requires several steps.To replace the Site 1.2 primary link IDU:1. Power off the Site 1.2 IDU. This activates the secondary link using Hot Standby.
ODU Replacement Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-102. Run the Configuration manager on the secondary link, and in the Hot Standby panel of Figure 12-4 above, check the Disabled button.3. Replace the Site 1.2 IDU without connecting it to the ODU (to prevent transmission by the primary link with the undefined IDU).4. Reconnect the MHS cable between the IDUs at Site 1.2.5. Again, run the Configuration Wizard on the secondary link, and in the panel of Figure 12-4 above, check the Secondary button to re-enable the link as secondary. 6. Connect the new Site 1.2 IDU to its ODU.The Hot Standby will automatically revert to the primary link within 50ms.ODU ReplacementBoth the primary and secondary replacement ODUs require pre-configuration prior to inser-tion into the link. The items to be pre-configured are•HSS mode•Link ID•Frequency• Hot Standby mode – using the new Services panel in Figure 12-4 above• IP address (optional)To pre-configure an ODU:1. Attach the new ODU to an IDU or a PoE device.2. Run the RADWIN Manager and use Hot Standby tab of Figure 12-4 above to config-ure the new ODU to Primary or Secondary mode as required.3. Ensure that it is set to the proper HSS mode in accordance with Figure 12-4 above. Enter the required Link ID and frequency.To replace an ODU for primary or secondary link, at either site:• Install the pre-configured ODU. (Since the other link is working normally, nothing need be done with it. If the secondary ODU was replaced, TDM service remains as is on the primary link. If the primary ODU was replaced, then the TDM service will shift back to the primary link.)Switching LogicSwitching from Primary Link to Secondary LinkSwitching from primary link to secondary link will occur following:• Loss of the primary air interface due to sync lossNotePre-configuration must be carried out before the new ODU is connected to its IDU. If you try to do it “live” against its IDU, it will cause spurious transmissions and a service break.
Switching from Primary Link to Secondary Link Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-11• Loss of the primary air interface due to failure of the receiver to acquire expected E1/T1 data during a period of 24ms• The Primary equipment (either ODU or IDU, local or remote) is powered offFollowing the switch from the primary to the secondary link, the primary and secondary link Manager main windows should look like this:Figure 12-9: Primary link after the switch over to secondary link (After a few seconds the dis-play moves to No-Link display, with TDM ports grayed out.)
Switching back from the Secondary to the Primary Link Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-12Figure 12-10: Secondary link operating after the switch over to secondary. (After a few moments the TDM icons become green.)Switching back from the Secondary to the Primary LinkSwitching back from the secondary link to the primary link will occur after the primary link has become and remains fully functional for a continuous period of at least one second. Following reversion from the secondary link to the primary link, the Manager main windows should look like this:
Switching back from the Secondary to the Primary Link Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-13Figure 12-11: Primary link operating after the switch back from secondary
System Operation description Chapter 12RADWIN 2000 User Manual Release  2.5.40 12-14Figure 12-12: Secondary Link operating after the switch back to PrimarySystem Operation description Normal operation • TDM services are carried by the primary link • The secondary link (equipment and air interface) is operating but not carrying user traffic•TDM ports on the secondary IDUs are tri-stateSwitching to backup• Switching to secondary will occur in the following cases:• Loss of the primary air interface due to sync loss• Loss of the primary air interface due to failure of the receiver to acquire expected TDM data during a period of 24ms• Primary equipment power off (either ODU or IDU, local or remote)• The switching result would be:• TDM ports on the primary IDUs turn to tri-state • TDM ports on the secondary IDUs become activeBackup operation • TDM services are carried by the secondary linkSwitching back to primary • Switching back to primary will occur as soon as the Primary link is fully functional for 1 second
RADWIN 2000 User Manual Release  2.5.40 13-1Chapter 13The RADWIN EthernetRingScopeThe description of RADWIN Ethernet Ring in this Chapter is completely generic: Both WinLink 1000 and RADWIN 2000 links may participate in an Ethernet ring.What is an Ethernet RingAn Ethernet ring consists of several nodes connected by hops (links). Loops are not allowed with Ethernet; therefore one hop is a Ring Protection Link (RPL) which “blocks” Ethernet traffic. In the event of failure in the ring, the Ring Protection Link unblocks and Ethernet traf-fic in the ring is restored.Some terminology:•Normal State – all member links are functional except the RPL which is blocked.•Blocked - the air-link is up but Ethernet traffic is not transmitted across the link. The Ethernet service panel for the RPL in the RADWIN Manager is labeled Idle•Unblocked - Ethernet traffic is transmitted across the RPL. The Ethernet service panel for the RPL in the RADWIN Manager is labeled Active•Protection State – a member link is broken and the RPL passes Ethernet traffic•Ring Protection Link - as described above•Ring Link - any member link controlled by the RPL•Independent Link - not subject to ring protectionCautionVLAN IDs are used by RADWIN products in three separate contexts: Management VLAN, Traffic VLAN and Ethernet Ring. It is recommended that you use different VLAN IDs for each context.
RADWIN Ethernet Ring Chapter 13RADWIN 2000 User Manual Release  2.5.40 13-2•Ring Protection Message (RPM) - control message used to monitor and control the ring.RADWIN Ethernet RingThe following figure describes the RPL behavior during a ring failure and recovery cycle.Figure 13-1: Ring Protection mechanismNoteRPM messages are broadcast, so it is essential (to prevent flooding) to associate the RPL and member Ring LInks with a VLAN ID. This requires in turn, that equipment used in the ring either supports VLAN or can transparently pass through VLAN tagged packets.
RADWIN Ethernet Ring Chapter 13RADWIN 2000 User Manual Release  2.5.40 13-3The steps below follow the numbering in Figure 13-1:1. Normal operationEthernet traffic runs in the ring, but does not pass through the RPL, which is blocked. The RPL does however, broadcast RPM packets through the ring.2. Ring Link down, RPL notifiedThe RPL detects a link-down condition by the non-arrival of an RPM packet. It remains blocked for the Minimum time for failure detection which is configurable using the RADWIN Manager (see page 13-9).3. Ring Link down, RPL unblocked for trafficThe RPL unblocks for Ethernet traffic after the Minimum time for failure detection expires and no RPM message has been received.4. Ring Link restored but still blocked for trafficThe Ring Link is restored, but remains blocked for the Minimum time for recovery, set using the RADWIN Manager, to avoid rapid fluctuations leading to potential short term loops (see page 13-9).5. Ring Link restored, RPL blocked for trafficThe RPL blocks to Ethernet traffic after the Minimum time for recovery expires and restores Ethernet traffic to the Ring Link (with a special RPM packet).Return to 1.) Ring Link restored, RPL blocked for traffic The ring is back to normal operation.With RADWIN links, RADWIN’s Ring Protection solution prevents Ethernet loops in the ring at all times. The ring is always broken somewhere.• Under a ring configuration a RADWIN Ring Link that was down and commences recov-ery, keeps blocking Ethernet traffic. The RPL identifies this situation, blocks itself and then unblocks the other Ring Link. This is the transition from step 4 to 5 in Figure 13-1.• If the failed hop is not a RADWIN link then there are two possibilities:• If the hop Ring Link can signal that it is down by issuing a Loss of Signal (LOS) at the Ethernet port, then the RPL will control the RADWIN link connected to that port in the same manner as described above, to prevent an Ethernet loop.• Otherwise, there may be a short loop period when the RPL is still open for traffic and the Ring Link is also unblocked during the Minimum time for recovery.
Ethernet Ring Topologies Supported by RADWIN Chapter 13RADWIN 2000 User Manual Release  2.5.40 13-4Ethernet Ring Topologies Supported by RADWINThe following ring topologies are supported:Table 13-1: Topologies supported by RADWIN Ethernet RingStand-alone ringThe ring is not connected to other ringsSingle-homed ringOne of the nodes is connected to another network / ring:Dual-homed ringTwo adjacent nodes are connected through a non-RADWIN link (e.g. micro wave or fiber):Note:• The network has to be layer 2 and support VLANs• The ring control broadcasts RPM packets. Hence it is recommended to prevent these packets from propagating into the network
Ethernet Ring Topologies Supported by RADWIN Chapter 13RADWIN 2000 User Manual Release  2.5.40 13-5Mixed ringSome of the hops are connected through non-RADWIN links:Repeater sitesSome of the hops are connected through RADWIN links with PoE devices, not supporting ring functionality:Shared ringRADWIN rings with shared hops. Note:• A RADWIN link hop can be a part of up to 4 rings• The RPL cannot be a shared link• The two RPLs should use different Minimum Time for Activation values to prevent duplicate action causing a loopTable 13-1: Topologies supported by RADWIN Ethernet Ring (Continued)
Protection Switching Chapter 13RADWIN 2000 User Manual Release  2.5.40 13-6Protection SwitchingProtection switching occurs upon failure in the ring.The Ethernet service restoration time depends on the number of hops in the ring. With four hops the Ethernet service is restored in less than 50 ms.In single and dual homed topologies the service restoration may take longer due to the aging time of the external switches. Switches that are immediately aware of routing changes reduce the restoration time.Hardware ConsiderationsEthernet Ring Protection is supported by the IDU-C, IDU-E and PoE.A typical Ring Protection Link consists of an IDU-C or new style IDU-E, a PoE and two ODUs as shown in Figure 13-2. Hence one end of the RPL and of ring controlled links, as shown in Figure 13-2 has to be an IDU. It is recommended to have an IDU at each node to have the flexibility to change the RPL. A ring node is built from two ODUs from adjacent links. The ODUs can be connected to either an IDU or to a PoE device as in Figure 13-2. Port names in the IDU are shown.Figure 13-2: Node with IDU and PoE deviceThe switching function is carried out by the IDU-Cs and IDU-Es, both of which provide Layer 2 support (see Chapter 14).Special Case: 1 + 1 Ethernet RedundancyThe same device may be used to provide economic 1 +1 redundancy for a single link.A 1+1 Ethernet is a ring with two nodes. One of the links is RPL. NoteConnect the switch at the site only to one IDU.
Using RADWIN Manager to Set up a Ring Chapter 13RADWIN 2000 User Manual Release  2.5.40 13-7The equipment in a 1+1 Ethernet installation is as follows:Figure 13-3: 1+1 EthernetFigure 13-4: Using IDU-C or IDU-E with PoEs for the RPLNotice that link content drops from four PoEs plus two switches to two PoEs and two IDU-Cs or IDU-Es.Using RADWIN Manager to Set up a RingCreating a Ring using RADWIN Manager requires two stages:6. Set up each participating link separately, in the usual way7. For each link, run the Configuration wizard to define it as RPL or a Ring LinkHere then, is step 2 in more detail:Note• The Ring uses a VLAN ID for the RPL. It is used to manage the Ring and nothing else; it is completely separate from the management and traffic VLANs referred to elsewhere• A regular Ring Link may be a member of up to four rings and each of their RPL VLAN IDs must be configured
Using RADWIN Manager to Set up a Ring Chapter 13RADWIN 2000 User Manual Release  2.5.40 13-8To integrate a link into an Ethernet Ring:1. Using either the Installation or Configuration wizards, navigate to the Services win-dow and chose the Ring tab.Figure 13-5: Services window with Ring selected2. Click Configure. The Ring definition window is displayed. The default is Indepen-dent Link and is used when the link is not part of any Ring.Figure 13-6: Ring Options3. To configure the link as a regular Rink link, click Rink Link (Non- RPL) and enter the ring LAN VIDs (at least one) to which it belongs and click OK:
Using RADWIN Manager to Set up a Ring Chapter 13RADWIN 2000 User Manual Release  2.5.40 13-9Figure 13-7: Configuring Ring LAN VIDs4. To configure the link as RPL, click Ring Protection Link (RPL) and enter its Ring VID.Figure 13-8: Configuring RPL VIDs5. Enter the minimum times for failure detection and recovery.For dual-homed configurations, where part of the ring goes through the core, if a core segment fails, the core should be allowed to recover before the RPL enters Pro-tection State. Otherwise, it could happen that both the core and the RADWIN ring will switch in parallel. You should therefore, configure a Minimum time for failure detection high enough to take this possibility into account.The Minimum time for recovery is a delay switch to prevent rapid “on-off” fluctu-ations. It functions like a delay switch use to protect electrical devices from rapid “on-off” power fluctuations, which in this context, may lead to potential short term loops.6. Click OK to accept your settings.
Using RADWIN Manager to Set up a Ring Chapter 13RADWIN 2000 User Manual Release  2.5.40 13-10The RPL will be clearly indicated in the RADWIN Manager. In the Link status area on the top left, you will see an Ethernet (Blocked) notice:A Link-Idle message is displayed on the Ethernet Services Bar:When the RPL cuts in as a result of a failure, the “Ethernet (Blocked)” notice disap-pears. The Ethernet Services Bar indicated that the RPL is active:Upon restoration of the broken link, the RPL returns to idle status with the appropri-ate indications on the RADWIN Manager main window.On the status bar for all ring member links, you will see the ring membership indica-tor icon: Caution• Do not configure more than one RPL. If you do, you will break the Ring• If you forget to configure one RPL in a Ring, you will introduce a loop into your network
RADWIN 2000 User Manual Release  2.5.40 14-1Chapter 14VLAN Functionality withRADWIN 2000VLAN Tagging - OverviewVLAN TerminologyBoth the technical literature and the RADWIN Manager use the terms VLAN ID and VID inter-changeably to denote a VLAN identification number.VLAN Background Information on the WEBThe standards defining VLAN Tagging are IEEE_802.1Q and extensions.For general background about VLAN see http://en.wikipedia.org/wiki/Virtual_LAN.Background information about Double Tagging also known as QinQ may be found here: http://en.wikipedia.org/wiki/802.1QinQ.VLAN TaggingVLAN tagging enables multiple bridged networks to transparently share the same physical network link without leakage of information between networks:Figure 14-1: Two network using the same link with tagging
QinQ (Double Tagging) for Service Providers Chapter 14RADWIN 2000 User Manual Release  2.5.40 14-2IEEE 802.1Q is used as the encapsulation protocol to implement this mechanism over Ether-net networks.QinQ (Double Tagging) for Service ProvidersQinQ is useful for Service Providers, allowing them to use VLANs internally in their “transport network” while mixing Ethernet traffic from clients that are already VLAN-tagged.Figure 14-2: Separating client data streams using double taggingThe outer tag (representing the Provider VLAN) comes first, followed by the inner tag. In QinQ the EtherType = 0x9100. VLAN tags may be stacked three or more deep.When using this type of “Provider Tagging” you should keep the following in mind:• Under Provider Tagging, the system double-tags egress frames towards the Provider’s network. The system adds a tag with a VLAN ID and EtherType = 0x9100 to all frames, as configured by the service provider (Provider VLAN ID).• The system always adds to each frame, tags with VLAN ID and EtherType = 0x9100. Therefore,• For a frame without a tag – the system will add a tag with VLAN ID and EtherType = 0x9100 so the frame will have one tag• For a frame with a VLAN tag – the system will add a tag with VLAN ID and EtherType = 0x9100 so the frame will be double-tagged• For a frame with a VLAN tag and a provider tag – the system will add a tag with VLAN ID and EtherType = 0x9100 so the frame will be triple-tagged and so onVLAN UntaggingVLAN Untagging means the removal of a VLAN or a Provider tag.Port FunctionalityThe VLAN functionality is supported by all LAN and SFP ports in the IDU. Each port can be configured how to handle Ethernet frames at the ingress direction (where frames enter the IDU) and at the egress direction (where frame exit the IDU).The configuration is independent at each port.
Port Functionality Chapter 14RADWIN 2000 User Manual Release  2.5.40 14-3Ingress DirectionEgress DirectionTable 14-1: Port settings - Ingress directionTransparent The port ‘does nothing’ with regard to VLANs - inbound frames are left untouched.TagFrames entering the port without VLAN or QinQ tagging are tagged with VLAN ID and Prioritya, which are pre-configured by the user. Frames which are already tagged at ingress are not modified.a. Priority Code Point (PCP) which refers to the IEEE 802.1p priority. It indicates the frame priority level from 0 (lowest) to 7 (highest), which can be used to prioritize different classes of traffic (voice, video, data, etc).Table 14-2: Port settings - Egress directionTransparent The port ‘does nothing’ with regard to VLANs - outbound frames are left untouched.Untag allAll frames are untagged.
Port Functionality Chapter 14RADWIN 2000 User Manual Release  2.5.40 14-4Untag selected VIDsUntags only frames tagged with one of the user defined VIDs. You can define up to eight VIDs per port. Other frames are not modified.Filtered VLAN IDs at egressThis setting allows for mutual filtering of multiple ingress tags not relevant at the egress end:Table 14-2: Port settings - Egress direction (Continued)
VLAN Availability Chapter 14RADWIN 2000 User Manual Release  2.5.40 14-5VLAN AvailabilityVLAN is available for links using either WinLink 1000 or RADWIN 2000 radios. VLAN support requires the use of IDU-Cs or new style IDU-Es.VLAN Configuration Using the RADWIN ManagerProvider taggingWith Provider tagging, the system double-tags egress frames towards the provider’s network. All frames are tagged QinQ with a VLAN ID, which is configured by the service provider (Provider VLAN ID).With this setting, ingress frames which are not tagged with the configured Provider VLAN ID are blocked (filtered).Note: Each port can be configured independently to a tagging mode. However, only a single Provider VLAN ID can be defined per IDU.Provider tagging without filterThis setting functions like Provider tagging. However, all ingress frames are passed through.CautionVLAN IDs are used by RADWIN products in three separate contexts: Management VLAN, Traffic VLAN and Ethernet Ring. It is recommended that you use different VLAN IDs for each context.DisclaimerIf you are not a VLAN expert, please be aware that incorrect VLAN configuration may cause havoc on your network. The facilities described below are offered as a service to enable you to get best value from your RADWIN 2000 links and are provided “as is”. Under no circumstances does RADWIN accept responsibility for network system or financial damages arising from incorrect use of these VLAN facilities.Table 14-2: Port settings - Egress direction (Continued)
Management Traffic and Ethernet Service Separation Chapter 14RADWIN 2000 User Manual Release  2.5.40 14-6Management Traffic and Ethernet Service SeparationYou can define a VLAN ID for management traffic separation. You should configure the sys-tem to prevent conflicts as detailed below.When configured for the default operational mode, a “Provider port” will handle ingress traffic as follows:• Filters frames that are not tagged with the Provider VLAN ID• Removes the Provider double tagTherefore, if a port is configured for management traffic separation by VLAN and as ‘Provider port’, then the received management frames must be double tagged as follows: • The outer tag has to be the Provider’s tag (so the frame is not filtered)• The internal tag has to be management VLAN IDTo avoid mix-ups, best practice is to:• Separate the management and data ports• Define only a data port with Provider functionAll IDU-C and new style IDU-E models have two LAN ports so you can easily separate man-agement and Ethernet service.VLAN Tagging for Ethernet Service: ConfigurationVLAN Configuration is carried out per site. It is up to you to ensure consistency between the link sites. The discussion below is based on Site A however, it also applies to Site B.To set up VLAN tagging for Ethernet service, enter Site Configuration for Site A, choose the Ethernet tab and click the VLAN Configuration... button (Figure 8-15). The following win-dow is displayed:
VLAN Tagging for Ethernet Service: Configuration Chapter 14RADWIN 2000 User Manual Release  2.5.40 14-7Figure 14-3: VLAN tag settingsThe choices for Ingress Mode are - Figure 14-4: VLAN: Ingress modesThe two choices correspond respectively to the two rows of Table 14-1. Choosing Tag causes the VLAN ID and VLAN Priority fields to become available:NoteIf you are using a new style IDU-E, the SFP row will not appear.
VLAN Tagging for Ethernet Service: Configuration Chapter 14RADWIN 2000 User Manual Release  2.5.40 14-8Figure 14-5: VLAN: Ingress mode - setting VLAN ID and PriorityThe choices for Egress Mode are - Figure 14-6: VLAN: Egress modesThe five non-transparent choices correspond respectively to the five rows of Table 14-2 in the order, row 1, 2, 4, 5, 3.The first two choices, Transparent and Untag all require no further action.Untag selected VIDs causes the eight VLAN ID fields to become available:Figure 14-7: Untagging selected VIDsYou may nominate up to eight VIDs for untagging; beyond simple range checking, there is no other validation.Both Provider tagging and Provider tagging without filter enable the Provider parameters fields:Figure 14-8: Provider parametersNoteThroughout this chapter, all VLAN IDs must be between 1 and 4094, inclusive. All VLAN priorities must be between 0 and 6, inclusive. The values entered are range-checked. If for example, you enter a VLAN ID of 4095, then 4094 will be reflected back.
VLAN Tagging for Ethernet Service: Configuration Chapter 14RADWIN 2000 User Manual Release  2.5.40 14-9There is of course only one Provider VLAN ID. It is most likely yours, as the Provider!Filtered VLAN IDs enables you to filter and block only frames tagged with one of the user defined VIDs. You can define up to eight VIDs per port. Other frames are not modified and are forwarded transparently.When you are finished, remember to click OK (Figure 14-3) to save your entries.
RADWIN 2000 User Manual Release  2.5.40 15-1Chapter 15Software UpgradeWhat is the Software Upgrade Utility?The RADWIN Manager provides a Software Upgrade Utility (SWU) to upgrade the software (firmware) of installed ODUs in a network. The update files may be located anywhere acces-sible by the operator.The SWU provides for:• Prior backup of the current files prior to upgrade• Upgrade from a list• Delayed upgrade• Various ODU reset optionsThe default location of the software files is in the installation area, and can be used to restore factory defaults.Upgrading an Installed LinkTo upgrade software for a link:1. In the RADWIN Manager main menu, click Tools | Software Upgrade ... The fol-lowing detached window appearsNoteThe following procedure is generic to all RADWIN radio and GSU products.
Upgrading an Installed Link Chapter 15RADWIN 2000 User Manual Release  2.5.40 15-2Figure 15-1: Software Upgrade Utility - Main windowThe default sites shown in the Software Upgrade list panel belong to the currently link. The list may be empty if you are running the RADWIN Manager “offline”.2. Click Add Site to add additional sites for upgrade.Figure 15-2: Add site optionsClick Add Single Site for one site only:Figure 15-3: Adding a single site for upgradeWarningWhat follows about adding sites manually or from a list file, assumes that all sites to be upgraded are of the same type - either WinLink 1000 or RADWIN 2000. but not both. This will not work with a mixed list.
Upgrading an Installed Link Chapter 15RADWIN 2000 User Manual Release  2.5.40 15-3Enter the IP address of the site, the Community strings (Default: public and net-man, respectively) and then click OK. The site will appear in the Software Upgrade list box. For example if we add the site at IP address 192.168.2.101, the SWU main window of Figure 15-1 looks like this:Figure 15-4: Single site added for upgradeThe list can be cleared using the Clear All button.As an alternative to adding sites one at a time, you can add sites from a prepared list using the Add from File option in Figure 15-2. The list has the following format:<IP address>,<Read-Only community>,<Read-Write community>Here is an example:192.168.1.101,public,netman192.168.1.102,public,netman192.168.2.101,public,netman192.168.2.102,public,netman3. Having created an update list, click Upgrade Package to chose the relevant files. The default files are located in the SWU subdirectory in the RADWIN Manager instal-lation area. They are currently named SWU_1k.swu and SWU_2k.swu. You may have to find them elsewhere, depending on your system.4. You make limited changes to the list by right-clicking any line:Figure 15-5: Software Upgrade site options
Upgrading an Installed Link Chapter 15RADWIN 2000 User Manual Release  2.5.40 15-45. To back up your existing system, check Backup device software check-box. Then click the   button for a standard file dialog. The default location is the My Docu-ments directory on the managing computer or the last backup directory you used.6. In addition to the previous step, you may opt to perform a delayed upgrade. Check the Delayed Upgrade box, and enter the date and time for the delayed upgrade.7. The radio buttons on the right determines how your sites should be reset. Bear in mind that on the one hand, a reset involves a service interruption, but on the other hand, the software upgrade will not become effective until after the reset is carried out.8. Click Start Upgrade to commence the process. For an immediate upgrade you will be able to observe the upgrade progress from the green progress bars:Figure 15-6: Software upgrade in progress - Note the stop buttonFigure 15-7: Software upgrade completed successfully9. Click Close to exit.10. If you requested a delayed upgrade, a notice like this will appear in the SWU title bar:NoteThe backup here is the same as that in page 8-32, and serves the same purpose. It provides a fallback if the upgrade proves problematic.
Software Update for GSUs Chapter 15RADWIN 2000 User Manual Release  2.5.40 15-5Software Update for GSUsAll GSUs in a distributed site can be updated simultaneously. Use an IP list as described above. CautionIf one or both sites fail to update, a warning notice will be displayed.If one site of a link updates but the other fails, you should correct the problem and update the second site as soon as possible. If you do not, following the next reset of the updated site, you could experience a link software mismatch which may affect service. See page 9-3 for details.
RADWIN 2000 User Manual Release  2.5.40 16-1Chapter 16FCC/IC DFS InstallationProcedureFCC/IC 5.4/5.3 GHz Links: BackgroundThe FCC/IC regulation for 5.4/5.3 GHz allows unlicensed wireless data equipment, provided that it does not interrupt radar services. If radar activity is detected, the equipment must automatically change frequency channel. This feature is termed Dynamic Frequency Selection (DFS). According to the standard, a channel with active radar is prohibited from use for 30 minutes. Before using a channel for transmission, the radio equipment must probe it for radar signals for a period of 60 seconds.RADWIN radio products support DFS as well as ACS.An immediate consequence of the FCC/IC regulation for 5.4/5.3 GHz is that the standard method of link installation using a single default fixed installation channel, cannot be used.Instead of the installation procedure of Chapter 5, a link activation method is used.The ODUs are either supplied from the factory ready for use at 5.4 GHz or 5.3 GHz FCC/IC or alternatively, they can be set up for these bands using the RADWIN Manager.FCC/IC 5.4/5.3 GHz Link ActivationTo Activate a FCC/IC 5.4/5.3 GHz Link:1. Install RADWIN Manager software as usual.2. Connect the PC to the IDU-ODU pair to be used as the local site.3. Run the RADWIN Manager and log in as Installer. You will see the following window:NoteThe following procedure is generic to all relevant RADWIN radio products. What you see on your running RADWIN Manager may differ in some details from the screen captures used to illustrate this chapter.
FCC/IC 5.4/5.3 GHz Link Activation Chapter 16RADWIN 2000 User Manual Release  2.5.40 16-2Figure 16-1: Activating an ODU - Inactive linkWhen the Manager Main Screen is displayed it appears with the Link Status label red and showing Inactive.4. Click Site:Location | Air Interface for the logged in site.5. The Air Interface dialog box opens:Figure 16-2: Air Interface dialog box6. Enter the Link ID and note it for use with the second site of the link.7. Check the Master radio button.
FCC/IC 5.4/5.3 GHz Link Activation Chapter 16RADWIN 2000 User Manual Release  2.5.40 16-38. Click OK. The following window appears:Figure 16-3: The local ODU after activation - ProbingNotice that the Link ID is shown in the Link details pane (circled).9. Repeat the above procedure for the remote ODU, ensuring that in the Air Interface window, that you enter exactly the same Link ID, but this time that you check the Slave radio button.If both ODUs are powered up, after a minute or so a link will be established. If you are still connected to the remote site (from the previous steps), the window of Figure 16-3 will look like this:
FCC/IC 5.4/5.3 GHz Link Configuration Chapter 16RADWIN 2000 User Manual Release  2.5.40 16-4Figure 16-4: Both sites activated and awaiting configurationFCC/IC 5.4/5.3 GHz Link ConfigurationThe Configuration procedure may be carried out from either site using the Configuration wiz-ard as shown in Chapter 7. The only difference is in the Channel Settings window:NoteBoth sites in a FCC/IC 5.4/5.3 GHz Link must be configured identically.
FCC/IC 5.4/5.3 GHz Link Configuration Chapter 16RADWIN 2000 User Manual Release  2.5.40 16-5Figure 16-5: Channel Select dialog box - ACS permanently enabledUpon completion of the wizard, the Site configuration dialogs can be used in the usual way. Once operational, the RADWIN Manager window is the same as for other radio equipment models.Here is the RADWIN Manager main window upon completion of the wizard:NoteACS cannot be disabled.
FCC/IC 5.4/5.3 GHz Link Configuration Chapter 16RADWIN 2000 User Manual Release  2.5.40 16-6Figure 16-6: FCC/IC 5.4/5.3 GHz operational
RADWIN 2000Broadband Wireless Transmission SystemUSER MANUALRELEASE 2.5.40Part 4: Field InstallationTopicsUM 2000-2540/02.11
RADWIN 2000 User Manual Release  2.5.40 17-1Chapter 17Pole and Wall InstallationODU Mounting Kit ContentsTable 17-1: Bill of Materials: ODU mounting kitItem QtyLarge Clamp (see Figure 17-1)1Small Clamp (see Figure 17-2)1Arm (see Figure 17-3)1Screw hex head M8x40 4Screw hex head M8x70 2Washer flat M8 4Washer spring M8 3M8 Nuts 2Figure 17-1: Large Clamp Figure 17-2: Small Clamp Figure 17-3: Arm
Mounting an ODU on a Pole Chapter 17RADWIN 2000 User Manual Release  2.5.40 17-2Mounting an ODU on a PoleFigure 17-4: Mounting on a pole
Mounting an ODU on a Wall Chapter 17RADWIN 2000 User Manual Release  2.5.40 17-3Mounting an ODU on a WallFigure 17-5: Mounting on a Wall
Mounting an External Antenna Chapter 17RADWIN 2000 User Manual Release  2.5.40 17-4Mounting an External AntennaOptional external antennas can be mounted on a pole. The external mounting kit varies according to the specific antenna model.Mounting a Connectorized ODU HorizontallyWhat follows applies to both WinLink 1000 and RADWIN 2000 with obvious differences.An ODU may be mounted horizontally as shown in Figure 17-6.To mount an ODU horizontally, observe the following cautions:1. To ensure your warranty rights for horizontally installed ODUs, make sure that the four ports ANT1, ANT2, HSS and ODU are firmly secured or moisture sealed with the supplied caps.2. Further, ensure that cables are connected using a “water nose” as shown in Figure 17-6.Figure 17-6: Mounted ODUs with correct “water nose”Do not do this:Figure 17-7: Incorrectly mounted ODU (No “water nose”)3. If you attach an external PoE device near the ODU, the same considerations apply.
RADWIN 2000 User Manual Release  2.5.40 18-1Chapter 18Lightning Protection andGrounding GuidelinesMeticulous implementation of the guidelines in this chapter will provide best protection against electric shock and lightning.The RADWIN Lightning Protection System consists of the following components:• Grounding for the antenna coax cable• Grounding for each IDU and ODU• External Primary Surge Suppressor units and grounding for the outdoor cable• Internal ESD protection circuits over the Power/Telecom linesGrounding for Antenna CableA Grounding Kit must be connected to the coax antenna cable and reliably grounded. The grounding kit is an Andrew Type 223158-2 (www.andrew.com). See Figure 18-1 below.Warning100% protection is neither implied nor possible.NoteThis chapter is at best a guide. The actual degree of lightning protection required depends on local conditions and regulations.
Grounding for Indoor/Outdoor Units Chapter 18RADWIN 2000 User Manual Release  2.5.40 18-2Figure 18-1: Grounding antenna cablesGrounding for Indoor/Outdoor UnitsODU GroundingRADWIN Lightning Protection System uses a Shielded CAT-5e cable to interconnect the Out-door (ODU) and Indoor (IDU) units. However, this shielding does not provide a good lightning discharge path, since it can not tol-erate the high Lightning Current surges.To provide an alternate Lightning Discharge path, the ODU and antenna grounding posts should be connected to ground point by a 10 AWG short copper wire.The device should be permanently connected to ground.
IDU Grounding Chapter 18RADWIN 2000 User Manual Release  2.5.40 18-3IDU GroundingThe IDU’s grounding post should be connected to the internal ground point, using a ground-ing wire of at least 10 AWG. The grounding wire should be connected to a grounding rod or the building grounding system.The device should be permanently connected to ground.External Lightning Surge Suppressors and GroundingA Grounding Kit and Surge Arrestor Unit must be located near the ODU and properly grounded as illustrated in Figures 18-2 and 18-3 below:
External Lightning Surge Suppressors and Grounding Chapter 18RADWIN 2000 User Manual Release  2.5.40 18-4Figure 18-2: Grounding a typical pole installation
External Lightning Surge Suppressors and Grounding Chapter 18RADWIN 2000 User Manual Release  2.5.40 18-5Figure 18-3: Grounding a typical wall installationThe next figure shows a close-up of the rear of grounded ODU:Figure 18-4: ODU Surge Suppressor and grounding
External Lightning Surge Suppressors and Grounding Chapter 18RADWIN 2000 User Manual Release  2.5.40 18-6The Transtector protection circuits shown in Figure 18-5 below, utilize silicon avalanche diode technology. The unit consists of an outdoor rated NEMA 3R type enclosure with easy mounting flanges, ground stud attachment and easy wiring.The ALPU-POE features RJ-45 protection circuits for the ODU-IDU data pairs (pins 1,2 & 3,6) and DC power (pins 4,5 & 6,7 with the pairs bonded).The unit is designed to be wall mounted. An optional set of bracket is available from the man-ufacturer to allow a wide range of pole mount applications. A dedicated ground stud is pro-vided inside the unit that must be bonded to the nearest grounding system (or Master Ground bar) for proper surge protection.The system wiring is installed with RJ-45 type connectors that can feed directly into the chas-sis without having to cut, splice or route through awkward strain relief holes.Figure 18-5: Transtector’s Surge SuppressorTo mount the lightning protection devices:1. Mount the device as close to the ODU as possible. Mount the unit so that the cable connectors are at the bottom (to prevent water from penetrating), with the strain reliefs facing the ground.2. Remove the cover by unscrewing the front of the unit.3. Mount the unit to an outside surface using the two mounting holes.4. Connect the ODU-IDU cable using the RJ-45 jack.5. Connect one cable between the ODU and the suppressor using an RJ-45 jack.6. Connect the suppressor’s ground stud to a grounding point. Use the appropriate wire gauge and type, keeping the wire as short as possible, less than 1m (3’), between the stud and the site grounding point.7. Replace the cover.NoteThere may also be regulatory requirements to cross bond the ODU-IDU CAT-5e cable at regular intervals up the mast. This may be as frequent as every 10 meters (33 feet).
External Lightning Surge Suppressors and Grounding Chapter 18RADWIN 2000 User Manual Release  2.5.40 18-7A second Surge Arrestor Unit should be mounted at the building entry point and must be grounded, as shown in Figure 18-3 above.To mount the lightning protection at the building entry point:1. Mount the device outside the building, located as near as possible to the entrance of the CAT-5e ODU-IDU cable. Mount the unit so that the cable connectors are at the bottom (to prevent water from penetrating), with the strain reliefs facing the ground.2. Remove the cover by unscrewing the front of the unit.3. Mount the unit to an outside surface using the two mounting holes.4. Connect the ODU-IDU cable using the RJ-45 jack.5. Connect one cable between the IDU and the suppressor using an RJ-45 jack.6. Connect the suppressor’s ground stud to a grounding point. Use the appropriate wire gauge and type, keeping the wire as short as possible, less than 1m (3’), between the stud and the site grounding point.7. Replace the coverFigure 18-6: Surge Suppressor and grounding at building entry point
Internal ESD Protection circuits Chapter 18RADWIN 2000 User Manual Release  2.5.40 18-8Internal ESD Protection circuitsRADWIN equipment is designed to meet the ETSI/FCC/Aus/NZ/CSA EMC and Safety require-ments. To fulfill these requirements, the system's Telecom lines at the ODU/IDU are Trans-former-isolated and include internal ESD (Electro-Static-Discharge) Protection circuits.
RADWIN 2000 User Manual Release  2.5.40 19-1Chapter 19Preloading an ODU withan IP AddressWhy this is Needed?All ODUs supplied by RADWIN come pre-configured with an IP address of 10.0.0.120. For use in a network, the ODUs must be configured with suitable static IP addresses. The method for doing this under office conditions is set out in Chapter 5.There are two situations under which ODUs may need to be pre-loaded with an IP address prior to installation to a link:• Changing an individual ODU in the field• Preparing a large number of ODUs in a warehouse prior to deployment in the field, according to a network installation plan.This chapter explains how do this.Required EquipmentThe minimal equipment required to pre-load an ODU with an IP address is:• Laptop computer (managing computer) satisfying the requirements of Table 4-1• An installed copy of the RADWIN Manager• A PoE device• A crossed Ethernet LAN cable• An IDU-ODU cable• If you have connectorized ODUs, two N-type RF terminatorsCautionDo not carry out this procedure using a multi homed managing computer also connected to a network. It will flood the network with broadcast packets. Further, it will throw any other links on the network into Installation mode.
The procedure Chapter 19RADWIN 2000 User Manual Release  2.5.40 19-2The procedureTo Preolad an ODU with an IP address:1. Using the IDU-ODU cable, connect the PoE device to the ODU, ensuring that the cable is plugged into the PoE port marked P-LAN-OUT.2. For connectorized ODUs, screw the RF terminators into the two antenna ports.3. Connect the Poe device to AC power.4. Using a crossed LAN cable, connect the LAN-IN port of the PoE device to the Ethernet port of the managing computer. The ODU will commence beeping at about once per second, indicating correct operation.5. Launch the RADWIN Manager.6. At the log on window, choose Local Connection.Figure 19-1: Log on Window for Local Connection7. Enter the default password, admin. After a few moments, the RADWIN Manager main window appears:NoteThe following procedure is generic to all RADWIN radio products. What you see on your running RADWIN Manager may differ in some details from the screen captures used to illustrate this chapter.WarningA powered up ODU emits RF radiation from the antenna port (or connected antenna). When working with a powered up connectorized ODU, always use RF terminators.For an ODU with an integrated antenna, ensure that the antenna is always directed away from other people.
The procedure Chapter 19RADWIN 2000 User Manual Release  2.5.40 19-3Figure 19-2: Opening RADWIN Manager window prior to installation8. Click the un-grayed Site:Location button. The following dialog window appears:Figure 19-3: Configuration Dialog Box9. Click the Management item in the left hand panel. The following window is pre-sented:
The procedure Chapter 19RADWIN 2000 User Manual Release  2.5.40 19-4Figure 19-4: Management Addresses - Site Configuration dialog box10. Enter the IP Address, Subnet Mask and Default Gateway as requested. For example, the ODU used here is to be configured as follows:Figure 19-5: ODU with IP Addressing configured11. Click OK. You are asked to confirm the change:Figure 19-6: Confirmation of IP Address change
The procedure Chapter 19RADWIN 2000 User Manual Release  2.5.40 19-512.  Click Yes to accept the change. After about half a minute the changes will be reg-istered in the ODU. On the left hand panel of the main window, you will see the new IP configuration for the ODU.Figure 19-7: Main Window after IP Address change13. Click Cancel to leave the open Management dialog. You may now exit the RADWIN Manager, or connect to another ODU. If you choose to connect to another ODU, after about a minute, the main window of the RADWIN Manager will revert to that shown in Figure 19-2 above. In any event, power down the changed ODU; your changes will take effect when you power it up again.NoteSome additional things you may want to do now:•Go to Site Installation | Air Interface. You can enter a Link ID and change the Installation Frequency and Channel Bandwidth.• If you log on as Installer, you can change the default band (Chapter 20).NoteDon’t forget to remove the RF terminators from a connectorized ODU after powering it down.
Tip: How to Recover a Forgotten ODU IP Address Chapter 19RADWIN 2000 User Manual Release  2.5.40 19-6Tip: How to Recover a Forgotten ODU IP AddressIf you have an ODU with lost or forgotten IP address, use the above procedure to log on to it using Local Connection. The IP address will appear in the left hand status area:Figure 19-8: Existing IP address displayed after log-on with Local Connection
RADWIN 2000 User Manual Release  2.5.40 20-1Chapter 20Changing the FactoryDefault BandWhy this is NeededAll ODUs supplied by RADWIN come with pre-configured with a factory default product-dependent band according to the ODU part number.For ODUs supporting Multi-band, it may be changed using the procedure in this chapter. The procedure is generic, applying to all ODUs with the Multi-band feature.Required EquipmentThe minimal equipment required to change an ODU default band is:• Laptop computer (managing computer) satisfying the requirements of Table 4-1.• An installed copy of the RADWIN Manager• A PoE device• A crossed Ethernet LAN cable• An IDU-ODU cableThe procedureTo change the factory default band:1. Using the IDU-ODU cable, connect the PoE device to the ODU, ensuring that the cable is plugged into the PoE port marked P-LAN-OUT.Caution• If for some reason the default band needs to be changed, it should be done before link installation.• Use of an incorrect band may be in violation of local regulations.NoteThe following procedure is generic to all relevant RADWIN radio products. What you see on your running RADWIN Manager may differ in some details from the screen captures used to illustrate this chapter.
The procedure Chapter 20RADWIN 2000 User Manual Release  2.5.40 20-22. Connect the Poe device to AC power.3. Using a crossed LAN cable, connect the LAN-IN port of the PoE device to the Ethernet port of the managing computer. The ODU will commence beeping at about once per second, indicating correct operation.4. Launch the RADWIN Manager.5. Log on as Installer.Figure 20-1: Becoming Installer6. Enter the default password, wireless. After a few moments, the RADWIN Manager main window appears:
The procedure Chapter 20RADWIN 2000 User Manual Release  2.5.40 20-3Figure 20-2: Opening RADWIN Manager window prior to band change (default circled)7. Click Tools | Change Band. The following window appears:Figure 20-3: Change Band dialog8. Click the band required:NoteThe bands appearing in Figure 20-3 are product dependent. To see which bands are available for your product, check your product Inventory (see Figure 8-8) and then consult RADWIN Customer Support.
The procedure Chapter 20RADWIN 2000 User Manual Release  2.5.40 20-4Figure 20-4: A different band selected9. The Change Band warning is displayed. Click Yes to continue.Figure 20-5: Change Band confirmationThe change, which may take some time, is carried out:The result is reflected in the RADWIN Manager main window:
Changing Band for DFS Chapter 20RADWIN 2000 User Manual Release  2.5.40 20-5Figure 20-6: Main Window after band change - new band circledChanging Band for DFSChanging to a DFS band is similar to the foregoing procedure.As soon as you establish a link using a DFS band, you are offered Configuration only in the main menu. Installation mode is disabled.Special Products or Features: Entering a License KeyIf you go to the Operations window as Installer (Figure 20-7), you will see a provision for entering a license key. Should you ever require such a key, the procedure is as follows:To enter a License key:1. Log on as Installer (as for the previous procedure).2. Click the Site:Location tool bar button from the main tool bar.NoteIf you carry out this operation on a link, the band is effective on both sites and you are placed in installation mode.
Provisions for Licensed 3.X and 2.5 GHz Bands Chapter 20RADWIN 2000 User Manual Release  2.5.40 20-6Figure 20-7: Using the Operations window to enter a license key3. Enter your license key and click Activate.4. When it is accepted, click Cancel.Provisions for Licensed 3.X  and 2.5 GHz BandsOverview3.X BandsThe new RADWIN 2000 C and RADWIN 2000 X series add additional bands in the 3.X GHz range to those in Release 2.5.00. The new supported bands fall into two categories: The first category consists of those falling under the ubiquitous FCC, IC or ETSI regulation. The second category is referred to  as RADWIN Universal bands. These bands are known to be regulated but the numerous combinations of regulation and location preclude specific support.Release 2.5.40 introduces support for the band 3.3-3.8 GHz as follows:• FCC part 90 subpart Z and IC RSS-197 supporting 3.650-3.700 GHz• 3.650 -3.675 GHz in Restricted mode• Hardware ready for the Unrestricted Mode band operating in all 50 MHz of the 3.650-3.700 GHz band• IC RSS-192 supporting 3.475 – 3.650 GHz• ETSI 3.4 -3.7 GHz split into three sub-bands, 3.650-3.675 GHz, 3.475-3.650 GHz and  3.590-3.710 GHzNoteLicense keys, where appropriate, are obtainable from RADWIN Customer Support.
Terminology Recap Chapter 20RADWIN 2000 User Manual Release  2.5.40 20-7• RADWIN Universal 3.300-3.800 GHz.Integrated and connectorized products are available. All of them are multiple band with the default band being 3.650-3.675 GHz other than the ETSI 3.4 - 3.7 GHz models.The new products may be operated under 5, 10 and 20 MHz channel bandwidths and are broadly compatible with the full feature set of RADWIN 2000.To meet regulatory requirements, a somewhat different procedure is required to set up links using these bands.2.5GHz Bands for BRS/EBSThe rationale for these bands and relevant details are described in Chapter 24. The installa-tion method ids the same as for other licenced FCC bands as described below.Terminology Recap•3.X Universal bands refer to RADWIN Universal bands as described above•3.X or 3.X GHz refers to the frequency range 3.300 – 3.800GHz•A 3.X ODU is an ODU pre configured to operate in the 3.X GHz licensed bands•A 3.X Link in a RADWIN 2000 link using a pair of 3.X ODUs•High Resolution Bands - Channel minimum step is 250 KHz. Applies to 3.475 - 3.650 GHz IC RSS-192, 3.4 -3.7 GHz ETSI and the 3.3 - 3.8 GHz Universal band.•Low Resolution Bands - Channel minimum step is 1 MHz. Applies to FCC regula-tions in the 3.650-3.675 GHz band.•Inactive Mode - An ODU  is powered up, in communication with a managing com-puter but not transmitting. It is required where regulation does not permit the use of RADWIN’s default Installation Mode frequency and channel bandwidth. The ODU may transmit using the licensed or registered band, channel bandwidth and permitted Tx power.•Regular Mode - The usual default Installation ModeRegulatory Considerations for 3.650-3.675 GHz FCC/IC part 90 sub part ZRestricted ModeThe band is supported in accordance with 3.650-3.675 FCC/IC part 90 subpart Z:RADWIN Ltd. conforms to FCC DA 07-4605 (November 14, 2007) FCC-certified with FCC-ID: Q3KRW2030 and supporting the following equipment requirements:“Restricted contention protocols can prevent interference only with other devices incorporat-ing the same or similar protocols. Equipment using a restricted protocol can operate only on the lower 25 megahertz (3650-3675 MHz)."
Regulatory Considerations for 3.650-3.675 GHz FCC/IC part 90 sub part Z Chap-RADWIN 2000 User Manual Release  2.5.40 20-8Transmission power optionsTable 20-1shows the extent of compliance by RADWIN 2000 C products to FCC/IC power limits, having regards to antenna type and transmission power options.Higher Transmission Power Options and Restrictions:Table 20-2 defines the maximum transmission power and EIRP limits for the specified fre-quency and channel bandwidths.It specifies the power limits to be used by the operator when assigning center frequencies.Table 20-1: FCC/IC compliance by antenna and transmission powerMeasuredFrequency PowerAntenna Nominal CBWLow Center Frequency Channel [MHz]High Center Frequency Channel [MHz]Max Conducted Tx Power per Pole [dBm]Total Conducted Max Tx Power [dBm]Max EIRP [dBm]21dBi INT5 MHz 3653 3672 11.14 14.14 35.1410 MHz 3655 3670 14.46 17.46 38.4620 MHz 3660 3665 17.36 20.36 41.3621dBi EXT (22dBi-1dB feeder)5 MHz 3653 3672 11.14 14.14 35.1410 MHz 3655 3670 14.46 17.46 38.4620 MHz 3660 3665 17.36 20.36 41.3624dBi EXT (25 -1dB feeder loss)5 MHz 3653 3672 8.65 11.65 35.6510 MHz 3655 3670 11.36 14.36 38.3620 MHz 3660 3665 13.73 16.73 40.73Table 20-2: Higher Transmission Power LimitsNominalCBWLow Center Frequency Channel [MHz]High Center Frequency Channel [MHz]Max Conducted Tx Power per Pole [dBm]Total Conducted Max Tx Power [dBm]Max EIRP[dBm]5 MHz 3653 3672 15.60 18.60 35.6010 MHz 3655 3670 18.69 21.69 38.693656 3669 22.00 25.00 38.5020 MHz 3660 3665 21.18 24.18 41.183661 3664 22.60 25.60 39.10
Band Splitting for ETSI 3.4 - 3.7GHz Chapter 20RADWIN 2000 User Manual Release  2.5.40 20-9Availability Summary for FCC/IC and Universal 3.X GHzBand Splitting for  ETSI 3.4 - 3.7GHzThe ETSI 3.4 - 3.7GHz band is split into three sub-bands reflecting the different Max Tx Power allowed in each one. The details are shown in below:Using he RADWIN Manager to set up a 3.X  or BRS LinkInactive and Active ModeLow Resolution Band 3.X ODUs may be installed and configured in the usual way.What follows applies to High Resolution Band ODUs.To ensure compliance with the relevant license, 3.X ODUs for IC, ETSI and Universal must be configured from an inactive mode where the ODU is powered up, in communication with a managing computer but not transmitting.Table 20-3: Availability for FCC/IC and Universal 3.X GHzProducts series Occupied BandGHz Regulation Mode Channel Bandwidth MHzMax Tx Power dBmFrequency StepKHzRADWIN 2000 C3.650-3.675  FCC/IC Regular5, 10, 20 25 10003.475-3.650  IC Inactive 2503.300-3.800 Universal UnlimitedRADWIN 2000 X3.650-3.675  FCC/IC Regular525 10003.475-3.650  IC Inactive 2503.300-3.800 Universal UnlimitedTable 20-4: Band split for ETSI 3.4-3.7GHzProducts series Occupied Sub-Band GHzCenter Frequency GHz Mode Channel Bandwidth MHzMax Tx Power dBmFrequency Step KHzRADWIN 2000 C3.403-3.490 3.413-3.480Inactive 5, 10, 20162503.470-3.6103.480-3.60023(†)3.590-3.7103.600-3.700 25(‡)RADWIN 2000 X3.403-3.490 3.413-3.480Inactive 5162503.470-3.6103.480-3.60023(†)3.590-3.7103.600-3.700 25(‡)Note(†) The 3.480 GHz frequency is overlaped, occuring in two different bands as shown. If you wish to use the 3.480 GHz frequency, you should set Max TX Powerto 16 dBm.(‡) The 3.600 GHz frequency is overlaped, occuring in two different bands as shown. If you wish to use the 3.600 GHz frequency, you should set Max TX Powerto 23 dBm.
Using he RADWIN Manager to set up a 3.X or BRS Link Chapter 20RADWIN 2000 User Manual Release  2.5.40 20-10Setting up a link is a two stage procedure:1. Activate the ODUs by individually by configuring the band, frequency and channel band-width for the license2. Complete link configuration in the usual wayTo set up a 3.X or BRS ODU:1. Log on to it as Installer (Operator sufficient for ETSI) and set the IP address as shown in Chapter 19.2. Navigate to Site:Location|Air Interface and enter the Link ID for the ODU.3. Click OK to dismiss the Site Configuration window. Answer Yes to the following popup message:4. For ETSI models, skip to step 7 below. For all others, navigate to Tools|Change Band. The following window is displayed:5.  Choose the required band. For illustration, we will choose the IC band.6. Click OK to continue and accept the notification message which appears:
Using he RADWIN Manager to set up a 3.X or BRS Link Chapter 20RADWIN 2000 User Manual Release  2.5.40 20-11After a few seconds, the ODU goes into inactive mode:7. Activate the ODU by navigating to Site:Location|Air Interface:
Using he RADWIN Manager to set up a 3.X or BRS Link Chapter 20RADWIN 2000 User Manual Release  2.5.40 20-128. Choose a frequency from the drop down list:9. Enter Installation Mode and confirm your choice:10. After a few moments of processing, you may click OK to dismiss the Site Configura-tion window. The ODU is now in normal Installation Mode:
Using he RADWIN Manager to set up a 3.X or BRS Link Chapter 20RADWIN 2000 User Manual Release  2.5.40 20-1311.  Repeat the above procedure for the second ODU in the link, ensuring that the Link ID is entered correctly and the same band is chosen.12. From this point, you may install both ODUs in the field according to the procedures in this User Manual.
RADWIN 2000 User Manual Release  2.5.40 21-1Chapter 21Link Budget CalculatorOverviewThe Link Budget Calculator is a utility for calculating the expected performance of the RAD-WIN 2000 wireless link and the possible configurations for a specific link range.The utility allows you to calculate the expected RSS of the link, and find the type of services and their effective throughput as a function of the link range and deployment conditions.User InputYou are required to enter or choose the following parameters. Depending on the product, some of the parameters have a default value that cannot be changed. • Band, which determines frequency and regulation• Channel Bandwidth• Tx Power (maximum Tx power per modulation is validated)• Antenna Type (cannot be changed for ODU with integrated antenna)• Antenna Gain per site (cannot be changed for integrated antenna)• Cable Loss per site (cannot be changed for integrated antenna)• Required Fade Margin• Rate (and Adaptive check box)• Service Type• Required RangeLink Budget Calculator Internal DataFor each product (or Regulation and Band) the calculator stores the following data required for link budget calculations:• Maximum Transmit power (per modulation)• Receiver Sensitivity (per modulation) for Ethernet service and for TDM services at var-ious BER• Maximum linear input power (used to calculate minimum distance)• Antenna gain and cable loss for ODU with integrated antenna• Available Channel Bandwidths
Calculations Chapter 21RADWIN 2000 User Manual Release  2.5.40 21-2CalculationsEIRPExpected RSS and Fade Marginwhere:Site A is the transmitting siteSite B is the receiving sitePathLoss is calculated according to the free space model,where Sensitivity is dependent on air-rate.Min and Max RangeMinRange is the shortest range for which   per air-rate.MaxRange (with Adaptive checked) is the largest range for which , at the highest air-rate for which this relationship is true. In a link with adaptive rate this will be the actual behavior. MaxRange (for a given air-rate) is the largest range for which .ServiceThe Ethernet and configured TDM trunks throughput is calculated according to internal prod-uct algorithms.AvailabilityThe Service Availability calculation is based on the Vigants Barnett method which predicts the downtime probability based on a climate factor (C factor).EIRP TxPower AntennaGainSiteA CableLossSiteA–+=ExpectedRSS EIRP PathLoss AntennaGainSiteB CableLossSiteB–+–=PathLoss 32.45 20 frequencyMHz20 RequiredRangeKm10log+10log+=ExpectedFadeM inarg ExpectedRSS Sensitivity–=ExpectedRSS MaxInputPowerExpectedRSS SensitivityExpectedRSS Sensitivity RequiredFadeM inarg+Availability16–107–CfactorfrequencyGHzRequiredRangeKM310ExpectedFadeM inarg–10------------------------------------------------------------=
Antenna Height Chapter 21RADWIN 2000 User Manual Release  2.5.40 21-3Antenna HeightThe recommended antenna height required for line of sight is calculated as the sum the Fresnel zone height and the boresight height. See About the Fresnel Zone below. Using the notation of Figure 21-1 below, splitting ExpectedRange into d1 + d2, the Fresnel zone height at distance d1 from the left hand antenna, is given byFor the most conservative setting, we take the mid-point between the antennas, setting which gives simplifying to  .The boresight clearance height is calculated as:where .About the Fresnel ZoneThe Fresnel zone (pronounced "frA-nel", with a silent “s”) is an elliptically shaped conical zone of electromagnetic energy that propagates from the transmitting antenna to the receiving antenna. It is always widest in the middle of the path between the two antennas.0.6300frequencyGHz----------------------------------- d1d2d1d2+-----------------------------------------------------------d1d2ExpectedRange2-----------------------------------------==0.6300frequencyGHz----------------------------------- ExpectedRange2----------------------------------------- 2ExpectedRange2----------------------------------------- ExpectedRange2-----------------------------------------+--------------------------------------------------------------------------------------------0.52 ExpectedRangefrequencyGHz-----------------------------------------R2Mean ExpectedRange2----------------------------------------- 2+RMean–RMean 6367.4425Km=
About the Fresnel Zone Chapter 21RADWIN 2000 User Manual Release  2.5.40 21-4 Figure 21-1: Fresnel zoneFresnel loss is the path loss occurring from multi-path reflections from reflective surfaces such as water, and intervening obstacles such as buildings or mountain peaks within the Fresnel zone.Radio links should be designed to accommodate obstructions and atmospheric conditions, weather conditions, large bodies of water, and other reflectors and absorbers of electromag-netic energy.The Fresnel zone provides us with a way to calculate the amount of clearance that a wireless wave needs from an obstacle to ensure that the obstacle does not attenuate the signal.There are infinitely many Fresnel zones located coaxially around the center of the direct wave. The outer boundary of the first Fresnel zone is defined as the combined path length of all paths, which are half wavelength (1/2 ) of the frequency transmitted longer than the direct path. If the total path distance is one wavelength (1 ) longer than the direct path, then the outer boundary is said to be two Fresnel zones. Odd number Fresnel zones reinforce the direct wave path signal; even number Fresnel zones cancel the direct wave path signal.The amount of the Fresnel zone clearance is determined by the wavelength of the signal, the path length, and the distance to the obstacle. For reliability, point-to-point links are designed to have at least 60% of the first Fresnel zone clear to avoid significant attenuation.The concept of the Fresnel zone is shown in Figure 21-1 above. The top of the obstruction does not extend far into the Fresnel zone, leaving 60% of the Fresnel zone clear; therefore, the signal is not significantly attenuated.For more about Fresnel zone, see http://en.wikipedia.org/wiki/Fresnel_zone.
Running the Link Budget Calculator Chapter 21RADWIN 2000 User Manual Release  2.5.40 21-5 Running the Link Budget CalculatorThe Link Budget Calculator is supplied on the RADWIN Manager CD. It may be run stand-alone from the CD or from the RADWIN Manager application.To run the Link Budget Calculator from the CD:1. Insert the RADWIN Manager CD into the drive on the managing computer. In the window which opens, click the Link Budget Calculator option.2. If the CD autorun application does not start by itself, then point your browser toZ:\RADWIN\Setup\DATA\Link Budget Calculator.htmwhere Z should be replaced with your own CD drive name.To run the Link Budget Calculator from the RADWIN Manager:• Choose Help | Link Budget Calculator from the main menu of the RADWIN Man-ager as in the following figure:Figure 21-2: Accessing the Link Budget CalculatorHowever invoked, your browser displays the following page:Figure 21-3: Link Budget window
Running the Link Budget Calculator Chapter 21RADWIN 2000 User Manual Release  2.5.40 21-6To use the Link Budget Calculator for RADWIN 2000:1. Choose a band from the drop-down list.Figure 21-4: Band selector2. Chose the relevant RADWIN 2000 series.Note• Microsoft Internet Explorer users may see a warning message like this:• Click the yellow bar and follow the instructions to allow blocked con-tent.
Running the Link Budget Calculator Chapter 21RADWIN 2000 User Manual Release  2.5.40 21-7Figure 21-5: RADWIN 2000 series selector3. Choose the Channel Bandwidth.Figure 21-6: RADWIN 2000 Channel Bandwidth selector4. For a collocated link choose the RFP. Use the Help button to the right of the RFP selection box for help:
Running the Link Budget Calculator Chapter 21RADWIN 2000 User Manual Release  2.5.40 21-8Figure 21-7: RFP SelectorFigure 21-8: RFP Selection GuideFor collocated RADWIN 2000 products, you may only use RFP B or E.5. Enter the radio details. Note that Rate is chosen from a drop-down list:
Running the Link Budget Calculator Chapter 21RADWIN 2000 User Manual Release  2.5.40 21-9Figure 21-9: Rate selectorThe Rate shown, defines the air-interface rate in Mbps. The system operates in TDD mode and has the overhead of the air-interface protoco.l Thus, the Ethernet actual throughput is provided by the Ethernet Rate.The Fade margin is the minimum required for line-o- sight (LOS) conditions. For degraded link conditions, a larger Fade margin should be used.The EIRP is given in dBm and Watts.6. If the required range between the two link sites is known, you may enter it directly. Alternatively, you may enter the latitude and longitude of each site in the link, in which case the distance between them will be calculated and displayed.NoteIf you choose Adaptive Rate, then the Rate list is unavailable as is the Climate factor list. Both of these quantities are calculated.NoteFor a given air-rate, Ethernet throughput will decrease with increasing range due to propagation delay.
Running the Link Budget Calculator Chapter 21RADWIN 2000 User Manual Release  2.5.40 21-10Figure 21-10:  Calculation of distance from site coordinatesFor example, if you enter the following coordinates and press Set,the range will be calculated and displayed:If for example, we enter:Site A: 41.1°N lat 74.2°W LongSite B: 40.8°N lat 74.0°W Long
Running the Link Budget Calculator Chapter 21RADWIN 2000 User Manual Release  2.5.40 21-117. Click Set. The distance and link budget is calculated.8. Located to the right of the green Coordinates button is a drop-down list of Climactic C Factor values. It is only available if you choose a non-adaptive rate.Figure 21-11: Climactic C FactorsFor help about what these mean, click the ? button to the right of the list in Figure 21-11.
Running the Link Budget Calculator Chapter 21RADWIN 2000 User Manual Release  2.5.40 21-12Figure 21-12: Climactic C Factor descriptionIn Figure 21-13 we display a map of the world showing C Factor contours:Figure 21-13: World map showing C Factor contours
Running the Link Budget Calculator Chapter 21RADWIN 2000 User Manual Release  2.5.40 21-139. Click Calculate to obtain the required performance estimate.Figure 21-14: LBC - Results sectionThe Expected Performance parameters are calculated and displayed:•Expected RSS - the expected RSS that the RADWIN Manager shows when the RAD-WIN 2000 ODUs are optimally aligned•Services Type - max number of T1 or E1 trunks if “Max Trunks” is selected•Ethernet Rate - maximum throughput available for the chosen parameter combina-tion•Antenna height for LOS – the minimum antenna height required for line-of-sight operation. It is the sum of the height required for boresight clearance due to the earth’s curvature plus the height required to clear the Fresnel zoneIf the expected performance is not suitable for your application, try different parameters and repeat the calculation.NotePlacing the cursor in any other calculated field will also update the calculated results.
RADWIN 2000 User Manual Release  2.5.40 22-1Chapter 22Quick Install ModeWhy this is NeededIt may be required to temporarily suspend service traffic over a link without losing the link connection. The simplest way to do this is to place the link in Installation mode but without changing any configured parameters. Quick Install Mode is a “one click” method for doing this. The method is completely generic, working identically for both WinLink 1000 and RAD-WIN 2000 products.Enabling Quick InstallBy default, this feature is disabled.To enable Quick Install mode:1. Log on to the RADWIN Manager, navigate to Tools | Preferences and click the Advanced tab:
Using Quick Install Chapter 22RADWIN 2000 User Manual Release  2.5.40 22-2Figure 22-1: Preferences: Quick Install2. Check the Enable Quick Install box and then OK. A new button is added to the main window toolbar:Figure 22-2: New Install Mode button for Quick Install modeQuick Install mode may be disabled by unchecking the Enable Quick Install box.Using Quick InstallTo suspend service traffic and enter Installation mode:1. Click the Install mode button. You are offered a confirmatory message:
Using Quick Install Chapter 22RADWIN 2000 User Manual Release  2.5.40 22-3Figure 22-3: Change to Installation Mode cautionary message2. Click Yes to continue. The link goes into Installation mode. The main window looks the same as if you had entered Installation mode in the usual way through one of the Site windows with the exception of the toolbar:Figure 22-4: Service Mode button to resume link service traffic3. When you are ready to resume normal service traffic, click the Service Mode but-ton. The following cautionary message is displayed:Figure 22-5: Resumption of services cautionary message
Using Quick Install Chapter 22RADWIN 2000 User Manual Release  2.5.40 22-44. Click Yes to continue. The link will resume normal services with your last set config-uration parameters provides that you did not change link parameters in a a way leading to sync loss. NoteIt is also possible to change parameters in a way leading to service degradation. For example mis-configuring the number of antennas or transmission parameters at one side of the link may allow service to resume, but in a degraded fashion.You may only enter Quick Install mode from a configured link. If you set both sites back to factory settings and chose Quick Install, you will not be able to continue:
RADWIN 2000Broadband Wireless Transmission SystemUSER MANUALRELEASE 2.5.40Part 5: Product DependentFeaturesUM 2000-2540/02.11
RADWIN 2000 User Manual Release  2.5.30 23-1Chapter 23Spectrum ViewWhat is Spectrum View?The RADWIN Manager Spectrum View utility is an RF survey tool designed to support the link installation prior to full link service activation. The tool provides comprehensive and clear spectral measurement information enabling easier, faster and better quality installations.You can view real-time spectrum information, save the spectral information and view retrieved spectral information from historic spectrum scans.RADWIN’s spectrum measurement and estimation algorithms are designed to show accurate information while accommodating with variations in frequency, temperature and interference power while overcoming anomalies that tend to occur in high interference environments.Running Spectrum View in Installation ModeTo launch Spectrum View, go to the RADWIN Manager main window menu and click Tools | Spectrum View.Figure 23-1: Starting the analysis
Running Spectrum View in Installation Mode Chapter 23RADWIN 2000 User Manual Release  2.5.30 23-2To obtain a spectrum analysis:1. Click Start Analysis. You are asked for confirmation:2. Click Yes. After a few moments, the first results for the managing site appear:Figure 23-2: Site A (managing site) doneThe over-the-air site takes a little longer:
Running Spectrum View in Installation Mode Chapter 23RADWIN 2000 User Manual Release  2.5.30 23-3Figure 23-3: Site B (over- the-air site) done, showing current channelThe analysis complete when the Start Analysis button reverts to green. It never runs for longer than ten minutes and you may stop it any time by clicking the red Stop Analysis button.The results for the over-the-air site are displayed after the link is re-established regardless whether the analysis completes by itself or is stopped. Current channel
Understanding the Spectrum View Display Chapter 23RADWIN 2000 User Manual Release  2.5.30 23-4Understanding the Spectrum View DisplayInformation DisplayedFigure 23-4 shows an annotated display taken from a live link.Figure 23-4: RADWIN 2000 Spectrum View - annotated display
Changing the Display Chapter 23RADWIN 2000 User Manual Release  2.5.30 23-5From Figure 23-4 above, you can see that the Spectrum View provides clear information including:• Spectral measurement for each of the 4 receivers that make a RADWIN 2000 link (two sites x two antennas per site)• Spectral power measurements in 5MHz channel granularity• Current, average and maximum power per channel• Indication of • channels free from radars• channels with radars detected•  barred channels (for DFS bands)• Indication of scanned and un-scanned channels• Indication of channels selected for ACS• Notation of the current operational channel of the RADWIN 2000 link• Time stamp of the last spectrum scan• Further, it supports zoom capability, selective view of antennas and sites constituting the link and selectable detail levelChanging the DisplayMoving the mouse anywhere over one the display areas changes it to a cross hair. The mouse may then be used to select an area for zooming, or to enable a right-click System menu.Figure 23-5: Mouse pointer active for zoomingSelecting a rectangle and clicking will zoom the channels below it to full panel width:
Changing the Display Chapter 23RADWIN 2000 User Manual Release  2.5.30 23-6Figure 23-6: Selecting an area of interest to zoom with the right mouse button downFigure 23-7: Requested section zoomedThe zoom can be reversed using the System menu obtained by right-clicking any of the Spec-trum View display panels. It also offers display variations such as maximum, average and cur-rent power per channel.Zoomed frequencies
Changing the Display Chapter 23RADWIN 2000 User Manual Release  2.5.30 23-7Figure 23-8: Spectrum View System menuHere are two examples:If you click Show Max, each panel will show the peak values recorded during the analysis:Figure 23-9: Effect of setting Show MaxIf you click Show Average, each panel will show the average values recorded during the analysis:Figure 23-10: Effect of setting Show Average
Restricting the Panels to be Displayed Chapter 23RADWIN 2000 User Manual Release  2.5.30 23-8Restricting the Panels to be DisplayedClick View for further viewing options:Figure 23-11: Further viewing optionsIf for example you want Antenna A only, the resulting display will look like this:Figure 23-12: Antenna A selectedSaving a Spectrum AnalysisYour analysis can be saved in a CSV (comma separated values) text file. Use the Files menu item in the usual way:
Saving a Spectrum Analysis Chapter 23RADWIN 2000 User Manual Release  2.5.30 23-9The Spectrum View information is logged as part of the Diagnostics Information to improve link and system diagnostics and remote support. It can be retrieved from the RADWIN Manager menu using Help |Get Diagnostic Information.Here is extract of a saved Spectrum View:Spectrum View - Site: AFrequencies Scanned,Last Scan Timestamp,Last NF-AntennaA,Last NF-AntennaB,Average NF-AntennaA,Average NF-Anten-naB,Max NF-AntennaA,Max NF-AntennaB5735,True,30/11/2009 08:20:52,-89,-90,-90,-91,-89,-90,5740,True,30/11/2009 08:20:52,-89,-90,-90,-91,-89,-90,5745,True,30/11/2009 08:20:52,-89,-90,-90,-91,-89,-90,...5830,True,30/11/2009 08:20:52,-92,-94,-93,-94,-92,-93,5835,True,30/11/2009 08:20:52,-92,-94,-93,-95,-92,-94,5840,True,30/11/2009 08:20:52,-92,-94,-93,-95,-92,-94,Rx Power - AntennaA: -55Rx Power - AntennaB: -55Spectrum View - Site: BFrequency,Is Scanned,Last Scan Timestamp,Last NF-AntennaA,Last NF-AntennaB,Average NF-AntennaA,Average NF-Anten-naB,Max NF-AntennaA,Max NF-AntennaB5735,True,30/11/2009 08:20:53,-91,-90,-92,-91,-91,-90,5740,True,30/11/2009 08:20:53,-90,-89,-91,-90,-90,-89,5745,True,30/11/2009 08:20:53,-90,-89,-91,-90,-90,-89,...5830,True,30/11/2009 08:20:53,-93,-94,-94,-94,-93,-93,5835,True,30/11/2009 08:20:53,-93,-94,-94,-95,-93,-94,5840,True,30/11/2009 08:20:53,-93,-94,-94,-95,-93,-94,Rx Power - AntennaA: -57Rx Power - AntennaB: -55The column headings are wrapped around. The table values in dBm, are noise-floor (NF) relative.The CSV file imports easily into most spreadsheet programs. Here is a MS Excel import:
Management Integration Chapter 23RADWIN 2000 User Manual Release  2.5.30 23-10Figure 23-13: Spectrum View CSV file imported into MS ExcelManagement IntegrationSpectrum view information is supported in RADWIN’s MIB and can be used by external Net-work Management applications.
RADWIN 2000 User Manual Release  2.5.30 24-1Chapter 24BRS/EBS ConsiderationsWhat is BRS/EBSThe Broadband Radio Service (BRS), formerly known as the Multipoint Distribution Service (MDS)/Multichannel Multipoint Distribution Service (MMDS), is a US FCC regulated commer-cial service. The relevant FCC rule is 47CFR part 27.In the past, it was generally used for the transmission of data and video programming to sub-scribers using high-powered wireless cable systems. However, over the years, it has evolved to include digital two-way systems capable of providing high-speed, high-capacity broadband service, including two-way Internet service via cellularized communication systems. Such ser-vices provide consumers integrated access to voice, high-speed data, video-on-demand, and interactive delivery services from a wireless device.For further details see:http://wireless.fcc.gov/services/index.htm?job=service_home&id=ebs_brsThis link (part of the FCC site) contains the Technical Rules covering matters such as:• Operational scope• Geographic service area• Antenna registrationBRS/EBS BandsThe BRS/EBS band (post-transition) is illustrated in Figure 24-1 below and in more detail in the three tables following.Observe that the BRS/EBS spectrum is divided into small channels, mainly of 5.5 and 6 MHz. There are two small ranges of 0.333 MHz channels as well.BRS/EBS user may lease blocks of up to four contiguous channels to achieve their required channel bandwidth. These are often referred to as single, double, triple or quad bands.
Post transition frequency assignments according to FCC CFR47 PART 27 sectionRADWIN 2000 User Manual Release  2.5.30 24-2Post transition frequency assignments according to FCC CFR47 PART 27 section 27.5:2009Figure 24-1: BRS/EBS Bands SchematicThe tables below provide a detailed view of the spectrum from 2.495 GHz to 2.690 GHz The sections marked J and K are not detailed. since they are not supported by RADWIN prod-ucts.
Post transition frequency assignments according to FCC CFR47 PART 27 section 27.5:2009 Chapter 24RADWIN 2000 User Manual Release  2.5.30 24-3(‡) Using a triple channel would be wasteful over a single link.Table 24-1: BRS/EBS Lower Band Segment (LBS)Channel type Channel Tag CBWMHzBandMHzFrom  ToBRS Guard 1 6 2496.0 2502.0EBSA15.52502.0 2507.5A2 2507.5 2513.0A3 2513.0 2518.5B1 2518.5 2524.0B2 2524.0 2529.5B3 2529.5 2535.0C1 2535.0 2540.5C2 2540.5 2546.0C3 2546.0 2551.5D1 2551.5 2557.0D2 2557.0 2562.5D3 2562.5 2568.0EBS(not supportedby RADWIN)JA10.33333 2568.0 2572.0JA2JA3JB1JB2JB3JC1JC2JC3JD1JD2JD3Table 24-2: BRS/EBS Middle Band Segment (MBS)Channel type Channel Tag CBWMHzBandMHzFrom  ToEBSA462572 2578B4 2578 2584C4 2584 2590D4 2590 2596G4 2596 2602BRS/EBS F4 2602 2608E4 2608 2614Table 24-3: BRS/EBS to RADWIN 2000 CBW mapping and Max Tx PowerBRS/EBS BandChannel TypeTotal CBW MHzRADWIN 2000CBWMHzMax Tx PowerdBmLBS & HBS5.5 MHz/sliceSingle 5.5 5 22Double 11.0 10 23Triple 16.5 Don’t use (‡)Quad 22.0 20 24MBS6 MHz / sliceSingle 6 5 22Double 12 10 23Triple 18 Don’t use (‡)Quad 24 20 24Table 24-4: BRS/EBS Upper Band Segment (UBS)Channel type Channel Tag CBWMHzBandMHzFrom  ToEBS/EBS, mixed(not supportedby RADWIN)KH10.33333 2614.0 2618.0KH2KH3KG1KG2KG3KF1KF2KF3KE1KE2KE3BRS Guard 2 6 2618 2624BRS/EBSE15.52624.0 2629.5E2 2629.5 2635.0E3 2635.0 2640.5F1 2640.5 2646.0F2 2646.0 2651.5F3 2651.5 2657.0BRSH1 2657.0 2662.5H2 2662.5 2668.0H3 2668.0 2673.5EBSG1 2673.5 2679.0G2 2679.0 2684.5G3 2684.5 2690.0
Setting up a BRS/EBS link using RADWIN 2000 2.5GHz Band Chapter 24RADWIN 2000 User Manual Release  2.5.30 24-4Setting up a BRS/EBS link using RADWIN 2000 2.5GHz BandThe key issue in setting up a RADWIN 2000 2.5GHz Band BRS link is the choice of an appro-priate channel bandwidth (CBW), which in turn depends on whether you are leasing a single, double, triple or quad band set.RADWIN BRS radios operate with channel bandwidths selectable from 5, 10 and 20 MHz. Choose your channel bandwidth in accordance with Table 24-3.  NoteRADWIN does not support the bands labeled J and K in Figure 24-1.
RADWIN 2000 User Manual Release  2.5.40 25-1Chapter 25Quality of ServiceAvailabilityThe Quality of Service (QoS) feature is available for links using RADWIN 2000 C radios. If you already have this model, you can access the feature by carrying out a Software Upgrade to the 2.5.40 release.To use the facility you must be familiar with the use of VLAN (802.1p) or Diffserv.QoS - OverviewQoS is a technique for prioritization of network traffic packets during congestion.RADWIN 2000 C links support two classification criteria, VLAN based or Diffserv based. You may chose which of them to use.Based upon the classification criterion chosen, received packets will be mapped into one of four quality groups: Real time, Near real time, Controlled load and Best effort.You may partition the total link capacity across the four Quality queues. The default weights as percentages are shown in Table 25-1.Table 25-1: Default priorities an d allocation by VLAN ID and DiffservQuality queue Priority REDAT %Diffserv  VLANReal time 48-63 6-7 15Near real time (responsive applications) 32-47 4-5 20Controlled load 16-31 2-3 25Best effort 0-15 0-1 40NoteFor REDAT (Remaining Ethernet Data - Ethernet throughput) measurement - see Throughput Checking. REDAT measures remaining Ethernet throughput after reduction of bandwidth used by TDM channels. Use the Link Budget Calculator to see how much remaining bandwidth is available for Ethernet.
Setting up QoS Chapter 25RADWIN 2000 User Manual Release  2.5.40 25-2Further, you may also limit the maximum information rate (MIR) for each queue per site.Setting up QoSYou may set up QoS from either the Installation or Configuration wizards. Before doing so, set up for VLAN (Chapter 14) or Diffserv, depending on which you intend to use.To define QoS settings for a link:1. Using either the Installation or Configuration wizards, navigate to the Services win-dow and chose the QoS tab.Figure 25-1: Services window with QoS selectedAlthough QoS is a link-oriented feature, each site may have its own separate param-eters.2. Click the Configure button for a site.Figure 25-2: Ethernet QoS Configuration - Mode selection3. Choose the required mode - 802.1p (VLAN) or Diffserv.
Setting up QoS Chapter 25RADWIN 2000 User Manual Release  2.5.40 25-3Figure 25-3: Top: VLAN allocation. Bottom: Diffserv allocation4. The entry fields in both cases are self evident. Upon clicking OK, •  If you over-book the Weight column, the last entered field will be reduced so that the total is 100%.• No weight field may be left zero. If you do, you will not be able to proceed until it is set to something:.This reflects the implementation policy under which no checked queue may be completely starved. If you really do not want to use a queue under congestion, uncheck it.• If you are under-booked, you will receive this notice:• In any event, you may automatically apply the same settings to both link sites:
Disabling QoS Chapter 25RADWIN 2000 User Manual Release  2.5.40 25-45. Priorities: You are completely responsible for the completeness and consistency of your VLAN or Diffserv priorities.6. Choose a Maximum Information Rate for each queue:Figure 25-4: MIR choice - per queueIf you previously used Site | Ethernet | Maximum Information Rate (Chapter 8) to globally limit the site, then your choice in Figure 25-4 will also be limited.l7. Click OK on the exit dialog to accept the settings. If you did not use these settings for the opposite site, you should configure it now.8. Complete the wizard in the usual way.Disabling QoSIn the dialog of Figure 25-2, choose the Disabled mode. The two sites may be enabled or disabled independently.
RADWIN 2000Broadband Wireless Transmission SystemUSER MANUALRELEASE 2.5.40Part 6: Product ReferenceUM 2000-2540/02.11
RADWIN 2000 User Manual Release  2.5.40 A-1Appendix ATechnical SpecificationsScope of these SpecificationsThis appendix contains technical specifications for the major link components appearing in this User Manual. They are correct at the date of publication, but are intended for general background only. The latest authoritative and most up to date technical specifications are available as Data Sheets obtainable from RADWIN Customer Service.In any event, RADWIN reserves the right to change these specifications without notice.ODUCapacity• RADWIN 2000 C: Up to 16 E1/T1 services and up to 100 Mbps capacity (net throughput, full duplex)• RADWIN 2000 X: Up to 3 E1 or 4 T1 services up to 10Mbps capacity (net throughput , full duplex)• RADWIN 2000 L: Up to 50 Mbps capacity (net throughput, full duplex)• RADWIN 2000 PDH: Up to 16 E1/T1 services and up to 10 Mbps capacity (net throughput, full duplex. Requires an IDU-C or E, no PoE supportRange Up to 120 km / 75 milesRadio Modulation 2x2 MIMO-OFDM (BPSK/QPSK/16QAM/64QAM)Adaptive Modulation & Coding SupportedAutomatic Channel Selection SupportedDiversity SupportedSpectrum View SupportedDuplex Technology TDDError Correction FEC k = 1/2, 2/3, 3/4, 5/6Rate – Dual Antenna [Mbps] 13 26 39 52 78 104 117 130Rate – Single Antenna [Mbps] 6.5 13 19.5 26 39 52 58.5 65Modulation BPSK QPSK 16QAM 64QAMFEC [k=] 1/2 1/2 3/4 1/2 3/4 2/3 3/4 5/6Max Tx Power [dBm] for 4.8 – 6 GHz 25 24 21 19 18Max Tx Power [dBm] for 2.4 GHz 26 25 24 24 21 20Max Tx Power [dBm] for 2.5 GHz (BRS) See Table 24-3
ODU Appendix ARADWIN 2000 User Manual Release  2.5.40 A-2(‡)Not available for X series ODUs.(†)Split into three sub-bands. See page 20-9.(*) Split into many sub-bands. There are also Tx Power limitations. See Chapter 24, and in particular,  tables 24-1 to 24-4.Sensitivity (dBm) @BER <10e-11 (20MHz) -88 -86 -83 -81 -77 -72 -70 -67Encryption AES 128Band Occupied Frequency  range [GHz] Compliance  Channel Bandwidth5 MHz 10 MHz 20 MHz 40 MHzFCC/IC 5.8 5.725 - 5.850 FCC 47CFR, Part 15, Subpart C and IC RSS-210 No Yes Yes YesFCC 5.4 5.480 - 5.715 FCC 47CFR, Part 15, Subpart E No Yes Yes YesIC 5.4 5.480 – 5.5905.660 – 5.715 IC RSS-210 No Yes Yes YesFCC/IC 5.3 5.260 - 5.340 FCC 47CFR, Part 15, Subpart E and IC RSS-210 No Yes Yes YesFCC/IC 4.9 4.940 - 4.990 FCC 47CFR, Part 90, Subpart Y and IC RSS-111 No Yes Yes NoFCC/IC 2.4 2.402 - 2.472 FCC 47CFR, Part 15, Subpart C and IC RSS-210 No Yes Yes NoFCC/IC 3.6(Lic) 3.650 - 3.675 FCC Part 90 Subpart Z and IC RSS-197 (Restricted) Yes Yes(‡) Yes(‡) NoFCC 2.5(*) 2.495  2.690 FCC CFR47 PART 27 section 27.5:2009 (BRS/EBS) Yes Yes Yes NoIC 3.4 (Lic) 3.475 – 3.650 IC RSS-192 Yes Yes(‡) Yes(‡) NoWPC India 5.8 5.825 – 5.875 GSR-38 No Yes Yes YesMII China 5.8  5.730 – 5.845 MII China No Yes Yes YesETSI 5.8 5.735 – 5.865 ETSI EN 302 502 No Yes Yes NoETSI 5.4 5.480 – 5.715 ETSI EN 301 893 No Yes Yes YesETSI 5.3 5.160 – 5.340 ETSI EN 301 893 No Yes Yes NoETSI 3.4 (Lic)(†) 3.400 - 3.700 ETSI EN 302 326-2 Yes Yes(‡) Yes(‡) NoUniversal 6.0 5.690– 6.060N/ANo Yes Yes YesUniversal 5.9 5.730 – 5.960 No Yes Yes YesUniversal 5.4 5.490 – 5.710 No Yes Yes YesUniversal 5.3 5.140 – 5.345 No Yes Yes YesUniversal 4.9 4.890 - 5.010 No Yes Yes YesUniversal 4.8 4.800 - 4.900 No Yes Yes YesUniversal 2.3 2.302 - 2.379 No Yes Yes NoUniversal 3.4 3.300 - 3.800 Yes Yes(‡) Yes(‡) NoODU with Integrated Antenna 37.1/14.84(W) x 37.1/14.84(H) x 9.00/3.6(D) cm/in; 3.5 kg / 7 lbsODU Connectorized 18.0/7.2(W) x 27.0/10.8(H) x 5.5/2.2(D) cm/in; 1.5 kg / 3.0 lbsPower Feeding Dual feeding, -20 to -60 VDC (AC/DC converter is available)Power Consumption - alone 25WPower Consumption with IDU See IDU specifications, this Appendix
IDU Appendix ARADWIN 2000 User Manual Release  2.5.40 A-3IDUThe following specifications are for most part, common to both IDU-C and new style IDU-E products. Differences are pointed out in the tables.Architecture ODU: Outdoor Unit with Integrated Antenna or Connectorized for External AntennaIDU: Indoor Unit for service interfaces or PoE device for Ethernet onlyODU to IDU/PoE Interface Outdoor CAT-5e cable; Maximum cable length: 100 mManagement Application (per link) RADWIN ManagerProtocol SNMP and TelnetNMS RADWIN NMSOperating Temperatures ODU: -35°C to +60°C / -31°F to +140°FHumidity ODU: Up to 100% non-condensing, IP67FCC/IC (cTUVus) UL 60950-1, UL 60950-22, CAN/CSA C22.2 60950-1, CAN/CSA C22.2 60950-22ETSI/IEC EN/IEC 60950-1, EN/IEC 60950-22FCC 47 CFR Class B, Part15, Subpart BETSI EN 300 386, EN 301 489-1, EN 301 489-4CAN/CSA CISPR 22-04 Class BAS/NZS CISPR 22:2004 Class BIDU-C IDU-ENumber of ports 16, 8, 4 ports or no TDM ports. 2 or no TDM portMax ports usable by WinLink 1000 42Max ports usable by RADWIN 2000 16 2Type E1/T1 configurable by RADWIN ManagerFraming Unframed (transparent)Timing Independent timing per port, Tx and Rx Connector RJ-45Standards Compliance ITU-T G.703, G.826Line Code E1: HDB3 @ 2.048 Mbps, T1: B8ZS/AMI @ 1.544 MbpsLatency Configurable 5-20 msec Impedance E1: 120Ω, balanced, T1: 100Ω, balancedJitter & Wander According to ITU-T G.823, G.824
IDU Appendix ARADWIN 2000 User Manual Release  2.5.40 A-4Jitter Buffer Jitter Buffer configuration enabling a latency from 5msec to 16msec for interference immunity confrontClock Recovery Resolution 0.05ppbClock stability 20ppm as clock master (crucial for wander requirements of cellular operators)Ethernet portsPorts: 210/100BaseT with Auto-Negotiation (IEEE 802.3u)Framing/Coding IEEE 802.3Connector RJ-45Line Impedance 100 ΩSFP port (IDU-C only) 1 port, Type: Fast Ethernet VLAN Support TransparentMaximum Frame Size 2047 BytesBridge Layer 2, self-learning of up to 2047 MAC addresses (IEEE 802.1Q), hub/Bridge selectable modeLatency 3 msec Dry Contact Alarms 4 Inputs + 4 Outputs; Configurable by the RADWIN ManagerMonitored Hot Standby (IDU-C only) SupportedIDU-C IDU-EStyle 1U 19” Rack mounted Half 19” wall mounted or desktopDimensions 43.6cm(W) x 21cm(D) x 4.4cm(H) 22cm(W) x 17cm(D) x 4.4cm(H)Weight 1.5 kg/3.3 lbs 0.5 kg/1.1 lbsIDU-C IDU-EPower Consumption        With WinLink 1000 ODU < 15W < 15W        With RADWIN 2000 ODU < 35W < 35W       Alone 7W 3WPower Feeding Options Dual feeding, -20 to -60VDC Single feeding, -20 to -60VDCOperating Temperatures 0°C - 50°C / 32°F - 122°FHumidity 90% non-condensingFCC/IC (cTUVus) UL 60950-1, CAN/CSA C22.2 60950-1ETSI/IEC EN/IEC 60950-1IDU-C IDU-E
PoE Device - Indoor, AC Appendix ARADWIN 2000 User Manual Release  2.5.40 A-5PoE Device - Indoor, ACFCC CFR47 Class B, Part15, Subpart BETSI EN 300 386, EN 301 489-4, EN 301 489-1CAN/CSA-CEI/IEC CISPR 22 Class BAS/NZS CISPR 22:2006 Class BAC Input Voltage 100-240VAC nominal, 85-265VAC max rangeInput Frequency 47-63HzInput Current 1.5A max at 90VAC, 0.75A max at 265VACOutput Voltage and Current 55VDC, 0-1A Range 50-58VDCProtectionShort circuit protectionAuto recoveryOver voltage protectionIndication Green led for normal operationEthernet LAN interface type RJ 45, 10/100BaseT Interface (Line Impedance -100)AC Standard socket IEC320 C14 typeODU (PoE Port) RJ-45 connectorCase PlasticDimensions 16cm(W) x 6.3cm(D) x 3.33cm(H)Weight 250gOperating Temperatures 0°C - 40°CHumidity 90% non-condensingUL 60950C-UL 60950TUV/GS IEC/EN 60950ESD 61000-4-2RS 61000-4-3EFT 61000-4-4Surge 61000-4-5CS 61000-4-6
PoE Device - Outdoor, DC Appendix ARADWIN 2000 User Manual Release  2.5.40 A-6PoE Device - Outdoor, DCGSUDIPS 61000-4-11EMI FCC part 15 class B, CISPR Pub 22 class BInput voltage range -20 to -60 VDC (single input)Output voltage  48VDC / 0.6APower Consumption 0.5W (not including radio)Protections Differential - 15KWCommon – 3KWEthernet LAN interface type RJ 45, 10/100BaseT Interface (Line Impedance -100)DC input 2 pins connectorODU (PoE Port) RJ45 Dimensions 24.5cm(H) x 13.5cm(W) x 4.0cm(D)Weight 1.0kg/2.2lbsEnclosure All weather casesOperating Temperatures -35C - 60C / -31F - 140FHumidity Up to 100% non-condensingStandards IEC 60721-3-4 Class 4M5IP67FCC/IEC/ CAN/CSA 60950-1, 60950-22ETSI EN 300 386 V1.3.2; EN 301 489-1 V1.4.1FCC CFR47 Class B, Part15, Subpart BCAN/CSA ICES-003:2004 Class BAS/NZS CISPR 22:2006 class BArchitecture Outdoor Unit Connectorized for External GPS AntennaGSU to PoE Interface Outdoor CAT-5e cable; Maximum cable length: 100 mDimensions 24.5cm(H) x 13.5cm(W) x 4.0cm(D) Weight 1.0kg/2.2lbs
Antenna Characteristics Appendix ARADWIN 2000 User Manual Release  2.5.40 A-7Antenna CharacteristicsAn antenna is the radiating and receiving element from which the radio signal, in the form of RF power, is radiated to its surroundings and vice versa. The transmission range is a function of the antenna gain and transmitting power. These factors are limited by country regulations.The RADWIN 2000 may be operated with an integrated antenna attached to the ODU unit, or with an external antenna wired to the ODU via a N-type connectors. All cables and connec-tions must be connected correctly to reduce losses. The required antenna impedance is 50Ω.  Power Feeding Power provided by PoE deviceMax Power Dissipation 10WattOperating Temperature Range -35°C to + 60°C / -13°F to 140°FHumidity Up to 100% non-condensingEN/IEC Designed to meet EN/IEC 60950-1, 60950-22FCC Designed to meet 47 CFR Class B, Part15, Subpart BETSI Designed to meet EN 300 386 V1.3.3; EN 301 489-4 V1.3.1; EN 301 489-1 CAN/CSA-CEI/IEC Designed to meet CISPR 22-02AS/NZS Designed to meet CISPR22: 2006 Class B
RADWIN 2000 User Manual Release  2.5.40 B-1Appendix BWiring SpecificationsODU-IDU CableThe ODU-IDU cable is shielded/outdoor class CAT-5e, 4 twisted-pair 24 AWG terminated with RJ-45 connectors on both ends. A cable gland on the ODU side provides hermetic sealing.The following table shows the connector pinout:ODU/HSS Unit Connection PinoutTable B-1: ODU-IDU RJ-45 Connector PinoutFunction Color IDU ODUEthernet (RxN) White/Green 1 1Ethernet (RxT) Green 2 2Ethernet (TxT) White/Orange 3 3Ethernet (TxN) Orange 6 6Power (+) Blue 4 4 Power (+) White/Blue 5 5Power ()White/Brown 7 7Power ()Brown 8 8Table B-2: ODU/HSS Unit Connection PinoutColor ODU RJ-45 HSS UNIT RJ-45White/Green 1 1 Green Not connectedWhite/OrangeOrange 6 6 Blue 4 4 White/Blue 5 5
User Port Connectors Appendix BRADWIN 2000 User Manual Release  2.5.40 B-2 User Port ConnectorsLAN PortThe LAN 10/100BaseT interface terminates in an 8-pin RJ-45 connector, wired in accordance to Table B-3.Trunk Ports - E1/T1 RJ45 ConnectorThe E1/T1 interfaces terminate in 8-pin RJ-45 connectors, as shown in Table B-4 below: Hot Standby Port RJ-11White/Brown 7 7 Brown 8 8 Table B-3: Fast Ethernet Connector PinoutFunction Signal Pin Transmit Data (positive) TD (+) 1Transmit Data (negative) TD (–) 2Receive Data (positive) RD (+) 3Receive Data (negative) RD (–) 6Table B-4: Trunk Ports - E1/T1 RJ45PinoutFunction Signal PinTransmit Data Tip TxTip 1Transmit Data Ring TxRing 2Receive Data Tip RxTip 4Receive Data Ring RxRing 5Table B-5: Hot Standby RJ-11 Port PinoutSignal Pin Side A Pin Side BHSB out 12HSB in 21Ground 33Ground 44Table B-2: ODU/HSS Unit Connection Pinout (Continued)Color ODU RJ-45 HSS UNIT RJ-45
IDU (all models) Alarm Connector Appendix BRADWIN 2000 User Manual Release  2.5.40 B-3IDU (all models) Alarm ConnectorThe IDU Alarm interface is a 25 pin D type female connector. Its pinout is listed in Table B-6.The figure below, shows how to connect external input and output alarms.Table B-6: IDU Alarm Connector (Dry-Contact)I/O Description PinInput 1 Positive 14Input 1 Negative 15Input 2 Positive 16Input 2 Negative 17Input 3 Positive 18Input 3 Negative 19Input 4 Positive 20Input 4 Negative 21Output 1 Normally Open 1Output 1 Common 2Output 1 Normally Closed  3Output 2 Normally Open 4Output 2 Common 5Output 2 Normally Closed  6Output 3 Normally Open 7Output 3 Common 8Output 3 Normally Closed  9Output 4 Normally Open 10Output 4 Common 11Output 4 Normally Closed  12Note• Use an external current limit resistor to limit the current at the output relays to 1 Amp. Such resistor is not required if the equipment con-nected to the IDU supports current limiting to 1 Amp.• The voltage of the input alarm must be within the range of -10 to -50 VDC.
DC Power Terminals Appendix BRADWIN 2000 User Manual Release  2.5.40 B-4Figure B-1: Example for connecting the alarm connectorDC Power TerminalsIDU-C & EDC PoETable B-7: Terminal Block 3-pin -48VDCFunction Pin+RightChassis Center–LeftTable B-8: Terminal Block 2-pin -48VDCFunction Pin+Right–Left
DC PoE Appendix BRADWIN 2000 User Manual Release  2.5.40 B-5
RADWIN 2000 User Manual Release  2.5.40 C-1Appendix CSmall Form-factorPluggable TransceiverIDU-C SFP SupportThe Small Form-factor Pluggable (SFP) transceiver, is a compact, hot-pluggable transceiver used in communications applications.The SFP transceiver technology allows almost any protocol converter implementation with seamless integration to a standard Ethernet switch.The IDU-C supports SFP transceivers to provide and support several network applications.Any standard Fast Ethernet (FE) SFP transceiver can be plugged into the IDU-C. These SFPs support various Ethernet interfaces. For example a fibre optic interface can be used to sup-port long fibre distances.In addition, System on SFP transceivers can be used, supporting a protocol converter con-cept. The main application for such SFP transceivers is TDM over Ethernet providing E1/T1 or E3/T3 over full duplex Ethernet Remote Bridge The following table provides a few SFP types that can be used with the IDU-C: Table C-1: SFP Type and Interface descriptionSFP Type Interface Description100baseT 100BaseT, IEEE 802.3, UTP CAT5100baseFX Multimode fiber-optic (MMF) link spans up to 2km long 100baseLX Single-mode fiber optic (SMF) links pans up to 10km100baseBX SMF single-strand link spans up to 10 km or 40 kmE3T3/FE E3/T3
RADWIN 2000 User Manual Release  2.5.40 D-1Appendix DMIB ReferenceIntroductionAbout the MIBThe RADWIN MIB is a set of APIs that enables external applications to control RADWIN equipment.The MIB is divided into public and a private API groups:•Public: RFC-1213 (MIB II) variables, RFC-1214 (MIB II) System and Interfaces sec-tions•Private: Controlled by RADWIN and supplements the public group.This appendix describes the public and private MIB used by RADWIN.TerminologyThe following terms are used in this appendix.In addition, the MIB uses internally, the older notions of Local site and Remote site where this manual would use site A and site B.To avoid burdening the reader, this appendix will follow the MIB usage.Interface APIControl MethodThe RADWIN Manager application provides all the means to configure and monitor a RADWIN 2000 link, communicating with the SNMP agent in each ODU. Each SNMP agent contains data Term MeaningMIB Management Information BaseAPI Application Programming InterfaceSNMP Simple Network Management Protocol
Community String Appendix DRADWIN 2000 User Manual Release  2.5.40 D-2on each of the IDUs and ODUs in the link. Both agents communicate with each other over the air using a proprietary protocol.To control and configure the device using the MIB, you should adhere to the following rules:• The connection for control and configuration is to the local site, over any SNMP/UDP/IP network.• All Parameters should be consistent between both of the ODUs. Note that inconsis-tency of air parameters can break the air connection. To correct air parameters incon-sistency you must reconfigure each of the ODUs. • Common practice is to configure the remote site first and then to configure the local site.• For some of the configuration parameters additional action must be taken before the new value is loaded. Please refer to the operation in the parameters description.• Some of the MIB parameters values are product dependent. It is strongly recommend using the RADWIN Manager Application for changing these values. Setting wrong val-ues may cause indeterminate results.Community StringTo control a link, all SNMP requests should go to the local site IP address.See Table 4-4 for default Community strings.Private MIB StructureThe sections in the private RADWIN MIB and its location in the MIB tree are shown in Figure D-1 below:NoteEach ODU has a single MAC address and a single IP address.
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-3Figure D-1: Top Level Sections of the private MIBThe products MIB section contains the definition of the Object IDs for the two form factors of the ODU, Integrated Antenna and Connectorized (referred in the MIB as external antenna) and GSU (where applicable):  Figure D-2: Product MIB: Left WinLink 1000, Right RADWIN 2000The ODU MIB contains the sections: Admin, Service, Ethernet, Bridge, Air, PerfMon and Agent.The IDU MIB contains the sections: Admin, Service, Ethernet, Bridge and TDM.The GpsSynchronizerFamily MIB defines the GSU.The general MIB include a single generic parameter that is used by all traps as a trap descrip-tion parameter.MIB ParametersThe following section describes all of the MIB parameters. The MIB parameters follow the fol-lowing naming convention:<winlink1000><Section 1>...<Section n><Parameter Name>
Supported Variables from the RFC 1213 MIB Appendix DRADWIN 2000 User Manual Release  2.5.40 D-4For each of the configuration and control parameters (parameters with read-write access), the “Description” column describes when the new value is effective. It is recommended that you perform the appropriate action to make the values affective immediately after any change. Where a change is required on both sides of the link, it is recommended that you change both sides of the link first and then perform the action.Supported Variables from the RFC 1213 MIBTable D-1: Supported RFC 1213 Variables (Sheet 1 of 2)Name OID TypeAccessDescriptionifIndex .1.3.6.1.2.1.2.2.1.1.xaInteger RO A unique value for each interface.Its value ranges between 1 and the value of ifNumber.The value for each interface must remain constant at least from one re-initialization of the entity's network management system to the next re-initialization.ifDescr .1.3.6.1.2.1.2.2.1.2 DisplayString RO A textual string containing information about the interface.This string should include the name of the manufacturer, the product name and the version of the hardware interface.ifType .1.3.6.1.2.1.2.2.1.3 Integer RO The type of interface, distinguished according to the physical/link protocol(s) immediately `below' the network layer in the protocol stack.ifSpeed .1.3.6.1.2.1.2.2.1.5 Gauge RO An estimate of the interface's current bandwidth in bits per second.For interfaces which do not vary in bandwidth or for those where no accurate estimation can be made, this object should ontain the nominal bandwidth.ifPhysAddress .1.3.6.1.2.1.2.2.1.6 Phys-Address RO The interface's address at the protocol layer immediately `below' the network layer in the protocol stack. For interfaces which do not have such an address (e.g., a serial line), this object should contain an octet string of zero length.ifAdminStatus .1.3.6.1.2.1.2.2.1.7 Integer RW The desired state of the interface. The testing(3) state indicates that no operational packets can be passed.ifOperStatus .1.3.6.1.2.1.2.2.1.8 Integer RO The current operational state of the interface. The testing(3) state indicates that no operational packets can be passed.ifInOctets .1.3.6.1.2.1.2.2.1.10.x Counter RO The total number of octets received on the interface, including framing characters.ifInUcastPkts .1.3.6.1.2.1.2.2.1.11.x Counter RO The number of subnetwork-unicast packets delivered to a higher-layer protocol.ifInNUcastPkts .1.3.6.1.2.1.2.2.1.12.x Counter RO The number of non-unicast (i.e., subnetwork- broadcast or subnetwork-multicast) packets delivered to a higher-layer protocol.ifInErrors .1.3.6.1.2.1.2.2.1.14.x Counter RO The number of inbound packets that contained errors preventing them from being deliverable to a higher-layer protocol.ifOutOctets .1.3.6.1.2.1.2.2.1.16.x Counter RO The total number of octets transmitted out of the interface, including framing characters.ifOutUcastPkts .1.3.6.1.2.1.2.2.1.17.x Counter RO The total number of packets that higher-level protocols requested be transmitted to a subnetwork-unicast address, including those that were discarded or not sent.
Supported Variables from the RFC 1213 MIB Appendix DRADWIN 2000 User Manual Release  2.5.40 D-5ifOutNUcastPkts .1.3.6.1.2.1.2.2.1.18.x Counter RO The total number of packets that higher-level protocols requested be transmitted to a non- unicast (i.e., a subnetwork-broadcast or subnetwork-multicast) address, including those that were discarded or not sent.a. x is the interface IDTable D-1: Supported RFC 1213 Variables (Sheet 2 of 2)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-6MIB ParametersTable D-2: Private MIB Parameters (Sheet 1 of 18)Name OID TypeAccessDescriptionwinlink1000OduAdmProductType 1.3.6.1.4.1.4458.1000.1.1.1 DisplayString RO ODU configuration description. winlink1000OduAdmHwRev 1.3.6.1.4.1.4458.1000.1.1.2 DisplayString RO ODU Hardware Version. winlink1000OduAdmSwRev 1.3.6.1.4.1.4458.1000.1.1.3 DisplayString RO ODU Software Version. winlink1000OduAdmLinkName 1.3.6.1.4.1.4458.1000.1.1.4 DisplayString RW Link Name. A change is effective immediately. winlink1000OduAdmResetCmd 1.3.6.1.4.1.4458.1000.1.1.5 Integer RW Reset Command. A set command with a value of 3 will cause a device reset.   The read value is always 0. winlink1000OduAdmAddres 1.3.6.1.4.1.4458.1000.1.1.6 IpAddress RW ODU IP address. A change is effective after reset.    The parameter is kept for backward compatibility.    Using the alternative parameter: winlink1000OduAdmIpParamsCnfg is recommended. winlink1000OduAdmMask 1.3.6.1.4.1.4458.1000.1.1.7 IpAddress RW ODU Subnet Mask. A change is effective after reset.    The parameter is kept for backward compatibility.    Using the alternative parameter: winlink1000OduAdmIpParamsCnfg is recommended. winlink1000OduAdmGateway 1.3.6.1.4.1.4458.1000.1.1.8 IpAddress RW ODU default gateway. A change is effective after reset.    The parameter is kept for backward compatibility.    Using the alternative parameter: winlink1000OduAdmIpParamsCnfg is recommended. winlink1000OduAdmBroadcast 1.3.6.1.4.1.4458.1000.1.1.10 Integer RW This parameter is reserved for the Manager application provided with the product. winlink1000OduAdmHostsTable N/A Trap destinations table. Each trap destination is defined by an IP address and a UDP port.   Up to 10 addresses can be configured. winlink1000OduAdmHostsEntry N/A Trap destinations table entry.   INDEX { winlink1000OduAdmHostsIndex } winlink1000OduAdmHostsIndex RO Trap destinations table index. winlink1000OduAdmHostsIp 1.3.6.1.4.1.4458.1000.1.1.12.1.2 IpAddress RW Trap destination IP address. A change is effective immediately. winlink1000OduAdmHostsPort 1.3.6.1.4.1.4458.1000.1.1.12.1.3 Integer RW UDP port of the trap destination. A change is effective immediately. winlink1000OduBuzzerAdminState 1.3.6.1.4.1.4458.1000.1.1.13 Integer RW This parameter controls the activation of the buzzer while the unit is in install mode.   A change is effective immediately. The valid values are: disabled (0)  enabledAuto (1)  enabledConstantly(2). winlink1000OduProductId 1.3.6.1.4.1.4458.1000.1.1.14 DisplayString RO This parameter is reserved for the Manager application provided with the product. winlink1000OduReadCommunity 1.3.6.1.4.1.4458.1000.1.1.15 DisplayString RW Read Community String. This parameter always returns ***** when retrieving its value.   It is used by the Manager application to change the Read Community String.   The SNMP agent accepts only encrypted values. winlink1000OduReadWriteCommunity 1.3.6.1.4.1.4458.1000.1.1.16 DisplayString RW Read/Write Community String. This parameter always returns ***** when retrieving its value.   It is used by the Manager application to change the Read/Write Community String.   The SNMP agent accepts only encrypted values. winlink1000OduTrapCommunity 1.3.6.1.4.1.4458.1000.1.1.17 DisplayString RW Trap Community String. This parameter is used by the Manager application to change the Trap Community String.   The SNMP agent accepts only encrypted values.
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-7winlink1000OduAdmSnmpAgentVersion 1.3.6.1.4.1.4458.1000.1.1.18 Integer RO Major version of the SNMP agent. winlink1000OduAdmRemoteSiteName 1.3.6.1.4.1.4458.1000.1.1.19 DisplayString RO Remote site name. Returns the same value as sysLocation parameter of the remote site. winlink1000OduAdmSnmpAgentMinorVersion 1.3.6.1.4.1.4458.1000.1.1.20 Integer RO Minor version of the SNMP agent. winlink1000OduAdmLinkPassword 1.3.6.1.4.1.4458.1000.1.1.21 DisplayString RW Link Password. This parameter always returns ***** when retrieving its value.   It is used by the Manager application to change the Link Password.   The SNMP agent accepts only encrypted values. winlink1000OduAdmSiteLinkPassword 1.3.6.1.4.1.4458.1000.1.1.22 DisplayString RW Site Link Password. This parameter always returns ***** when retrieving its value.   It is used by the Manager application to change the Link Password of the site.   The SNMP agent accepts only encrypted values. winlink1000OduAdmDefaultPassword 1.3.6.1.4.1.4458.1000.1.1.23 Integer RO This parameter indicates if the current Link Password is the default password. winlink1000OduAdmConnectionType 1.3.6.1.4.1.4458.1000.1.1.24 Integer RO This parameter indicates if the Manager application is connected to the local ODU   or to the remote ODU over the air. A value of 'unknown' indicates community string mismatch. winlink1000OduAdmBackToFactorySettingsCmd1.3.6.1.4.1.4458.1000.1.1.25 Integer RW Back to factory settings Command. A change is effective after reset.    The read value is always 0. winlink1000OduAdmIpParamsCnfg 1.3.6.1.4.1.4458.1000.1.1.26 DisplayString RW ODU IP address Configuration. The format is: <IP_Address>|<Subnet_Mask>|<Default_Gateway>| winlink1000OduAdmVlanID 1.3.6.1.4.1.4458.1000.1.1.27 Integer RW VLAN ID. Valid values are 1 to 4094.   Initial value is 0 meaning VLAN unaware. winlink1000OduAdmVlanPriority 1.3.6.1.4.1.4458.1000.1.1.28 Integer RW VLAN Priority. 0 is lowest priority  7 is highest priority. winlink1000OduAdmSN 1.3.6.1.4.1.4458.1000.1.1.29 DisplayString RO ODU Serial Number winlink1000OduAdmProductName 1.3.6.1.4.1.4458.1000.1.1.30 DisplayString RO This is the product name as it exists at EC winlink1000OduAdmActivationKey 1.3.6.1.4.1.4458.1000.1.1.31 DisplayString RW Activates a general key. winlink1000OduAdmRmtPermittedOduType 1.3.6.1.4.1.4458.1000.1.1.32 DisplayString RW Mobile Application: permitted partner OduType. winlink1000OduAdmCpuID 1.3.6.1.4.1.4458.1000.1.1.33 Integer RO CPU ID winlink1000OduSrvMode 1.3.6.1.4.1.4458.1000.1.2.1 Integer RW System mode. The only values that can be set are installMode and slaveMode;   normalMode reserved to the Manager application provided with the product.   A change is effective after link re-synchronization. winlink1000OduSrvBridging 1.3.6.1.4.1.4458.1000.1.2.3 Integer RO Bridging Mode. Valid values are: disabled (0)  enabled (1). winlink1000OduSrvRingLinkMode 1.3.6.1.4.1.4458.1000.1.2.4.1 Integer RW Mode of the link regarding ring topology. winlink1000OduSrvRingTopologySupported 1.3.6.1.4.1.4458.1000.1.2.4.2 Integer RO Ring Topology  options are: supported  not supported winlink1000OduSrvRingVlanIdTable N/A Ring VLAN IDs table. winlink1000OduSrvRingVlanIdEntry N/A VLAN ID of the internal ring messages. Valid values are 1 to 4094.   Initial value is 0 meaning VLAN unaware.   INDEX { winlink1000OduSrvRingVlanIdIndex } winlink1000OduSrvRingVlanIdIndex 1.3.6.1.4.1.4458.1000.1.2.4.3.1.1 Integer RO Index of VLAN ID of the internal ring messages.    winlink1000OduSrvRingVlanId 1.3.6.1.4.1.4458.1000.1.2.4.3.1.2 Integer RW VLAN ID of the internal ring messages. Valid values are 1 to 4094.   Initial value is 0 meaning VLAN unaware. winlink1000OduSrvRingEthStatus 1.3.6.1.4.1.4458.1000.1.2.4.4 Integer RO Represents the Ethernet service blocking state of a Rings link Table D-2: Private MIB Parameters (Sheet 2 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-8winlink1000OduSrvRingMaxAllowedTimeFromLastRpm1.3.6.1.4.1.4458.1000.1.2.4.5 Integer RW Defines the minimal time (in ms) required for determination of ring failure. winlink1000OduSrvRingWTR 1.3.6.1.4.1.4458.1000.1.2.4.6 Integer RW Defines the minimal time (in ms) required for ring recovery. winlink1000OduSrvQoSMode 1.3.6.1.4.1.4458.1000.1.2.5.1 Integer RW Mode of QoS feature. winlink1000OduSrvQoSConfTable N/A QoS configuration table. winlink1000OduSrvQoSConfEntry N/A QoS configuration table.    INDEX { winlink1000OduSrvQoSConfIndex } winlink1000OduSrvQoSConfIndex 1.3.6.1.4.1.4458.1000.1.2.5.2.1.1 Integer RO Index of QoS Configuration.    winlink1000OduSrvConfVlanQGroups 1.3.6.1.4.1.4458.1000.1.2.5.2.1.2 Integer RO Frames classification according to VLAN Priority IDs.    winlink1000OduSrvConfDiffservQGroups 1.3.6.1.4.1.4458.1000.1.2.5.2.1.3 Integer RO Frames classification according to Diffserv.    winlink1000OduSrvConfQueMir 1.3.6.1.4.1.4458.1000.1.2.5.2.1.4 Integer RW Desired Private MIR.    winlink1000OduSrvConfQueWeight 1.3.6.1.4.1.4458.1000.1.2.5.2.1.5 Integer RW QoS queueu's weights in percent.    winlink1000OduSrvQoSVlanQGroupsSetStr 1.3.6.1.4.1.4458.1000.1.2.5.3 DisplayString RW Frames classification according to VLAN IDs string for set. winlink1000OduSrvQoSDiffservQGroupsSetStr 1.3.6.1.4.1.4458.1000.1.2.5.4 DisplayString RW Frames classification according to Diffserv IDs string for set. winlink1000OduSrvQoSMaxRTQuePercent 1.3.6.1.4.1.4458.1000.1.2.5.5 Integer RO Maximal percent for RT & NRT queues. winlink1000OduEthernetRemainingRate 1.3.6.1.4.1.4458.1000.1.3.1 Integer RO Current Ethernet bandwidth in bps. winlink1000OduEthernetIfTable N/A ODU Ethernet Interface table. winlink1000OduEthernetIfEntry N/A ODU Ethernet Interface table entry.   INDEX { winlink1000OduEthernetIfIndex } winlink1000OduEthernetIfIndex 1.3.6.1.4.1.4458.1000.1.3.2.1.1 Integer RO ODU Ethernet Interface Index.  winlink1000OduEthernetIfAddress 1.3.6.1.4.1.4458.1000.1.3.2.1.5 DisplayString RO ODU MAC address. winlink1000OduEthernetIfAdminStatus 1.3.6.1.4.1.4458.1000.1.3.2.1.6 Integer RW Required state of the interface. winlink1000OduEthernetIfOperStatus 1.3.6.1.4.1.4458.1000.1.3.2.1.7 Integer RO Current operational state of the interface. winlink1000OduEthernetIfFailAction 1.3.6.1.4.1.4458.1000.1.3.2.1.8 Integer RW Failure action of the interface. winlink1000OduEthernetNumOfPorts 1.3.6.1.4.1.4458.1000.1.3.3 Integer RO Number of ODU network interfaces. winlink1000OduBridgeBasePortTable N/A ODU Bridge Ports table. winlink1000OduBridgeBasePortEntry N/A ODU Bridge Ports table entry.   INDEX { winlink1000OduBridgeBasePortIndex } winlink1000OduBridgeBasePortIndex RO ODU Bridge Port Number. winlink1000OduBridgeBaseIfIndex RO IfIndex corresponding to ODU Bridge port. winlink1000OduBridgeTpMode 1.3.6.1.4.1.4458.1000.1.4.4.101 Integer RW ODU bridge mode.    A change is effective after reset. Valid values: hubMode (0)  bridgeMode (1). winlink1000OduBridgeTpPortTable N/A ODU Transparent Bridge Ports table. winlink1000OduBridgeTpPortEntry N/A ODU Transparent Bridge Ports table entry.   INDEX { winlink1000OduBridgeTpPortIndex } winlink1000OduBridgeTpPortIndex RO ODU Transparent Bridge Port Number. winlink1000OduBridgeTpPortInFrames 1.3.6.1.4.1.4458.1000.1.4.4.3.1.3 Counter RO Number of frames received by this port. winlink1000OduBridgeTpPortOutFrames 1.3.6.1.4.1.4458.1000.1.4.4.3.1.4 Counter RO Number of frames transmitted by this port. winlink1000OduBridgeTpPortInBytes 1.3.6.1.4.1.4458.1000.1.4.4.3.1.101Counter RO Number of bytes received by this port. winlink1000OduBridgeTpPortOutBytes 1.3.6.1.4.1.4458.1000.1.4.4.3.1.102Counter RO Number of bytes transmitted by this port. winlink1000OduBridgeConfigMode 1.3.6.1.4.1.4458.1000.1.4.4.102 Integer RO ODU bridge configuration mode winlink1000OduAirFreq 1.3.6.1.4.1.4458.1000.1.5.1 Integer RW Installation Center Frequency. Valid values are product dependent. A change is effective after link re-synchronization. Table D-2: Private MIB Parameters (Sheet 3 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-9winlink1000OduAirDesiredRate 1.3.6.1.4.1.4458.1000.1.5.2 Integer RW Deprecated parameter  actual behavior is read-only.    Required Air Rate. For Channel Bandwidth of 20  10  5 MHz divide the value by 1  2  4 respectively. winlink1000OduAirSSID 1.3.6.1.4.1.4458.1000.1.5.3 DisplayString RW Reserved for the Manager application provided with the product. winlink1000OduAirTxPower 1.3.6.1.4.1.4458.1000.1.5.4 Integer RW Required Transmit power in dBm . This is a nominal value while the actual transmit power includes additional attenuation.   The min and max values are product specific. A change is effective immediately. winlink1000OduAirSesState 1.3.6.1.4.1.4458.1000.1.5.5 Integer RO Current Link State. The value is active (3) during normal operation.  winlink1000OduAirMstrSlv 1.3.6.1.4.1.4458.1000.1.5.6 Integer RO This parameter indicates if the device was automatically selected into the radio link master or slave.    The value is undefined if there is no link. winlink1000OduAirResync 1.3.6.1.4.1.4458.1000.1.5.8 Integer RW Setting this parameter to 1 will cause the link to restart the synchronization process. winlink1000OduAirRxPower 1.3.6.1.4.1.4458.1000.1.5.9.1 Integer RO Received Signal Strength in dBm. winlink1000OduAirTotalFrames 1.3.6.1.4.1.4458.1000.1.5.9.2 Counter RO Total Number of received radio frames. winlink1000OduAirBadFrames 1.3.6.1.4.1.4458.1000.1.5.9.3 Counter RO Total number of received radio frames with CRC error. winlink1000OduAirCurrentRate 1.3.6.1.4.1.4458.1000.1.5.9.4 Integer RO Deprecated parameter. Actual rate of the air interface in Mbps.    For Channel Bandwidth of 20  10  5 MHz divide the value by 1  2  4 respectively. winlink1000OduAirCurrentRateIdx 1.3.6.1.4.1.4458.1000.1.5.9.5 Integer RO Index of current air rate. winlink1000OduAirTxPower36 1.3.6.1.4.1.4458.1000.1.5.10 Integer RW Deprecated parameter. Actual behavior is read-only. winlink1000OduAirTxPower48 1.3.6.1.4.1.4458.1000.1.5.11 Integer RW Deprecated parameter. Actual behavior is read-only. winlink1000OduAirCurrentTxPower 1.3.6.1.4.1.4458.1000.1.5.12 Integer RO Current Transmit Power in dBm. This is a nominal value while the actual transmit power includes additional attenuation. winlink1000OduAirMinFrequency 1.3.6.1.4.1.4458.1000.1.5.13 Integer RO Minimum center frequency in MHz. winlink1000OduAirMaxFrequency 1.3.6.1.4.1.4458.1000.1.5.14 Integer RO Maximum center frequency in MHz. winlink1000OduAirFreqResolution 1.3.6.1.4.1.4458.1000.1.5.15 Integer RO Center Frequency resolution.    Measured in MHz if value < 100  otherwise in KHz. winlink1000OduAirCurrentFreq 1.3.6.1.4.1.4458.1000.1.5.16 Integer RO Current Center Frequency.   Measured in MHz if center frequency resolution value < 100  otherwise in KHz. winlink1000OduAirNumberOfChannels 1.3.6.1.4.1.4458.1000.1.5.17 Integer RO Number of channels that can be used. winlink1000OduAirChannelsTable N/A Table of channels used by automatic channels selection (ACS). winlink1000OduAirChannelsEntry N/A ACS channels table entry.   INDEX { winlink1000OduAirChannelsIndex } winlink1000OduAirChannelsIndex 1.3.6.1.4.1.4458.1000.1.5.18.1.1 Integer RO Channel Index. winlink1000OduAirChannelsFrequency 1.3.6.1.4.1.4458.1000.1.5.18.1.2 Integer RO Channel frequency in MHz. winlink1000OduAirChannelsOperState 1.3.6.1.4.1.4458.1000.1.5.18.1.3 Integer RW Channel state. Can be set by the user.     Automatic Channel Selection uses channels that are AirChannelsOperState enabled and AirChannelsAvail enabled.     A change is effective after link re-synchronization. Valid values: disabled (0)  enabled (1). Table D-2: Private MIB Parameters (Sheet 4 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-10winlink1000OduAirChannelsAvail 1.3.6.1.4.1.4458.1000.1.5.18.1.4 Integer RO Channel state. Product specific and cannot be changed by the user.    Automatic Channel Selection uses channels that are AirChannelsOperState enabled and AirChannelsAvail enabled.    Valid values: disabled (0)  enabled (1). winlink1000OduAirChannelsDefaultFreq 1.3.6.1.4.1.4458.1000.1.5.18.1.5 Integer RO Default channel's availability for all CBWs.   The valid values are: forbidden (0)  available (1). winlink1000OduAirDfsState 1.3.6.1.4.1.4458.1000.1.5.19 Integer RO Radar detection state. Valid values: disabled (0)  enabled (1). winlink1000OduAirAutoChannelSelectionState 1.3.6.1.4.1.4458.1000.1.5.20 Integer RO Deprecated parameter. Indicating Automatic Channel Selection availability at current channel bandwidth.    Valid values: disabled (0)  enabled (1). winlink1000OduAirEnableTxPower 1.3.6.1.4.1.4458.1000.1.5.21 Integer RO Indicating Transmit power configuration enabled or disabled. winlink1000OduAirMinTxPower 1.3.6.1.4.1.4458.1000.1.5.22 Integer RO Minimum Transmit power in dBm. winlink1000OduAirMaxTxPowerTable N/A Table of Maximum transmit power per air rate  in dBm. winlink1000OduAirMaxTxPowerEntry N/A Maximum Transmit power table entry.   INDEX { winlink1000OduAirMaxTxPowerIndex } winlink1000OduAirMaxTxPowerIndex 1.3.6.1.4.1.4458.1000.1.5.23.1.1 Integer RO Air interface rate index. winlink1000OduAirMaxTxPower 1.3.6.1.4.1.4458.1000.1.5.23.1.2 Integer RO Maximum Transmit power in dBm. winlink1000OduAirChannelBandwidth 1.3.6.1.4.1.4458.1000.1.5.24 Integer RW Channel bandwidth in KHz. A change is effective after reset. winlink1000OduAirChannelBWTable N/A Channel Bandwidths table. winlink1000OduAirChannelBWEntry N/A Channel Bandwidth table entry.   INDEX { winlink1000OduAirChannelBWIndex } winlink1000OduAirChannelBWIndex 1.3.6.1.4.1.4458.1000.1.5.25.1.1 Integer RO Channel Bandwidth index. winlink1000OduAirChannelBWAvail 1.3.6.1.4.1.4458.1000.1.5.25.1.2 Integer RO Channel Bandwidth availability  product specific.   Options are: Not supported  supported with manual channel selection  supported with Automatic Channel Selection. winlink1000OduAirChannelsAdminState 1.3.6.1.4.1.4458.1000.1.5.25.1.3 DisplayString RO Channels' availability per CBW. winlink1000OduAirChannelBWHSSATDDConflictPerCBW1.3.6.1.4.1.4458.1000.1.5.25.1.4 Integer RO Indication for possible Link drop per CBW due to conflict between HSS and ATDD. winlink1000OduAirChannelBWMinRatioForSupporting1.3.6.1.4.1.4458.1000.1.5.25.1.5 Integer RO Minimal TX ratio that may be used by the HSM and still enable proper operation of the aforementioned CBW. winlink1000OduAirChannelBWMaxRatioForSupporting1.3.6.1.4.1.4458.1000.1.5.25.1.6 Integer RO Maximal TX ratio that may be used by the HSM and still enable proper operation of the aforementioned CBW. winlink1000OduAirRFD 1.3.6.1.4.1.4458.1000.1.5.26 Integer RO Current radio frame duration in microseconds. winlink1000OduAirRatesTable N/A Air Rate indexes table for current channel bandwidth. winlink1000OduAirRatesEntry N/A Air Rate indexes table entry.   INDEX { winlink1000OduAirRatesIndex } winlink1000OduAirRatesIndex 1.3.6.1.4.1.4458.1000.1.5.27.1.1 Integer RO Air Rate index. winlink1000OduAirRatesAvail 1.3.6.1.4.1.4458.1000.1.5.27.1.2 Integer RO Air Rate availability  depending on air interface conditions. winlink1000OduAirDesiredRateIdx 1.3.6.1.4.1.4458.1000.1.5.28 Integer RW Required Air Rate index. 0 reserved for Adaptive Rate.   A change is effective immediately after Set operation to the master side   while the link is up. Table D-2: Private MIB Parameters (Sheet 5 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-11winlink1000OduAirLinkDistance 1.3.6.1.4.1.4458.1000.1.5.29 Integer RO Link distance in meters.    A value of -1 indicates an illegal value and is also used when a link is not established. winlink1000OduAirLinkWorkingMode 1.3.6.1.4.1.4458.1000.1.5.30 Integer RO Link working mode as a result of comparing versions of both sides of the link.    Possible modes are: Unknown - no link  Normal - versions on both sides are identical with full compatibility     with restricted compatibility  or versions on both sides are different with software upgrade or versions incompatibility. winlink1000OduAirMajorLinkIfVersion 1.3.6.1.4.1.4458.1000.1.5.31 Integer RO Major link interface version winlink1000OduAirMinorLinkIfVersion 1.3.6.1.4.1.4458.1000.1.5.32 Integer RO Minor link interface version winlink1000OduAirHssDesiredOpState 1.3.6.1.4.1.4458.1000.1.5.40.1 Integer RW Required Hub Site Synchronization operating state.   winlink1000OduAirHssCurrentOpState 1.3.6.1.4.1.4458.1000.1.5.40.2 Integer RO Current Hub Site Synchronization operating state.   winlink1000OduAirHssSyncStatus 1.3.6.1.4.1.4458.1000.1.5.40.3 Integer RO Hub Site Synchronization sync status.   winlink1000OduAirHssExtPulseStatus 1.3.6.1.4.1.4458.1000.1.5.40.4 Integer RO Hub Site Synchronization external pulse detection status.   In GSS mode:    if generating then 1PSP is auto generated by the GSS Unit.   if generatingAndDetecting then 1PSP is generated by GPS satellites signal.   winlink1000OduAirHssExtPulseType 1.3.6.1.4.1.4458.1000.1.5.40.5 Integer RO Hub Site Synchronization external pulse type.   winlink1000OduAirHssDesiredExtPulseType 1.3.6.1.4.1.4458.1000.1.5.40.6 Integer RW Hub Site Synchronization required external pulse type. Valid values for read write:    {typeA(2) typeB(3) typeC(4) typeD(5) typeE(6) typeF(7)}. Valid value for read only:    {notApplicable(1)}.   winlink1000OduAirHssRfpTable N/A ODU Radio Frame Patterns (RFP) Table. winlink1000OduAirHssRfpEntry N/A ODU RFP Table entry.   INDEX { winlink1000OduAirHssRfpIndex } winlink1000OduAirHssRfpIndex 1.3.6.1.4.1.4458.1000.1.5.40.7.1.1 Integer RO ODU RFP Table index. The index represent the Radio Frame Pattern:    typeA(2)  typeB(3)  typeC(4)  typeD(5) typeE(6). winlink1000OduAirHssRfpEthChannelBW5MHz1.3.6.1.4.1.4458.1000.1.5.40.7.1.2 Integer RO Represents the compatibility of Ethernet service under Channel BW of 5MHz     in the specific Radio Frame Pattern. winlink1000OduAirHssRfpTdmChannelBW5MHz1.3.6.1.4.1.4458.1000.1.5.40.7.1.3 Integer RO Represents the compatibility of TDM service under Channel BW of 5MHz     in the specific Radio Frame Pattern. winlink1000OduAirHssRfpEthChannelBW10MHz1.3.6.1.4.1.4458.1000.1.5.40.7.1.4 Integer RO Represents the compatibility of Ethernet service under Channel BW of 10MHz     in the specific Radio Frame Pattern. winlink1000OduAirHssRfpTdmChannelBW10MHz1.3.6.1.4.1.4458.1000.1.5.40.7.1.5 Integer RO Represents the compatibility of TDM service under Channel BW of 10MHz     in the specific Radio Frame Pattern. winlink1000OduAirHssRfpEthChannelBW20MHz1.3.6.1.4.1.4458.1000.1.5.40.7.1.6 Integer RO Represents the compatibility of Ethernet service under Channel BW of 20MHz     in the specific Radio Frame Pattern. winlink1000OduAirHssRfpTdmChannelBW20MHz1.3.6.1.4.1.4458.1000.1.5.40.7.1.7 Integer RO Represents the compatibility of TDM service under Channel BW of 20MHz     in the specific Radio Frame Pattern. winlink1000OduAirHssRfpEthChannelBW40MHzRO Represents the compatibility of Ethernet service under Channel BW of 40MHz     in the specific Radio Frame Pattern. winlink1000OduAirHssRfpTdmChannelBW40MHzRO Represents the compatibility of TDM service under Channel BW of 40MHz     in the specific Radio Frame Pattern. winlink1000OduAirHssRfpStr 1.3.6.1.4.1.4458.1000.1.5.40.8 DisplayString RO Hub Site Synchronization supported patterns Table D-2: Private MIB Parameters (Sheet 6 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-12winlink1000OduAirHSSHsmID 1.3.6.1.4.1.4458.1000.1.5.40.9 Integer RO A  unique ID which is common to the HSM and all its collocated ODUs winlink1000OduAirHssTime 1.3.6.1.4.1.4458.1000.1.5.40.10.0 DisplayString RO Hub Site Synchronization GPS time winlink1000OduAirHssLatitude 1.3.6.1.4.1.4458.1000.1.5.40.11.0 DisplayString RO Hub Site Synchronization GPS Latitude winlink1000OduAirHssNSIndicator 1.3.6.1.4.1.4458.1000.1.5.40.12.0 DisplayString RO Hub Site Synchronization GPS N/S Indicator winlink1000OduAirHssLongitude 1.3.6.1.4.1.4458.1000.1.5.40.13.0 DisplayString RO Hub Site Synchronization GPS Longitude winlink1000OduAirHssEWIndicator 1.3.6.1.4.1.4458.1000.1.5.40.14.0 DisplayString RO Hub Site Synchronization GPS E/W Indicator winlink1000OduAirHssNumSatellites 1.3.6.1.4.1.4458.1000.1.5.40.15.0 DisplayString RO Hub Site Synchronization GPS Number of satellites winlink1000OduAirHssAltitude 1.3.6.1.4.1.4458.1000.1.5.40.16.0 DisplayString RO Hub Site Synchronization GPS Altitude winlink1000OduAirHssRfpPhase 1.3.6.1.4.1.4458.1000.1.5.40.17.0 Integer RW Hub Site Synchronization GPS RFP phase winlink1000OduAirLockRemote 1.3.6.1.4.1.4458.1000.1.5.41 Integer RW This parameter enables locking the link with a specific ODU.    The following values can be set:    Unlock (default) - The ODU is not locked on a specific remote ODU. Unlock can only be performed when the link is not connected.    Lock - The ODU is locked on a specific remote ODU. Lock can only be performed when the link is active. winlink1000OduAirAntennaGain 1.3.6.1.4.1.4458.1000.1.5.42 Integer RW Current Antenna Gain in 0.1 dBi resolution. User defined value for    external antenna.   Legal range: MinAntennaGain<AntennaGain<MaxAntennaGain. winlink1000OduAirFeederLoss 1.3.6.1.4.1.4458.1000.1.5.43 Integer RW Current Feeder Loss in 0.1 dBm resolution. User defined value for    external antenna. winlink1000OduAirMaxAntennaGain 1.3.6.1.4.1.4458.1000.1.5.44 Integer RO Maximum allowed Antenna Gain in 0.1 dBi resolution. winlink1000OduAirMinAntennaGain 1.3.6.1.4.1.4458.1000.1.5.45 Integer RO Minimum allowed Antenna Gain in 0.1 dBi resolution. winlink1000OduAirMaxEIRP 1.3.6.1.4.1.4458.1000.1.5.46 Integer RO Maximum EIRP value as defined by regulation in 0.1 dBm resolution. winlink1000OduAirAntennaGainConfigSupport 1.3.6.1.4.1.4458.1000.1.5.47 Integer RO Antenna Gain Configurability  options are product specific: supported  not supported. winlink1000OduAirAntennaType 1.3.6.1.4.1.4458.1000.1.5.48 Integer RW External Antenna Type: Monopolar or Bipolar. winlink1000OduAirRssBalance 1.3.6.1.4.1.4458.1000.1.5.49 Integer RO RSS balance. Relation between RSS in radio 1 and RSS in radio 2. winlink1000OduAirTotalTxPower 1.3.6.1.4.1.4458.1000.1.5.50 Integer RO Total Transmit Power in dBm. This is a nominal value While the actual transmit power includes additional attenuation. winlink1000OduAirInstallFreqAndCBW 1.3.6.1.4.1.4458.1000.1.5.51 DisplayString RW Installation frequency   Channel BW. winlink1000OduAirDFStype 1.3.6.1.4.1.4458.1000.1.5.52 Integer RO DFS regulation type. winlink1000OduAirComboSubBandTable N/A ODU Multi-band Sub Bands Table. winlink1000OduAirComboSubBandEntry N/A ODU Multi-band Sub Bands Table entry.   INDEX { winlink1000OduAirComboSubBandIndex } winlink1000OduAirComboSubBandIndex 1.3.6.1.4.1.4458.1000.1.5.53.1.1.1 Integer RO ODU Multi-band sub bands table index. winlink1000OduAirComboSubBandId 1.3.6.1.4.1.4458.1000.1.5.53.1.1.2 DisplayString RO Represents the Multi-band sub band ID. winlink1000OduAirComboSubBandDescription 1.3.6.1.4.1.4458.1000.1.5.53.1.1.3 DisplayString RO Multi-band sub band description. winlink1000OduAirComboSubBandInstallFreq 1.3.6.1.4.1.4458.1000.1.5.53.1.1.4 Integer RO Represents the Multi-band sub band installation frequency in KHz. winlink1000OduAirComboSubBandAdminState 1.3.6.1.4.1.4458.1000.1.5.53.1.1.5 Integer RO Represents the Multi-band sub band administrative state. winlink1000OduAirComboSubBandInstallationAllowed1.3.6.1.4.1.4458.1000.1.5.53.1.1.6 Integer RO Reflects if the Multi-band sub band allowes installtion. winlink1000OduAirComboFrequencyBandId 1.3.6.1.4.1.4458.1000.1.5.53.1.1.7 Integer RO Reflects the frequency band Id. Table D-2: Private MIB Parameters (Sheet 7 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-13winlink1000OduAirComboNumberOfSubBands 1.3.6.1.4.1.4458.1000.1.5.53.2 Integer RO Represents the number of Multi-band sub bands. winlink1000OduAirComboSwitchSubBand 1.3.6.1.4.1.4458.1000.1.5.53.3 DisplayString RW Switch sub band operation with a given sub band ID.    The get operation retrieves the current sub band ID. winlink1000OduAirInternalMaxRate 1.3.6.1.4.1.4458.1000.1.5.54 Integer RO Max Ethernet throughput of the site (in Kpbs). winlink1000OduAirCapacityDirection 1.3.6.1.4.1.4458.1000.1.5.55 Integer RW Capacity direction of the site. winlink1000OduAirSpectrumAnalysisOperState1.3.6.1.4.1.4458.1000.1.5.56.1 Integer RW Spectrum Analysis operation state.    The configurable values are Spectrum Analysis Stop  Start and Restart.    Not Supported value indicates that the feature is not supported on the device.    Not Supported is not a configurable state. winlink1000OduAirRxPowerAntennaA 1.3.6.1.4.1.4458.1000.1.5.56.2 Integer RO Received Signal Strength in dBm of Antenna A. winlink1000OduAirRxPowerAntennaB 1.3.6.1.4.1.4458.1000.1.5.56.3 Integer RO Received Signal Strength in dBm of Antenna B. winlink1000OduAirNumberOfSpectrumChannels1.3.6.1.4.1.4458.1000.1.5.56.4 Integer RO Represents the number of Spectrum Channels. winlink1000OduAirSpectrumChannelTable N/A ODU Spectrum Analysis Channel Table. winlink1000OduAirSpectrumChannelTableEntryN/A ODU Spectrum Analysis Channel Table entry.   INDEX { winlink1000OduAirSpectrumChannelIndex } winlink1000OduAirSpectrumChannelIndex 1.3.6.1.4.1.4458.1000.1.5.56.5.1.1 Integer RO ODU Spectrum Channel index. winlink1000OduAirSpectrumChannelFrequency1.3.6.1.4.1.4458.1000.1.5.56.5.1.2 Integer RO ODU Spectrum Channel frequency in MHz. winlink1000OduAirSpectrumChannelScanned 1.3.6.1.4.1.4458.1000.1.5.56.5.1.3 Integer read-onlywinlink1000OduAirSpectrumChannelScanningTimestamp1.3.6.1.4.1.4458.1000.1.5.56.5.1.4 TimeTicks RO Channel last scan timestamp  in hundredths of a second  since device up time.    If the channel was not scanned than the return value will be 0. winlink1000OduAirSpectrumChannelLastNFAntennaA1.3.6.1.4.1.4458.1000.1.5.56.5.1.5 Integer RO Normalized Noise Floor value in dBm - of Antenna A - (including 2 neighbor frequencies). winlink1000OduAirSpectrumChannelLastNFAntennaB1.3.6.1.4.1.4458.1000.1.5.56.5.1.6 Integer RO Normalized Noise Floor value in dBm - of Antenna B - (including 2 neighbor frequencies). winlink1000OduAirSpectrumChannelAverageNFAntennaA1.3.6.1.4.1.4458.1000.1.5.56.5.1.7 Integer RO Average normalized Noise Floor value in dBm - of Antenna A -  over all dwells. winlink1000OduAirSpectrumChannelAverageNFAntennaB1.3.6.1.4.1.4458.1000.1.5.56.5.1.8 Integer RO Average normalized Noise Floor value in dBm - of Antenna B -  over all dwells. winlink1000OduAirSpectrumChannelMaxNFAntennaA1.3.6.1.4.1.4458.1000.1.5.56.5.1.9 Integer RO Max normalized Noise Floor value in dBm - of Antenna A -  over all dwells. winlink1000OduAirSpectrumChannelMaxNFAntennaB1.3.6.1.4.1.4458.1000.1.5.56.5.1.10Integer RO Max normalized Noise Floor value in dBm - of Antenna B -  over all dwells. winlink1000OduAirSpectrumChannelCACPerformed1.3.6.1.4.1.4458.1000.1.5.56.5.1.11Integer RO read-onlywinlink1000OduAirSpectrumChannelLastCACTimestamp1.3.6.1.4.1.4458.1000.1.5.56.5.1.12TimeTicks RO Last CAC performed timestamp  in hundredths of a second  since device up time.    If no CAC has performed on the channel  the return value will be 0. winlink1000OduAirSpectrumChannelRadarDetected1.3.6.1.4.1.4458.1000.1.5.56.5.1.13Integer RO read-onlywinlink1000OduAirSpectrumChannelRadarDetectionTimestamp1.3.6.1.4.1.4458.1000.1.5.56.5.1.14TimeTicks RO Last Radar Detection timestamp  in hundredths of a second  since device up time.    If no Radar has detected on the channel  the return value will be 0. winlink1000OduAirSpectrumChannelAvailable 1.3.6.1.4.1.4458.1000.1.5.56.5.1.15Integer RO read-onlywinlink1000OduAirAntConfAndRatesStatus 1.3.6.1.4.1.4458.1000.1.5.57 Integer RO Description: Antenna configuration and Rates status (1 = Single antenna with single data  stream  2 = Dual antenna with single data stream  3 = Dual antenna with dual data  stream). Table D-2: Private MIB Parameters (Sheet 8 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-14winlink1000OduAirDualAntTxMode 1.3.6.1.4.1.4458.1000.1.5.58 Integer RW Description: Transmission type when using Dual radios (MIMO or AdvancedDiversity using  one stream of data). winlink1000OduAirTxOperationMode 1.3.6.1.4.1.4458.1000.1.5.59 Integer RW This parameter controls the Operation mode of frames sent over the air.    The Operation mode is either normal (1) for regular transmission where frame size is determined by the traffic or throughput test (2) when the user requests an actual over the air throughput estimation using full frames.    The latter lasts no more than a predetermined interval (default 30 sec). winlink1000OduAirDesiredNetMasterTxRatio 1.3.6.1.4.1.4458.1000.1.5.60.1 Integer RW This parameter is reserved to the element manager provided with the product. winlink1000OduAirCurrentNetMasterTxRatio 1.3.6.1.4.1.4458.1000.1.5.60.2 Integer RO Represents the actual Net Master Tx RAtio. winlink1000OduAirMinUsableMasterTxRatio 1.3.6.1.4.1.4458.1000.1.5.60.3 Integer RO Represents the minimal value the user can configure for Desired net mAster Tx Ratio. winlink1000OduAirMaxUsableMasterTxRatio 1.3.6.1.4.1.4458.1000.1.5.60.4 Integer RO Represents the maximal value the user can configure for Desired net mAster Tx Ratio. winlink1000OduAirAccumulatedUAS 1.3.6.1.4.1.4458.1000.1.5.61 Integer RO Accumulates the Unavailable seconds of the Air Interface. winlink1000OduAirAccumulatedUAS 1.3.6.1.4.1.4458.1000.1.5.62 Integer RO Possibilities of the link according to RFP and CBW winlink1000OduPerfMonCurrTable N/A This table defines/keeps the counters of the current 15 min interval. winlink1000OduPerfMonCurrEntry N/A This is an entry in the Current Interval Table.   INDEX {ifIndex } winlink1000OduPerfMonCurrUAS 1.3.6.1.4.1.4458.1000.1.6.1.1.1 Gauge RO The current number of Unavailable Seconds starting from the present 15 minutes period. winlink1000OduPerfMonCurrES 1.3.6.1.4.1.4458.1000.1.6.1.1.2 Gauge RO Current number of Errored Seconds starting from the present 15 minutes period. winlink1000OduPerfMonCurrSES 1.3.6.1.4.1.4458.1000.1.6.1.1.3 Gauge RO Current number of Severely Errored Seconds starting from the present 15 minutes period. winlink1000OduPerfMonCurrBBE 1.3.6.1.4.1.4458.1000.1.6.1.1.4 Gauge RO Current number of Background Block Errors starting from the present 15 minutes period. winlink1000OduPerfMonCurrIntegrity 1.3.6.1.4.1.4458.1000.1.6.1.1.5 Integer RO Indicates the integrity of the entry. winlink1000OduPerfMonIntervalTable N/A This table defines/keeps the counters of the last day (in resolution of 15 min intervals). winlink1000OduPerfMonIntervalEntry N/A This is an entry in the Interval Table.   INDEX {ifIndex  winlink1000OduPerfMonIntervalIdx } winlink1000OduPerfMonIntervalIdx RO This table is indexed per interval number. Each interval   is of 15 minutes and the oldest is 96. winlink1000OduPerfMonIntervalUAS RO The current number of Unavailable Seconds per interval. winlink1000OduPerfMonIntervalES RO Current number of Errored Seconds per interval. winlink1000OduPerfMonIntervalSES RO Current number of Severely Errored Seconds per interval. winlink1000OduPerfMonIntervalBBE RO Current number of Background Block Errors per interval. winlink1000OduPerfMonIntervalIntegrity RO Indicates the integrity of the entry per interval. winlink1000OduPerfMonDayTable N/A This table defines/keeps the counters of the last month (in resolution of days). winlink1000OduPerfMonDayEntry N/A This is an entry in the Days Table.   INDEX {ifIndex  winlink1000OduPerfMonDayIdx } winlink1000OduPerfMonDayIdx RO This table is indexed per interval number. Each interval   is of 24 hours and the oldest is 30. Table D-2: Private MIB Parameters (Sheet 9 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-15winlink1000OduPerfMonDayUAS RO The current number of Unavailable Seconds per interval of 24 hours. winlink1000OduPerfMonDayES RO Current number of Errored Seconds per interval of 24 hours. winlink1000OduPerfMonDaySES RO Current number of Severely Errored Seconds per interval of 24 hours. winlink1000OduPerfMonDayBBE RO Current number of Background Block Errors per interval of 24 hours. winlink1000OduPerfMonDayIntegrity RO Indicates the integrity of the entry per interval of 24 hours. winlink1000OduPerfMonAirCurrTable N/A This table defines/keeps the air counters of the current 15 min interval. winlink1000OduPerfMonAirCurrEntry N/A This is an entry in the Current Interval Table.   INDEX {ifIndex } winlink1000OduPerfMonAirCurrMinRSL 1.3.6.1.4.1.4458.1000.1.6.4.1.1 Integer RO Current Min Received Level Reference starting from the present 15 minutes period. winlink1000OduPerfMonAirCurrMaxRSL 1.3.6.1.4.1.4458.1000.1.6.4.1.2 Integer RO Current Max Received Level Reference starting from the present 15 minutes period. winlink1000OduPerfMonAirCurrRSLThresh1Exceed1.3.6.1.4.1.4458.1000.1.6.4.1.3 Gauge RO Number of seconds Receive Signal Level exceeded the RSL1 threshold in the last 15 minutes. winlink1000OduPerfMonAirCurrRSLThresh2Exceed1.3.6.1.4.1.4458.1000.1.6.4.1.4 Gauge RO Number of seconds Receive Signal Level exceeded the RSL2 threshold in the last 15 minutes. winlink1000OduPerfMonAirCurrMinTSL 1.3.6.1.4.1.4458.1000.1.6.4.1.5 Integer RO Current Min Transmit Signal Level starting from the present 15 minutes period. winlink1000OduPerfMonAirCurrMaxTSL 1.3.6.1.4.1.4458.1000.1.6.4.1.6 Integer RO Current Max Transmit Signal Level starting from the present 15 minutes period. winlink1000OduPerfMonAirCurrTSLThresh1Exceed1.3.6.1.4.1.4458.1000.1.6.4.1.7 Gauge RO Number of seconds Transmit Signal Level exceeded the TSL1 threshold in the last 15 minutes. winlink1000OduPerfMonAirCurrBBERThresh1Exceed1.3.6.1.4.1.4458.1000.1.6.4.1.8 Gauge RO Number of seconds Background Block Error Ratio exceeded the BBER1 threshold in the last 15 minutes. winlink1000OduPerfMonAirIntervalTable N/A This table defines/keeps the air counters of the last day (in resolution of 15 min intervals). winlink1000OduPerfMonAirIntervalEntry N/A This is an entry in the Interval Table.   INDEX {ifIndex  winlink1000OduPerfMonAirIntervalIdx } winlink1000OduPerfMonAirIntervalIdx RO This table is indexed per interval number. Each interval   is of 15 minutes and the oldest is 96. winlink1000OduPerfMonAirIntervalMinRSL RO Current Min Received Level Reference per interval. winlink1000OduPerfMonAirIntervalMaxRSL RO Current Max Received Level Reference per interval. winlink1000OduPerfMonAirIntervalRSLThresh1ExceedRO Number of seconds Receive Signal Level exceeded the RSL1 threshold per interval. winlink1000OduPerfMonAirIntervalRSLThresh2ExceedRO Number of seconds Receive Signal Level exceeded the RSL2 threshold   ACCESS  read-only per interval. winlink1000OduPerfMonAirIntervalMinTSL RO Current Min Transmit Signal Level per interval. winlink1000OduPerfMonAirIntervalMaxTSL RO Current Max Transmit Signal Level per interval. winlink1000OduPerfMonAirIntervalTSLThresh1ExceedRO Number of seconds Transmit Signal Level exceeded the TSL1 threshold per interval. winlink1000OduPerfMonAirIntervalBBERThresh1ExceedRO Number of seconds Background Block Error Ratio exceeded the BBER1 threshold per interval. Table D-2: Private MIB Parameters (Sheet 10 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-16winlink1000OduPerfMonAirDayTable N/A This table defines/keeps the air counters of the last month (in resolution of days). winlink1000OduPerfMonAirDayEntry N/A This is an entry in the Days Table.   INDEX {ifIndex  winlink1000OduPerfMonAirDayIdx } winlink1000OduPerfMonAirDayIdx RO This table is indexed per Day number. Each Day   is of 15 minutes and the oldest is 96. winlink1000OduPerfMonAirDayMinRSL RO Current Min Received Level Reference per Day. winlink1000OduPerfMonAirDayMaxRSL RO Current Max Received Level Reference per Day. winlink1000OduPerfMonAirDayRSLThresh1ExceedRO Number of seconds Receive Signal Level exceeded the RSL1 threshold per Day. winlink1000OduPerfMonAirDayRSLThresh2ExceedRO Number of seconds Receive Signal Level exceeded the RSL2 threshold per Day. winlink1000OduPerfMonAirDayMinTSL RO Current Min Transmit Signal Level per Day. winlink1000OduPerfMonAirDayMaxTSL RO Current Max Transmit Signal Level per Day. winlink1000OduPerfMonAirDayTSLThresh1ExceedRO Number of seconds Transmit Signal Level exceeded the TSL1 threshold per Day. winlink1000OduPerfMonAirDayBBERThresh1ExceedRO Number of seconds Background Block Error Ratio exceeded the BBER1 threshold per Day. winlink1000OduPerfMonEthCurrTable N/A This table defines/keeps the ethernet counters of the current 15 min interval. winlink1000OduPerfMonEthCurrEntry N/A This is an entry in the Current Interval Table.   INDEX {ifIndex } winlink1000OduPerfMonEthCurrRxMBytes 1.3.6.1.4.1.4458.1000.1.6.7.1.1 Gauge RO Current RX Mega Bytes starting from the present 15 minutes period. winlink1000OduPerfMonEthCurrTxMBytes 1.3.6.1.4.1.4458.1000.1.6.7.1.2 Gauge RO Current Transmit Mega Bytes starting from the present 15 minutes period. winlink1000OduPerfMonEthCurrEthCapacityThreshUnder1.3.6.1.4.1.4458.1000.1.6.7.1.3 Gauge RO The number of times throughput was below threshold in the present 15 minutes period. winlink1000OduPerfMonEthCurrHighTrafficThreshExceed1.3.6.1.4.1.4458.1000.1.6.7.1.4 Gauge RO The number of times actual traffic was above threshold in the present 15 minutes period. winlink1000OduPerfMonEthCurrActiveSeconds1.3.6.1.4.1.4458.1000.1.6.7.1.5 Gauge RO The number of seconds in which RPL Ethernet swervice was not blocked in the present 15 minutes period. winlink1000OduPerfMonEthIntervalTable N/A This table defines/keeps the ethernet counters of the last day (in resolution of 15 min intervals). winlink1000OduPerfMonEthIntervalEntry N/A This is an entry in the Interval Table.   INDEX {ifIndex  winlink1000OduPerfMonEthIntervalIdx } winlink1000OduPerfMonEthIntervalIdx RO This table is indexed per interval number. Each interval   is of 15 minutes and the oldest is 96. winlink1000OduPerfMonEthIntervalRxMBytes RO Current RX Mega Bytes per interval. winlink1000OduPerfMonEthIntervalTxMBytes RO Current Transmit Mega Bytes per interval. winlink1000OduPerfMonEthIntervalEthCapacityThreshUnderRO The number of times throughput was below threshold in the each interval. winlink1000OduPerfMonEthIntervalHighTrafficThreshExceedRO The number of times actual traffic was above threshold in the each interval. winlink1000OduPerfMonEthIntervalActiveSecondsRO The number of seconds in which RPL Ethernet service was not blocked in the each interval. winlink1000OduPerfMonEthDayTable N/A This table defines/keeps the ethernet counters of the last month (in resolution of days). winlink1000OduPerfMonEthDayEntry N/A This is an entry in the Days Table.   INDEX {ifIndex  winlink1000OduPerfMonEthDayIdx } winlink1000OduPerfMonEthDayIdx RO This table is indexed per Day number. Each interval   is of 15 minutes and the oldest is 96. winlink1000OduPerfMonEthDayRxMBytes RO Current RX Mega Bytes per day. Table D-2: Private MIB Parameters (Sheet 11 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-17winlink1000OduPerfMonEthDayTxMBytes RO Current Transmit Mega Bytes per day. winlink1000OduPerfMonEthDayEthCapacityThreshUnderRO The number of times throughput was below threshold each day. winlink1000OduPerfMonEthDayHighTrafficThreshExceedRO The number of times actual traffic was above threshold each day. winlink1000OduPerfMonEthDayActiveSeconds RO The number of seconds in which RPL Ethernet service was not blocked each day. winlink1000OduPerfMonTdmCurrTable N/A This table defines/keeps the TDM counters of the current 15 min interval. winlink1000OduPerfMonTdmCurrEntry N/A This is an entry in the Current Interval Table.   INDEX {ifIndex } winlink1000OduPerfMonTdmCurrActiveSeconds1.3.6.1.4.1.4458.1000.1.6.10.1.1 Gauge RO Parameter indicating whether the TDM service was active.    Under TDM backup link  the parameter indicates whether     the backup link was active. winlink1000OduPerfMonTdmIntervalTable N/A This table defines/keeps the TDM counters of the last day (in resolution of 15 min intervals). winlink1000OduPerfMonTdmIntervalEntry N/A This is an entry in the Interval Table.   INDEX {ifIndex  winlink1000OduPerfMonTdmIntervalIdx } winlink1000OduPerfMonTdmIntervalIdx RO This table is indexed per interval number. Each interval   is of 15 minutes and the oldest is 96. winlink1000OduPerfMonTdmIntervalActiveSecondsRO Parameter indicating whether the TDM service was active.   Under TDM backup link  the parameter indicates whether    the backup link was active. winlink1000OduPerfMonTdmDayTable N/A This table defines/keeps the TDM counters of the last month (in resolution of days). winlink1000OduPerfMonTdmDayEntry N/A This is an entry in the Days Table.   INDEX {ifIndex  winlink1000OduPerfMonTdmDayIdx } winlink1000OduPerfMonTdmDayIdx RO This table is indexed per Day number. Each interval   is of 15 minutes and the oldest is 96. winlink1000OduPerfMonTdmDayActiveSecondsRO Parameter indicating whether the TDM service was active.   Under TDM backup link  the parameter indicates whether    the backup link was active. winlink1000OduPerfMonTxThresh1 1.3.6.1.4.1.4458.1000.1.6.20 Integer RW When the Transmit power exceeds this threshold  a performance monitoring TSL1 counter is incremented. winlink1000OduPerfMonRxThresh1 1.3.6.1.4.1.4458.1000.1.6.21 Integer RW When the RX power exceeds this threshold  a performance monitoring RSL1 counter is incremented. winlink1000OduPerfMonRxThresh2 1.3.6.1.4.1.4458.1000.1.6.22 Integer RW When the RX power exceeds this threshold  a performance monitoring RSL2 counter is incremented. winlink1000OduPerfMonBBERThresh1 1.3.6.1.4.1.4458.1000.1.6.23 Integer RW When the BBER exceeds this threshold  a performance monitoring BBER counter is incremented. The units are 1/10 of a percent. winlink1000OduPerfMonEthCapacityThreshKbps1.3.6.1.4.1.4458.1000.1.6.24 Integer RW When the current throughput is below this threshold  the corresponding counter is incremented winlink1000OduPerfMonHighTrafficThreshKbps1.3.6.1.4.1.4458.1000.1.6.25 Integer RW When the current traffic is above this threshold  then corresponding counter is incremented. winlink1000OduAgnGenAddTrapExt 1.3.6.1.4.1.4458.1000.1.7.1.1 Integer RW If 'yes' is chosen  the ifIndex  Unit  Severity  Time_T and Alarm Id from the winlink1000OduAgnCurrAlarmTable   will be bind to the end of each private trap.   Table D-2: Private MIB Parameters (Sheet 12 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-18winlink1000OduAgnGenSetMode 1.3.6.1.4.1.4458.1000.1.7.1.2 Integer RW This parameter is reserved to the element manager provided with the product.   winlink1000OduAgnNTPCfgTimeServerIP 1.3.6.1.4.1.4458.1000.1.7.2.1 IpAddress RW IP address of the server from which the current time is loaded. winlink1000OduAgnNTPCfgTimeOffsetFromUTC1.3.6.1.4.1.4458.1000.1.7.2.2 Integer RW Offset from Coordinated Universal Time (minutes). Possible values: -1440..1440. winlink1000OduAgnRealTimeAndDate 1.3.6.1.4.1.4458.1000.1.7.2.3 OctetString RW This parameter specifies the real time and date         Format 'YYYY-MM-DD HH:MM:SS' (Hexadecimal).           A date-time specification:          field  octets  contents                  range         -----  ------  --------                  -----           1      1-2   year                      0..65536           2       3    month                     1..12           3       4    day                       1..31           4       5    hour                      0..23           5       6    minutes                   0..59        6       7    seconds                   0..60                        (use 60 for leap-second)           7       8    deci-seconds              0..9                  For example  Tuesday May 26  1992 at 1:30:15 PM EDT         would be displayed as: 07 c8 05 1a 0d 1e 0f 00          ( 1992 -5 -26 13:30:15 ) winlink1000OduAgnCurrAlarmLastChange 1.3.6.1.4.1.4458.1000.1.7.3.1 Integer RO This counter is initialized to 0 after a device reset and is incremented upon each change in the winlink1000OduAgnCurrAlarmTable   (either an addition or removal of an entry). winlink1000OduAgnCurrAlarmTable N/A This table includes the currently active alarms. When a RAISED trap is          sent  an alarm entry is added to the table. When a CLEAR trap is sent           the entry is removed. winlink1000OduAgnCurrAlarmEntry N/A Entry containing the details of a currently RAISED trap.   INDEX { winlink1000OduAgnCurrAlarmCounter } winlink1000OduAgnCurrAlarmCounter 1.3.6.1.4.1.4458.1000.1.7.3.2.1.1 Integer RO A running counter of active alarms. The counter is incremented for every new RAISED trap.   It is cleared after a device reset. winlink1000OduAgnCurrAlarmSeverity 1.3.6.1.4.1.4458.1000.1.7.3.2.1.2 Integer RO Current Alarm severity. winlink1000OduAgnCurrAlarmId 1.3.6.1.4.1.4458.1000.1.7.3.2.1.3 Integer RO Unique Alarm Identifier (combines alarm type and interface). The same AlarmId is used for RAISED and CLEARED alarms. winlink1000OduAgnCurrAlarmIfIndex 1.3.6.1.4.1.4458.1000.1.7.3.2.1.4 Integer RO Interface Index where the alarm occurred. Alarms that are     not associated with a specific interface will have the following value: 65535. winlink1000OduAgnCurrAlarmUnit 1.3.6.1.4.1.4458.1000.1.7.3.2.1.5 Integer RO Unit associated with the alarm. winlink1000OduAgnCurrAlarmTrapID 1.3.6.1.4.1.4458.1000.1.7.3.2.1.6 Integer RO ID of the raised trap that was sent when this alarm was raised. winlink1000OduAgnCurrAlarmTimeT 1.3.6.1.4.1.4458.1000.1.7.3.2.1.7 Integer RO Timestamp of this alarm. This number is in seconds from Midnight January 1st  1970. winlink1000OduAgnCurrAlarmText 1.3.6.1.4.1.4458.1000.1.7.3.2.1.8 DisplayString RO Alarm display text (same as the text in the sent trap). winlink1000OduAgnLastEventsNumber 1.3.6.1.4.1.4458.1000.1.7.4.1 Integer RO This counter indicates the size of the winlink1000OduAgnLastEventsTable winlink1000OduAgnLastEventsTable N/A This table includes the last events. When a trap is          sent  an event entry is added to the table. winlink1000OduAgnLastEventsEntry N/A Entry containing the details of last traps.   INDEX { winlink1000OduAgnLastEventsIndex } winlink1000OduAgnLastEventsIndex 1.3.6.1.4.1.4458.1000.1.7.4.2.1.1 Integer RO The index of the table winlink1000OduAgnLastEventsSeverity 1.3.6.1.4.1.4458.1000.1.7.4.2.1.2 Integer RO Current Trap severity. Table D-2: Private MIB Parameters (Sheet 13 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-19winlink1000OduAgnLastEventsIfIndex 1.3.6.1.4.1.4458.1000.1.7.4.2.1.3 Integer RO Interface Index where the event occurred. Traps that are     not associated with a specific interface will have the following value: 65535. winlink1000OduAgnLastEventsTimeT 1.3.6.1.4.1.4458.1000.1.7.4.2.1.4 Integer RO Timestamp of this trap. This number is in seconds from Midnight January 1st  1970. winlink1000OduAgnLastEventsText 1.3.6.1.4.1.4458.1000.1.7.4.2.1.5 DisplayString RO Trap display text (same as the text in the sent trap). winlink1000IduAdmProductType 1.3.6.1.4.1.4458.1000.2.1.1 DisplayString RO IDU configuration description. winlink1000IduAdmHwRev 1.3.6.1.4.1.4458.1000.2.1.2 DisplayString RO IDU Hardware Revision. winlink1000IduAdmSwRev 1.3.6.1.4.1.4458.1000.2.1.3 DisplayString RO IDU Software Revision. winlink1000OduAdmNumOfExternalAlarmIn 1.3.6.1.4.1.4458.1000.2.1.4 Integer RO Indicates the number of currently available External Alarm Inputs. winlink1000OduAdmExternAlarmInTable N/A This is the External Alarm Inputs table. winlink1000OduAdmExternAlarmInEntry N/A Entry containing the elements of a single External Alarm Input.         INDEX { winlink1000OduAdmExternAlarmInIndex} winlink1000OduAdmExternAlarmInIndex 1.3.6.1.4.1.4458.1000.2.1.5.1.1 Integer RO This value indicates the index of the External Alarm Input entry. winlink1000OduAdmExternAlarmInText 1.3.6.1.4.1.4458.1000.2.1.5.1.2 DisplayString RW This field describes the External Alarm Input. It is an optional string of no more than 64 characters    which will be used in the event being sent as a result of a change in the status of the External Alarm Input.   DEFVAL {Alarm Description} winlink1000OduAdmExternAlarmInAdminState 1.3.6.1.4.1.4458.1000.2.1.5.1.3 Integer RW This value indicates if this External Alarm Input is enabled or disabled. winlink1000OduAdmExternAlarmInStatus 1.3.6.1.4.1.4458.1000.2.1.5.1.4 Integer RO This value indicates the current status of the External Alarm Input. winlink1000IduAdmSN 1.3.6.1.4.1.4458.1000.2.1.6 DisplayString RO IDU Serial Number winlink1000IduAdmIduDetectionMode 1.3.6.1.4.1.4458.1000.2.1.7 Integer RW The parameter defines whether to send Ethernet frames to detect an IDU.    The valid writable values are: userDisabled (3)  userEnabled (4).    A change requires a reset and is effective after reset. winlink1000IduAdmMountedTrunks 1.3.6.1.4.1.4458.1000.2.1.8 Integer RO Number of mounted trunks in the IDU  winlink1000IduAdmLicensedTrunks 1.3.6.1.4.1.4458.1000.2.1.9 Integer RO Number of Licensed Trunks in the IDU  winlink1000IduAdmVlanSupported 1.3.6.1.4.1.4458.1000.2.1.10 Integer RO Identifies if the local IDU supports VLAN tag/untag winlink1000IduAdmVlanEgressMode 1.3.6.1.4.1.4458.1000.2.1.11 DisplayString RW VLAN tag/untag egress values winlink1000IduAdmVlanIngressMode 1.3.6.1.4.1.4458.1000.2.1.12 DisplayString RW VLAN tag/untag ingress values winlink1000IduAdmVlanDefaultPortVIDs 1.3.6.1.4.1.4458.1000.2.1.13 DisplayString RW VLAN tag/untag default VLAN ids for each port - Right most digit is Vlan priority (0-6)  other digits compose Vlan Id (1-4094) winlink1000IduAdmVlanLan1UntaggedVIDs 1.3.6.1.4.1.4458.1000.2.1.14 DisplayString RW VLAN untagged VIDs for LAN1 port winlink1000IduAdmVlanLan2UntaggedVIDs 1.3.6.1.4.1.4458.1000.2.1.15 DisplayString RW VLAN untagged VIDs for LAN2 port winlink1000IduAdmVlanSfpUntaggedVIDs 1.3.6.1.4.1.4458.1000.2.1.16 DisplayString RW VLAN untagged VIDs for Sfp port winlink1000IduAdmVlanLan1FilteredVIDs 1.3.6.1.4.1.4458.1000.2.1.17 DisplayString RW VLAN filtered VIDs for LAN1 port winlink1000IduAdmVlanLan2FilteredVIDs 1.3.6.1.4.1.4458.1000.2.1.18 DisplayString RW VLAN filtered VIDs for LAN2 port winlink1000IduAdmVlanSfpFilteredVIDs 1.3.6.1.4.1.4458.1000.2.1.19 DisplayString RW VLAN filtered VIDs for Sfp port winlink1000IduSrvDesiredTrunks 1.3.6.1.4.1.4458.1000.2.2.2 Integer RW Required trunks bitmap.    Note that the number of possible trunks that can be configured may vary  based on the IDU hardware    configuration  the selected air interface rate and the range of the installation.    The provided Manager application enables the user to select only available configurations.   A change is effective immediately if applied to a master unit and the link is in service mode. Table D-2: Private MIB Parameters (Sheet 14 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-20winlink1000IduSrvServices 1.3.6.1.4.1.4458.1000.2.2.4 ObjectID RO This parameter is reserved to the Manager application provided with the product. winlink1000IduSrvActiveTrunks 1.3.6.1.4.1.4458.1000.2.2.6 Integer RO A bitmap describing the currently open TDM trunks. winlink1000IduSrvAvailableTrunks 1.3.6.1.4.1.4458.1000.2.2.8 Integer RO A bitmap describing the number of TDM trunks that can be opened in the current configuration.    The values take into account the IDU hardware configuration  the air rate and the installation range. winlink1000IduSrvPossibleServicesTable N/A IDU Possible Services table. winlink1000IduSrvPossibleServicesEntry N/A IDU Services table entry.   INDEX { winlink1000IduSrvPossibleServicesIndex } winlink1000IduSrvPossibleServicesIndex 1.3.6.1.4.1.4458.1000.2.2.10.1.1 Integer RO Table index  Rate index of the air interface. winlink1000IduSrvPossibleTdmServices 1.3.6.1.4.1.4458.1000.2.2.10.1.2 Integer RO Deprecated parameter.   A bitmap describing the TDM trunks that can be opened in the corresponding Air Rate. winlink1000IduSrvPossibleEthServices 1.3.6.1.4.1.4458.1000.2.2.10.1.3 Integer RO Deprecated parameter.   This parameter describes if the Ethernet Service can be opened   in the corresponding Air Rate. The valid values are: disabled (0)  enabled (1). winlink1000IduSrvRemainingRate 1.3.6.1.4.1.4458.1000.2.2.10.1.4 Integer RO Current Ethernet bandwidth in bps per air rate. winlink1000IduSrvTrunkCost 1.3.6.1.4.1.4458.1000.2.2.10.1.5 Integer RO Cost of the TDM Service in bps. winlink1000IduSrvAvailServicesTable N/A ODU Possible TDM Services table. winlink1000IduSrvAvailServicesEntry N/A ODU TDM Services table entry.   INDEX { winlink1000IduSrvAvailServicesIndex } winlink1000IduSrvAvailServicesIndex 1.3.6.1.4.1.4458.1000.2.2.11.1.1 Integer RO Table index. The index is the bit mask of the TDM service. winlink1000IduSrvAvailServicesState 1.3.6.1.4.1.4458.1000.2.2.11.1.2 Integer RO Represents the TDM service availability. winlink1000IduSrvAvailServicesMinRateIdx 1.3.6.1.4.1.4458.1000.2.2.11.1.3 Integer RO Minimum rate index of the air interface which make the service possible. winlink1000IduSrvAvailServicesMaxRateIdx 1.3.6.1.4.1.4458.1000.2.2.11.1.4 Integer RO Maximum rate index of the air interface which make the service possible. winlink1000IduSrvAvailServicesReason 1.3.6.1.4.1.4458.1000.2.2.11.1.5 Integer RO Information about the TDM Service availability.    - Not Applicable if the service is available.    The reasons for TDM Service unavailability:    - The available throughput isn't sufficient for Service demands;    - The IDU HW doesn't support the service;    - A Link Password mismatch was detected;    - The external pulse type detected is improper for TDM services;    - A Software versions mismatch was detected.    - A-Symetric TDD Mode Is Obligated. winlink1000IduSrvEthActive 1.3.6.1.4.1.4458.1000.2.2.12 Integer RO Represents the Ethernet service activation state. winlink1000IduSrvEthAvailable 1.3.6.1.4.1.4458.1000.2.2.13 Integer RO Represents the Ethernet service availability state. winlink1000IduSrvEthThroughput 1.3.6.1.4.1.4458.1000.2.2.14 Gauge RO Current available Ethernet service throughput in bps. winlink1000IduSrvEthMaxInfoRate 1.3.6.1.4.1.4458.1000.2.2.15 Integer RW Holds the maximum bandwidth (kbps) to be allocated for Ethernet service.    Value of zero means that Ethernet service works as best effort.    The maximum value is product specific. Refer to the user manual. winlink1000IduSrvAvailableTrunksT1 1.3.6.1.4.1.4458.1000.2.2.16 Integer RO A bitmap describing the TDM trunks that can be opened under T1 configuration.    The values take into account the IDU hardware configuration  the air rate and the installation range. winlink1000IduEthernetIfTable N/A IDU Ethernet Interface table. Table D-2: Private MIB Parameters (Sheet 15 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-21winlink1000IduEthernetIfEntry N/A IDU Ethernet Interface table entry.   INDEX { winlink1000IduEthernetIfIndex } winlink1000IduEthernetIfIndex RO If Index corresponding to this Interface. winlink1000IduEthernetIfAddress 1.3.6.1.4.1.4458.1000.2.3.1.1.5 DisplayString RO IDU MAC address. winlink1000IduEthernetNumOfLanPorts 1.3.6.1.4.1.4458.1000.2.3.3 Integer RO Number of LAN interfaces in the IDU. winlink1000IduEthernetNumOfSfpPorts 1.3.6.1.4.1.4458.1000.2.3.4 Integer RO The number of SFP interfaces in the IDU. winlink1000IduEthernetSfpProperties 1.3.6.1.4.1.4458.1000.2.3.5 DisplayString RO SFP venfor properties : Vendor Name  PN and Revision. winlink1000IduBridgeTpAging 1.3.6.1.4.1.4458.1000.2.4.4.2 Integer RW Timeout in seconds for aging. Note that for this parameter to be effective    the ODU must be configured to HUB mode. A change is effective immediately. winlink1000IduTdmTxClockAvailStates 1.3.6.1.4.1.4458.1000.2.6.1.1 Integer RO Available states of the TDM Transmit Clock Control  each input status is represented by a bit.   When the state is available  the bit value is 1. When the state is unavailable  the bit    value is 0.   The available states are:     bit 2 = Transparent   bit 3 = Local Loop Timed   bit 4 = Remote Loop Timed   bit 5 = Local Internal   bit 6 = Remote Internal winlink1000IduTdmTxClockDesiredState 1.3.6.1.4.1.4458.1000.2.6.1.2 Integer RW Required state of the TDM Transmit Clock Control. A change is effective after re-activation of the TDM service. winlink1000IduTdmTxClockActualState 1.3.6.1.4.1.4458.1000.2.6.1.3 Integer RO Actual state of the TDM Transmit Clock Control. winlink1000IduTdmMasterClockAvailOptions 1.3.6.1.4.1.4458.1000.2.6.2.1 Integer RO Available options of the TDM Master Clock Control  each input status is represented by a bit.   When the option is available  the bit value is 1. When the option is unavailable  the bit value is 0.   The available options are:     bit 2 = Automatic   bit 3 = Trunk #1   bit 4 = Trunk #2   bit 5 = Trunk #3   bit 6 = Trunk #4   When no options are available the returned value is: 1 winlink1000IduTdmMasterClockDesired 1.3.6.1.4.1.4458.1000.2.6.2.2 Integer RW Required TDM Master Clock. A change is effective after re-activation of the TDM service. winlink1000IduTdmMasterClockActual 1.3.6.1.4.1.4458.1000.2.6.2.3 Integer RO Actual Trunk used for TDM Master Clock. winlink1000IduTdmConfigTable N/A IDU TDM Links Configuration table. winlink1000IduTdmConfigEntry N/A IDU TDM Links Configuration table entry.   INDEX { winlink1000IduTdmConfigIndex } winlink1000IduTdmConfigIndex RO Table index. winlink1000IduTdmIfIndex RO Link index in the interface table. winlink1000IduTdmLineCoding 1.3.6.1.4.1.4458.1000.2.6.6.1.6 Integer RW This parameter applies to T1 trunks only. The parameter controls the line coding.   Setting the value to each of the indices applies to all.   A change is effective after the next open of the TDM service. winlink1000IduTdmLoopbackConfig 1.3.6.1.4.1.4458.1000.2.6.6.1.9 Integer RW Loop back configuration table. Each of the trunks can be set Normal  Line loop back or Reverse line loop back.   A change is effective immediately. winlink1000IduTdmLineStatus 1.3.6.1.4.1.4458.1000.2.6.6.1.10 Integer RO Line status. winlink1000IduTdmCurrentTable N/A IDU TDM Links Statistics table. winlink1000IduTdmCurrentEntry N/A IDU TDM Links Statistics table entry.   INDEX { winlink1000IduTdmCurrentIndex } winlink1000IduTdmCurrentIndex RO Table index (Same as winlink1000IduTdmLineIndex). winlink1000IduTdmCurrentBlocks 1.3.6.1.4.1.4458.1000.2.6.7.1.101 Counter RO Number of correct blocks transmitted to the line. winlink1000IduTdmCurrentDrops 1.3.6.1.4.1.4458.1000.2.6.7.1.102 Counter RO Number of error blocks transmitted to the line. Table D-2: Private MIB Parameters (Sheet 16 of 18)Name OID TypeAccessDescription
MIB Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-22winlink1000IduTdmCurrentTxClock 1.3.6.1.4.1.4458.1000.2.6.7.1.103 Integer RW TDM Transmit Clock. A change is effective after re-activation of the TDM service. winlink1000IduTdmCurrentBlocksHigh 1.3.6.1.4.1.4458.1000.2.6.7.1.104 Counter RO High part of the 64 bits counter Current Blocks winlink1000IduTdmRemoteQual 1.3.6.1.4.1.4458.1000.2.6.8 Integer RO Estimated average interval between error second events.    The valid values are 1-2^31 where a value of -1 is used to indicate an undefined state. winlink1000IduTdmRemoteQualEval 1.3.6.1.4.1.4458.1000.2.6.9 Integer RO Estimated average interval between error second events during evaluation process.   The valid values are 1-2^31 where a value of -1 is used to indicate an undefined state. winlink1000IduTdmSrvEval 1.3.6.1.4.1.4458.1000.2.6.10 Integer RW Evaluated TDM service bit mask.   Setting this parameter to value that is bigger than the activated TDM service bit mask    will execute the evaluation process for 30 seconds.    Setting this parameter to 0 will stop the evaluation process immediately. winlink1000IduTdmBackupAvailableLinks 1.3.6.1.4.1.4458.1000.2.6.11 Integer RO Number of TDM backup trunks. winlink1000IduTdmBackupTable N/A IDU TDM Links Statistics table. winlink1000IduTdmBackupEntry N/A IDU TDM Links Statistics table entry.   INDEX { winlink1000IduTdmBackupIndex } winlink1000IduTdmBackupIndex 1.3.6.1.4.1.4458.1000.2.6.12.1.1 Integer RO Table index. winlink1000IduTdmBackupMode 1.3.6.1.4.1.4458.1000.2.6.12.1.2 Integer RW TDM backup mode: Enable or Disable  where the     main link is the air link or the external link.    Changes will be effective immediatly. winlink1000IduTdmBackupCurrentActiveLink 1.3.6.1.4.1.4458.1000.2.6.12.1.3 Integer RO TDM backup current active link: N/A      air link is active or external link is active. winlink1000IduTdmJitterBufferSize 1.3.6.1.4.1.4458.1000.2.6.13 Integer RW TDM Jitter Buffer Size.    The value must be between the minimum and the maximum TDM Jitter Buffer Size.      The units are 0.1 x millisecond. winlink1000IduTdmJitterBufferDefaultSize 1.3.6.1.4.1.4458.1000.2.6.14 Integer RO TDM Jitter Buffer Default Size. The units are 0.1 x millisecond. winlink1000IduTdmJitterBufferMinSize 1.3.6.1.4.1.4458.1000.2.6.15 Integer RO TDM Jitter Buffer Minimum Size. The units are 0.1 x millisecond. winlink1000IduTdmJitterBufferMaxSize 1.3.6.1.4.1.4458.1000.2.6.16 Integer RO TDM Jitter Buffer Maximum Size. The units are 0.1 x millisecond. winlink1000IduTdmJitterBufferSizeEval 1.3.6.1.4.1.4458.1000.2.6.17 Integer RW TDM Jitter Buffer Size for evaluation.     The value must be between the minimum and the maximum TDM Jitter Buffer Size.     The units are 0.1 x millisecond. winlink1000IduTdmType 1.3.6.1.4.1.4458.1000.2.6.18 Integer RW TDM Type (The value undefined is read-only). winlink1000IduTdmTypeEval 1.3.6.1.4.1.4458.1000.2.6.19 Integer RW TDM Type for evaluation. winlink1000IduTdmLineStatusStr 1.3.6.1.4.1.4458.1000.2.6.20 DisplayString RO Line status. winlink1000IduTdmHotStandbySupport 1.3.6.1.4.1.4458.1000.2.6.21 Integer RO Indicates if Hot Standby is supported. winlink1000IduTdmDesiredHotStandbyMode 1.3.6.1.4.1.4458.1000.2.6.22 Integer RW Desired Hot Standby Mode. winlink1000IduTdmHotStandbyOperationStatus1.3.6.1.4.1.4458.1000.2.6.23 Integer RO The Link Actual Status. winlink1000IduTdmBackupLinkConfiguration 1.3.6.1.4.1.4458.1000.2.6.24 Integer RW The current configuration of the backup link. winlink1000GeneralTrapDescription 1.3.6.1.4.1.4458.1000.100.1 DisplayString RO Trap's Description. Used for Trap parameters. winlink1000GeneralTrapSeverity 1.3.6.1.4.1.4458.1000.100.2 Integer RO Trap's Severity. Used for Trap parameters. winlink1000GeneralCookie 1.3.6.1.4.1.4458.1000.100.3 DisplayString RW Reserved for the Manager application provided with the product  used for saving user preferences affecting ODU operation. winlink1000GeneralEcChangesCounter 1.3.6.1.4.1.4458.1000.100.4 Integer RO This counter is initialized to 0 after a device reset and is incremented upon each element constant write operation   via SNMP or Telnet. Table D-2: Private MIB Parameters (Sheet 17 of 18)Name OID TypeAccessDescription
MIB Traps Appendix DRADWIN 2000 User Manual Release  2.5.40 D-23MIB TrapsGeneralEach ODU can be configured with up to 10 different trap destinations. When the link is oper-ational, each ODU sends traps originating from both Site A and Site B.The source IP address of the trap is the sending ODU. The trap originator can be identified by the trap Community string or by the trap description text.Each trap contains a trap description and additional relevant information such as alarm sever-ity, interface index, time stamp and additional parameters.winlink1000GeneralTelnetSupport 1.3.6.1.4.1.4458.1000.100.5 Integer RW Enable/Disable Telnet protocol. Table D-2: Private MIB Parameters (Sheet 18 of 18)Name OID TypeAccessDescription
Trap Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-24Trap ParametersTable D-3: MIB Traps (Sheet 1 of 5)Name ID Severity DescriptiontrunkStateChanged 1 normal Indicates a change in the state of one of the TDM trunks.   Raised by both sides of the link.   Contains 3 parameters:   1 - Description: TDM Interface %n - %x   2 - %n: Is the trunk number   3 - %x: Is the alarm type and can be one of the following: Normal  AIS  LOS  Loopback    linkUp 2 normal Indicates that the radio link is up.   Contains a single parameter  which is its description:   1 - Description: Radio Link - Sync on channel %n GHz.   %n Is the channel frequency in GHz.    linkDown 3 critical Indicates that the radio link is down.   Contains a single parameter  which is its description:   1 - Description: Radio Link - Out of Sync. The reason is: %s.   %s Is the reason.    detectIDU 4 normal Indicates that the IDU was detected.   Raised by both sides of the link.   Contains a single parameter  which is its description:   1 - Description: IDU of Type %s was Detected.   %s Is the type of the IDU.    disconnectIDU 5 major Indicates that the IDU was disconnected.   Raised by both sides of the link.   Contains a single parameter  which is its description:   1 - Description: IDU Disconnected.    mismatchIDU 6 major Indicates a mismatch between the IDUs.   Raised by the master only.   Contains a single parameter  which is its description:   1 - Description: IDUs Mismatch: One Side is %s and the Other is %s.   %s Is the type of the IDU.    openedServices 7 normal Indicates that services were opened. Raised by the master only.   Contains 3 parameters:   1 - Description: %n2 out of %n1 Requested TDM Trunks have been Opened   2 - %n1: Is the requested number of TDM truncks   3 - %n2: Is the actual number of TDM trunks that were opened    closedServices 8 normal Indicates that services were closed.   Raised by the master only.   Contains a single parameter  which is its description:   1 - Description: TDM Service has been closed. The reason is: %s.   %s Is the reason.    incompatibleODUs 9 critical Indicates that the ODUs are incompatible.   Contains a single parameter  which is its description:   1 - Description: Incompatible ODUs.    incompatibleIDUs 10 major Indicates that the IDUs are incompatible.   Contains a single parameter  which is its description:   1 - Description: Incompatible IDUs.    incompatibleOduIdu 11 major Indicates that the ODU and IDU are incompatible.   Contains a single parameter  which is its description:   1 - Description: The IDU could not be loaded. The reason is: %s.   %s Is the incompatibility type.    probingChannel 12 normal Indicates that the ODU is monitoring radar activity. Contains a single parameter  which is its description:   1 - Description: Monitoring for radar activity on channel %n GHz.   %n is the channel frequency in GHz.    radarDetected 13 normal Indicates that radar activity was detected.   Contains a single parameter  which is its description:   1 - Description: Radar activity was detected in %s  on channel %n GHz.   %s Is the site name.   %n Is the channel frequency in GHz.    transmittingOnChannel 14 normal Indicates that the ODU is transmitting on channel.   Contains a single parameter  which is its description:   1 - Description: Transmitting on channel %n GHz.   %n Is the channel frequency in GHz.    scanningChannels 15 normal Indicates that the ODU is scanning channels.   Contains a single parameter  which is its description:   1 - Description: Channel scanning in progress.    incompatiblePartner 16 critical Indicates that configuration problem was detected and that link installation is required in order to fix it.   Contains a single parameter  which is its description:   1 - Description: Configuration problem detected. Link installation required.    timeClockSet 17 normal Indicates that the ODU time clock was set.   Contains a single parameter  which is its description:   1 - Description: The time was set to: %p.   %p Is the date and time.    configurationChanged 18 normal Indicates that the ODU recovered from an error  but there are configuration changes.   Contains two parameters:   1 - Description: Configuration changed. Error code is: %n.   2 - %n number.
Trap Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-25hssOpStateChangedToINU 19 normal Indicates that the HSS operating state was changed to INU type.   Contains a single parameter  which is its description:   1 - Description: HSS operating state was changed to: INU.    hssOpStateChangedToHSM 20 normal Indicates that the HSS operating state was changed to HSM type.   Contains a single parameter  which is its description:   1 - Description: HSS operating state was changed to: HSM.    hssOpStateChangedToHSC 21 normal Indicates that the HSS operating state was changed to HSC type.   Contains a single parameter  which is its description:   1 - Description: HSS operating state was changed to: HSC_DT/HSC_CT. vlanModeActive 22 normal    Indicates to non-VLAN PC that after 2 minutes the system will support only VLAN   tag on management interface. Contains a single parameter  which is its description:   1 - Description: VLAN Mode is active. Non-VLAN traffic will be blocked in 2 minutes.    spectrumAnalysis 23 normal Indicates that the ODU is in Spectrum Analysis mode.   Contains a single parameter  which is its description:   1 - Description: Spectrum analysis in progress.    tdmServiceAlarm 100 major Indicates that TDM Service is in alarm state.   Contains a single parameter  which is its description:   1 - Description: TDM Service - Alarm.    ethServiceClosed 101 major Indicates that Ethernet Service is closed.   Contains a single parameter  which is its description:   1 - Description: Ethernet Service is closed.    ethServiceNotPermitted 102 major Indicates that Ethernet Service is not permitted.   Contains a single parameter  which is its description:   1 - Description: A valid IDU could not be detected at %s. Please check your configuration.   %s - Is the Local Site name or Remote Site name or both sides of the Link.    encryptionAlarm 103 major Indicates an encryption key mismatch.   Contains a single parameter  which is its description:   1 - Description: Encryption Status - Failed. No Services are available.    changeLinkPasswordAlarm 104 major Indicates that a failure has occurred while attempting to change the Link Password.   Contains a single parameter  which is its description:   1 - Description: Failed to change the Link Password at/on: %s.   %s - Is the Local Site name or Remote Site name or both sides of the Link.    externalAlarmInPort1Alarm 105 major The trap is sent every time an alarm occurs in the External Alarm Input of port #1.   Contains a single parameter  which is its description:   1 - Description: External Alarm 1 - <User Text> - Alarm.    externalAlarmInPort2Alarm 106 major The trap is sent every time an alarm occurs in the External Alarm Input of port #2.   Contains a single parameter  which is its description:   1 - Description: External Alarm 2 - <User Text> - Alarm.    bitFailedAlarm 107 major The trap is sent if there is no way to recover from the situation.Contains two parameters:   1 - Description: ODU power up built in test failed. Error code is: %n   2 - %n number    wrongConfigurationLoadedAlarm 108 major The trap is sent if there is a way to recover from the situation.Contains two parameters:   1 - Description: Wrong configuration loaded. Error code is: %n   2 - %n number    lanPort1DisconnectedAlarm 109 major Indicates the LAN port 1 status changed to disconnected.Contains a single parameter  which is its description:   1 - Description: LAN port 1 status changed to disconnected.    lanPort2DisconnectedAlarm 110 major Indicates the LAN port 2 status changed to disconnected.Contains a single parameter  which is its description:   1 - Description: LAN port 2 status changed to disconnected.    mngPortDisconnectedAlarm 111 major Indicates the management port status changed to disconnected.Contains a single parameter  which is its description:   1 - Description: Management port status changed to disconnected.    externalAlarmInPort3Alarm 112 major The trap is sent every time an alarm occurs in the External Alarm Input of port #3.   Contains a single parameter  which is its description:   1 - Description: External Alarm 3 - <User Text> - Alarm.    externalAlarmInPort4Alarm 113 major The trap is sent every time an alarm occurs in the External Alarm Input of port #4.   Contains a single parameter  which is its description:   1 - Description: External Alarm 4 - <User Text> - Alarm.    Table D-3: MIB Traps (Sheet 2 of 5)Name ID Severity Description
Trap Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-26swVersionsMismatchFullCompatibilityAlarm 114 warning The trap is sent if SW versions mismatch with full link functionality.   Contains a single parameter  which is its description:   1 - Description: Software versions mismatch - full link functionality    swVersionsMismatchRestrictedCompatibilityAlarm 115 minor The trap is sent if SW versions mismatch with restricted link functionality.   Contains a single parameter  which is its description:   1 - Description: Software versions mismatch - restricted link functionality    swVersionsMismatchSoftwareUpgradeRequired 116 major The trap is sent if SW versions mismatch and SW upgrade is required.   Contains a single parameter  which is its description:   1 - Description: Software versions mismatch - Software upgrade required    swVersionsIncompatible 117 critical The trap is sent if SW versions are incompatible.   Contains a single parameter  which is its description:   1 - Description: SW Versions incompatible    hssMultipleSourcesDetectedAlarm 118 major Indicates that multiple sync pulse sources were detected.   Contains a single parameter  which is its description:   1 - Description: HSS multiple sync sources were detected.    hssSyncToProperSourceStoppedAlarm 119 major Indicates that synchronization to a proper sync pulse source was stopped.   Contains a single parameter  which is its description:   1 - Description: HSS sync pulse - Down. The reason is: %s.   %s - Is the reason for the sync down.    hssSyncPulseDetectedAlarm 120 major Indicates that HSS additional sync pulse was detected.   Contains a single parameter  which is its description:   1 - Description: HSS additional sync pulse was detected. tdmBackupAlarm 121 major Indicates that the TDM backup link was activated.   Contains a single parameter  which is its description:   1 - Description: TDM backup alarm - backup link was activated.    linkLockUnauthorizedRemoteODU 122 major Indicates that the remote ODU is unauthorized.    Contains a single parameter  which is its description:   1 - Description: Unauthorized remote ODU connection rejected.    linkLockUnauthorizedODU 123 major Indicates that the ODU is unauthorized.    Contains a single parameter  which is its description:   1 - Description: Unauthorized ODU connection rejected.    hotStandbyAlarm 124 major Indicates that the hot standby secondary link was activated.   Contains a single parameter  which is its description:   1 - Description: Secondary Link Is Active.    sfpInsertion 126 normal Indicates that a device was inserted to SFP Port    sfpPort1DisconnectedAlarm 127 major Indicates the SFP port 1 status changed to disconnected.Contains a single parameter which is its description:   1 - Description: SFP port 1 status changed to disconnected.    desiredRatioCanNotBeAppliedAlarm 129 normal Indicates Desired UL/DL RAtio Can Not Be Applied.    cbwMismatch 130 major Indicates that a Channel Bandwidth mismatch was detected.Contains two parameters:   1 - Description: Channel Bandwidth Mismatch: one side is %n0 MHz and the other is %n1 MHz.   %n0 is the local Channel Bandwidth value in MHz.   %n1 is the remoet Channel Bandwidth value in MHz. gpsNotSynchronized 131 major Indicates that the GPS is not synchronized with satellites.   Pulses are self generated.pdTooHighDueCbwLimitations 132 major Indicates that link cannot be established because link range is too large for channel bandwidth.tdmServiceClear 200 major Indicates that TDM Service fault is cleared.   Contains a single parameter  which is its description:   1 - Description: TDM Service - Normal.    ethServiceOpened 201 normal Indicates that Ethernet Service has been opened.   Contains a single parameter  which is its description:   1 - Description: Ethernet Service has been opened.    encryptionClear 203 normal Indicates that encryption is OK.   Contains a single parameter  which is its description:   1 - Description: Encryption Status - Normal.    changeLinkPasswordClear 204 normal Indicates that the Link Password was changed successfully.   Contains a single parameter  which is its description:   1 - Description: Link Password has been changed at/on: %s.   %s - Is the Local Site name or Remote Site name or both sides of the Link.    Table D-3: MIB Traps (Sheet 3 of 5)Name ID Severity Description
Trap Parameters Appendix DRADWIN 2000 User Manual Release  2.5.40 D-27externalAlarmInPort1Clear 205 normal This Trap is sent every time an External Alarm Input fault of port # 1 is cleared.   Contains a single parameter  which is its description:   1 - Description: External Alarm 1 - <User Text> - Alarm Cleared.    externalAlarmInPort2Clear 206 normal This Trap is sent every time an External Alarm Input fault of port # 2 is cleared.   Contains a single parameter  which is its description:   1 - Description: External Alarm 2 - <User Text> - Alarm Cleared. lanPort1Clear 209 normal Indicates the LAN port 1 status changed to connected.   Contains two parameters:   1 - Description: LAN port 1 status changed to connected - %s   2 - %s Is the Eth. mode (speed & duplex)    lanPort2Clear 210 normal Indicates the LAN port 2 status changed to connected.   Contains two parameters:   1 - Description: LAN port 2 status changed to connected - %s.   2 - %s Is the Eth. mode (speed & duplex).    mngPortClear 211 normal Indicates the management port status changed to connected.   Contains two parameters:   1 - Description: Management port status changed to connected - %s   2 - %s Is the Eth. mode (speed & duplex)    externalAlarmInPort3Clear 212 normal This Trap is sent every time an External Alarm Input fault of port # 3 is cleared.   Contains a single parameter  which is its description:   1 - Description: External Alarm 3 - <User Text> - Alarm Cleared.    externalAlarmInPort4Clear 213 normal This Trap is sent every time an External Alarm Input fault of port # 4 is cleared.   Contains a single parameter  which is its description:   1 - Description: External Alarm 4 - <User Text> - Alarm Cleared.    swVersionsMatchFullCompatibilityClear 214 normal The trap is sent if SW versions match.   Contains a single parameter  which is its description:   1 - Description: Software Versions compatible    swVersionsMatchRestrictedCompatibilityClear 215 normal The trap is sent if SW versions match and link functionality is not restricted.   Contains a single parameter  which is its description:   1 - Description: Software Versions compatible    swVersionsMatchSoftwareUpgradeRequiredClear 216 normal The trap is sent if SW versions match and SW upgrade is successful.   Contains a single parameter  which is its description:   1 - Description: Software Versions compatible    swVersionsCompatibleClear 217 normal The trap is sent if SW versions compatible   Contains a single parameter  which is its description:   1 - Description: Software Versions compatible    hssMultipleSourcesDisappearedClear 218 normal Indicates that multiple sync pulse sources disappeared.   Contains a single parameter  which is its description:   1 - Description: HSS multiple sync pulse sources disappeared.    hssSyncToProperSourceAchievedClear 219 normal Indicates that synchronization to a proper Sync source was achieved.   Contains a single parameter  which is its description:   1 - Description: HSS sync pulse - Up.    hssSyncPulseDisappearedClear 220 normal Indicates that HSS additional sync pulse disappeared.   Contains a single parameter  which is its description:   1 - Description: HSS additional sync pulse was disappeared. tdmBackupClear 221 normal Indicates that the TDM main link was activated.   Contains a single parameter  which is its description:   1 - Description: TDM main link was activated.    linkLockAuthorizedRemoteODU 222 normal Indicates that the remote ODU is authorized.   Contains a single parameter  which is its description:   1 - Description: Authorized remote ODU connection accepted.    linkLockAuthorizedODU 223 normal Indicates that the ODU is authorized.   Contains a single parameter  which is its description:   1 - Description: Authorized ODU connection permitted.    linkAuthenticationDisabled 224 normal Indicates that the Link Lock is disabled.   Contains a single parameter  which is its description:   1 - Description: Link Authentication has been disabled.    hotStandbyClear 225 normal Indicates that the Primary Link Was Activated.   Contains a single parameter  which is its description:   1 - Description: Primary Link Is Active.    sfpExtraction 226 normal Indicates that a device was extracted from SFP Port    sfpPort1Clear 227 normal Indicates the SFP port 1 status changed to connected.   Contains two parameters:   1 - Description: SFP port 1 status changed to connected - %s   2 - %s Is the Eth. mode (speed & duplex)    Table D-3: MIB Traps (Sheet 4 of 5)Name ID Severity Description
RADWIN Manager Traps Appendix DRADWIN 2000 User Manual Release  2.5.40 D-28RADWIN Manager TrapsThe RADWIN Manager application issues traps to indicate various events. These traps are shown in the RADWIN Managerr Events Log.A list of Trap Messages as displayed by the RADWIN Manager is shown in Table 9-5. compatibleIdus 228 normal Indicates that the ODU has identified compatible Idus on both sides of the link.    desiredRatioCanNotBeAppliedClear 229 normal Indicates Current UL/DL Ratio Is Equal To Desired Ratio.    cbwMatch 230 normal Indicates that a Channel Bandwidth match was detected.   Contains a single parameter  which is its description:   1 - Channel Bandwidth value in MHz.    switchCbwAndChannel 231 normal Indicates that the system is switching Channel Bandwidth and channel frequency.   Contains two parameters:   1 - Switching to Channel Bandwith %n0 MHz and to channel %n1 GHz.    ringRplStateIdle 232 normal RPL state changed to Idle.ringEthServiceStatus 233 normal Indicates Ethernet service's state - blocked \ unblocked.   Contains a single parameter:   1 - Description: Ethernet's state (blocked \ unblocked)ringFirstRpmReceived 234 normal Ring application: in non-RPL link indicates first from a specific RPL was received.   Contains a single parameter:   1 - Description: RPM's VLAN IDringEthernetSrviceUnblockedTO 235 normal Ring application: in non-RPL link Ethernet service is unblocked due to RPM timeout.gpsSynchronized 236 normal Indicates that the GPS is synchronized with satellites.Table D-3: MIB Traps (Sheet 5 of 5)Name ID Severity Description
RADWIN 2000 User Manual Release  2.5.40 E-1Appendix EExternal AlarmsSpecificationExternal Alarms SpecificationThe IDU-C and new style IDU-E support external input and output alarms through a standard DB25 pin female connector (see page B-3 for pinout details).Input alarmsThe input alarms are raised by events from external equipment, such as a fire warning, door open or air conditioner failure. They are user defined.Output alarmsOutput alarms are generated through dry contact relays to indicate vari-ous system events such as sync loss or disconnection. An alarm is raised if at least one of the conditions in one of the tables below, is met.IDU-C and new style IDU-E Alarms Table E-1: IDU-C/E - Output Alarms DescriptionAlarm Description Alarm On Conditions Alarm Off ConditionOutput 1 Air interface Alarm • Link is down• Link in installation mode• Link authentication problem Link is up or equipment alarm is ONOutput 2 Equipment Alarm • Built in Test (BIT) error• No connection to the ODU Both ODU and IDU are in operational stateOutput 3 Service Alarm at Site BN/A Permanently offOutput 4 Power Failure at Site B Link Loss due to Power Failure at Site B Link is up or down without power failure indication within the last two seconds
IDU-C and new style IDU-E Alarms Appendix ERADWIN 2000 User Manual Release  2.5.40 E-2 Table E-2: IDU-C - Input Alarms DescriptionAlarm Description Alarm On Conditions Alarm Off ConditionInput 1User Defined External Alarm Voltage in range -10 to -50VDC Voltage > 0VDCInput 2Input 3Input 4
RADWIN 2000 User Manual Release  2.5.40 F-1Appendix FRF ExposureThe antennas used for the following transmitters must be installed so as to provide a mini-mum separation distance from by-standers as specified in the following tables:Table F-1: Safety Distances for RADWIN 2000 FCC and IC ProductsFrequency Band [GHz] FCC ID IC ID Antenna gain [dBi] Min. Safety Distance [cm]5.8 Q3KRW2058 5100A-RW2054 28 2235.8 Q3KRW2058 5100A-RW2054 24 1415.3/5.4 Q3KRW2054 5100A-RW2054 23.5 / 28 204.9 Q3KRW2049 5100A-RW2054 28 2254.9 Q3KRW2049 5100A-RW2054 21 1132.4 Q3KRW2024 5100A-RW2054 19 392.4 Q3KRW2024I 5100A-RW2024I 17.5 402.5 Q3KRW2025 N/a 24 104.63.5 N/A 5100A-RW2030 25 923.6/3.7 Q3KRW2030 5100A-RW2030 25 86Table F-2: Safety Distances for RADWIN 2000 ETSI ProductsFrequency Band [GHz] Antenna gain [dBi] Min. Safety Distance [cm]5.8 24 / 28 205.4 23.5 / 28 205.3 23.5 / 28 202.4 19 / 17.5 203.5 25 200
RADWIN 2000 User Manual Release  2.5.40 G-1Appendix GRegional Notice: FrenchCanadianProcédures de sécuritéGénéralitésAvant de manipuler du matériel connecté à des lignes électriques ou de télécommunications, il est conseillé de se défaire de bijoux ou de tout autre objet métallique qui pourrait entrer en contact avec les éléments sous tension.Mise à la terreTous les produits RADWIN doivent être mis à la terre pendant l'usage courant. La mise à la terre est assurée en reliant la fiche d'alimentation à une prise de courant avec une protection de terre. En outre: •  La cosse de masse  sur l'IDU-C doit être constamment connectée à la protection de terre, par un câble de diamètre de 18 AWG ou plus. Le matériel monté sur rack doit être installé seulement sur des racks ou armoires reliés à la terre•  Une ODU doit mise à la terre par un câble de diamètre de 12 AWG ou plus•  Il ne doit pas y avoir de fusibles ou d'interrupteurs sur la connection à la terre De plus:•  Il faut toujours connecter la terre en premier et la déconnecter en dernier•  Il ne faut jamais connecter les câbles de télécommunication à du matériel non à la terre•  Il faut s'assurer que tous les autres câbles sont déconnectés avant de déconnecter la terreProtection contre la foudreL'utilisation de dispositifs de protection contre la foudre dépend des exigences réglementaires et de l'utilisateur final. Toutes les unités extérieures RADWIN sont conçues avec des circuits de limitation de surtension afin de minimiser les risques de dommages dus à la foudre. RAD-
Précautions de sécurité pendant le montage de ODU Appendix GRADWIN 2000 User Manual Release  2.5.40 G-2WIN conseille l'utilisation d'un dispositif de parafoudre supplémentaire afin de protéger le matériel de coups de foudre proches.Matériel supplémentaire requisL'équipement requis pour l'installation du matériel est le suivant:• Pince à sertir RJ-45 (si un câble pré-assemblé ODU/IDU n'est pas utilisé)• Perceuse (pour le montage sur mur seulement)•Câbles de terre IDU et ODU• Clef 13 mm (½)• Câble ODU - IDU si non commandé (type extérieur, CAT-5e, 4 paires torsadées, 24 AWG)• Colliers de serrage • Ordinateur portable avec Windows 2000 ou Windows XP.Précautions de sécurité pendant le montage de ODUAvant de connecter un câble à l'ODU, la borne protectrice de masse (visse) de l'ODU doit être connectée à un conducteur externe protecteur ou à un pylône relié à la terre. Il ne doit pas y avoir de fusibles ou d'interrupteurs sur la connection à la terre.Seulement un personnel qualifié utilisant l'équipement de sécurité approprié doit pouvoir monter sur le pylône d'antenne. De même, l'installation ou le démontage de ODU ou de pylônes doit être effectuée seulement par des professionnels ayant suivi une formation.Pour monter l'ODU:1. Vérifier que les supports de fixation de l'ODU sont correctement mis à la terre.2. Monter l'unité ODU sur le pylône ou sur le mur; se référer à la Installation sur pylône et mur au dessous.3. Connecter la câble de terre au point de châssis sur l'ODU.4. Relier le câble ODU-IDU au connecteur ODU RJ-45.5. Visser les presses-étoupe de câbles pour assurer le scellement hermétique des unités ODU.6. Attacher le câble au pylône ou aux supports en utilisant des colliers classés UV.7. Répéter la procédure sur le site distant.Connecter la terre à IDU-CConnecter un câble de terre de 18 AWG à la borne de masse de l'appareil. L'appareil doit être constamment connecté à la terre.Installation sur pylône et murL' ODU ou l'O-PoE peuvent être montés sur un pylône ou un mur.PrudenceNe pas se placer en face d'une ODU sous tension.
Contenu du kit de montage ODU Appendix GRADWIN 2000 User Manual Release  2.5.40 G-3Contenu du kit de montage ODULe kit de montage ODU comprend les pièces suivantes:• une grande clame (voir Figure G-1)•une petite clame (voir Figure G-2)• un bras (voir Figure G-3)• quatre visses hex tête M8x40• deux visses hex tête M8x70• quatre rondelles plates  M8• trois rondelles élastiques M8• deux écrous M8.Montage sur un pylônePrudence• Les appareils sont prévus pour être installés par un personnel de service.• Les appareils doivent être connectés à une prise de courant avec une protection de terre.• Le courant CC du IDU-C doit être fourni par l'intermédiaire d'un disjoncteur bipolaire et le diamètre du câble doit être de 14 mm avec un conduit de 16 mm.Figure G-1: grande clameFigure G-2: petite clameFigure G-3: bras
Montage sur un pylône Appendix GRADWIN 2000 User Manual Release  2.5.40 G-4Figure G-4: Montage sur un pylône
Montage sur un mur Appendix GRADWIN 2000 User Manual Release  2.5.40 G-5Montage sur un murFigure G-5: Montage sur un mur
Montage d'une antenne externe Appendix GRADWIN 2000 User Manual Release  2.5.40 G-6Montage d'une antenne externeL'antenne externe optionnelle peut être montée sur un pylône.Contenu du kit de montage d'une antenne externeLe kit de montage d'une antenne externe comprend les pièces suivantes•Douze rondelles plates• Huit rondelles élastiques• Huit écrous hex• Quatre boulons• Un support en U• Un support à pivotement• Deux courroies de fixation en métalPour installer une antenne externe sur un pylône:1. Attacher le support en U à l'arrière de l'antenne en utilisant quatre rondelles plates, quatre rondelles élastiques et quatre écrous hex.2. Attacher le support à pivotement au support en U en utilisant huit rondelles plates, quatre rondelles élastiques, quatre écrous hex et quatre boulons.3. Passer les deux courroies de fixation par les fentes verticales dans le support à pivot-ement.4. Attacher l'antenne au pylône en utilisant les deux courroies de fixation .Ajuster l'inclinaison nécessaire en utilisant l'échelle angulaire et serrer tous les boulons et écrous à la position requise.
RADWIN 2000 User Manual Release 2.5.40 Index 1AAAR 1-6ACS 5-7, 8-26aging time, ODU Bridge Mode 8-16Air Interface 1-13, 1-13Technical Specifications, general A-1AlarmsActivesummary 9-17Connector B-3External , specification E-1AntennasAir rates 5-11Align with beeper 3-13Aligning 3-13bipolar 3-13Buzzer signals 3-14monopolar 3-14Cable, grounding 18-1Connecting 3-13Described 1-12Diversity Mode 5-10External 1-13Mounting 3-7Package Contents 3-5External, Mounting 17-4MIMO - Diversity settings 5-11MIMO Mode 5-10Single and dual 5-9types 1-9ApplicationsBroadband Access 1-4, 1-4Cellular Backhaul 1-4Private Networks 1-5WiMAX 1-4Asymmetric Ethernetand Collocation 5-19and TDM services 5-20Installation 5-18Restrictions 5-19Transmission ratio 5-18, 6-5Automatic Adaptive Rate, see AAR 1-6Automatic Channel Selection, see ACSAutomatic Repeat Request 1-6BBackup 8-24backupODU replacement 9-20Backup and restore software, ODU 8-24Bandand DFS 20-5available 1-9Changing 20-1defaults 1-9, 20-3license key 1-9Beepermute 8-25muting and restoring 8-2restore 8-25Bridge mode,Telnet commands 8-26BRS 1-2, 1-3CChanging link password 5-5Channel, selecting 5-7Clock configuration, TDM 5-27Community StringsChanging 8-10Editing 8-10Forgotten passwords 8-10MIB D-2Read-Only 8-9Read-Write 8-9Trap 8-9Configuration Parameters 8-3ConfiguringAdvanced 8-2, 8-15, 8-17, 8-19Air Interface 8-2Air interface 7-1contact person 8-2Date and Time 8-2Date and time 8-1Ethernet settings 8-1External alarms 8-1Frequency channel 7-1Index
RADWIN 2000 User Manual Release2.5.40 Index 2HSS 8-1Security 8-2Security settings 8-1Service parameters 7-1System 8-2System parameters 7-1System settings 8-1TDM MHS status 8-1Tx Power and antenna 8-1View Inventory 8-2Connecting user equipment 5-7Customer Support 9-21DDate and time, setting 8-2, 8-13DC Powerterminal pinout B-4DFS 16-1changing band for 20-5Configuration 16-4Link Activation 16-1EEthernet Ring 13-11 + 1 13-6operation 13-2Protection Switching 13-6purpose 13-1setting up, ff 13-7supported topologies 13-4terminology 13-1Eventscolor codes 9-16log 9-2, 9-9priority 9-16FFactory settingsrevert to 8-1, 8-22, 9-21FCC/IC DFS Installation Procedure 16-1FEC 5-10, 5-11, A-1, A-1Forward Error Correction, see FECGGateway 8-2Telnet display 8-26GSU A-6Cascaded Sites 11-3Configuring 11-5Installation 11-4Kit 11-4Preferences 11-12Redundancy 11-3Software Update 11-13Telnet Support 11-12Transmission Phase 11-3, 11-9Tx Transmission Ratio 11-9use functionalityscenarios 11-1GUSand RFP 11-8HHSS 10-1and asymmetric allocation 10-11and asymmetric allocation<$endtrange 5-19Hardware Installation 10-3IDU-C front panel LEDs 3-11, 10-12ODU/HSS Connection Pinout 10-7, B-1Radio Frame Pattern Table 10-7HSS Client 10-2Continue Transmission 10-3Disable Transmission 10-3HSS Master 10-2Hub Site Synchronization, see HSSIIDUAging time 8-16aging time, ODU Bridge Mode 8-16Connecting to ODU 3-11described 1-9IDU-CAlarm Connector B-3Front panel 1-10, 1-11Described 3-9LEDs 3-9, 3-10, 4-3Front panel LEDs for HSSLEDs 3-11, 10-12Mounting 3-9Power connections 3-11, 3-11Installing IDU-E and R units 3-8Package Contents 3-4IDU-CPackage Contents 3-4IDU-E or IDU-R package contents 3-4Indoor Unit, see IDUInstallationMenu and Toolbar Functionality 6-3Post Configuration main window 7-13Post Installation main window 5-30see Link, InstallationInstallation Mode 8-2, 8-2, 8-17Interferencecaused by collocated units 10-2Inventory 8-1, 8-10Displaying 8-8IP address 8-2Telnet display 8-26
RADWIN 2000 User Manual Release2.5.40 Index 3JJitter Buffer 5-23KKey Features of Radio LinkAdvanced Air Interface 1-6Air Interface 1-6Capacity 1-5Combo Frequency Products 1-6E1/T1 + Ethernet in one Solution 1-5Installation and management 1-7Multi-band Products 1-6Range performance 1-6Security 1-7SFP support 1-8Spectral Efficiency 1-5Transmission (Tx) power 1-6LLBC 9-8Browser warnings 21-6Calculations 21-2Climactic C Factors 21-11described 21-1Fresnel Zone, described 21-3Internal data 21-1Running 21-5User input 21-1License keyband 1-9License Key, entering 20-5Lightning and Grounding Guidelines 18-1LinkBudget Calculator, see LBCConfigurationStep 1 - Start the Wizard 7-3Step 2 - System Parameters 7-3Step 3 - Channel Settings 7-4Step 4 - Tx Power and Antenna Settings 7-8Step 5 - Hub Site Synchronization Settings7-10Step 6 - Services 7-10Step 7 - TDM Clock Configuration 7-11Step 8 - Configuration Summary and Exit 7-12default frequency 5-7default Settings 4-11Information 9-1Air Interface ThresholdsBBER Threshold 9-13Ethernet Thresholds - Capacity 9-13Ethernet Thresholds - Traffic 9-13RSL Threshold 9-13TSL THreshold 9-13Air Interface Thresholds, setting 9-12AlarmsActive summary 9-17Error detection and 9-17output 9-19saved 9-17Compatibility 9-3Trap messages 9-3Events Log 9-8Events log 9-13Events referencestrapbackground color 9-16default colors 9-17Preferences 9-16saving 9-17Monitor log 9-8, 9-9saving 9-9Performance data, explained 9-11Performance monitoring 9-8Performance Reports 9-9Remote Power Fail Indication 9-19“Dying-Gasp” circuit 9-19Throughput Checking 9-8Troubleshooting 9-19Installation 4-9ODUMast and Wall 17-1Step 1 - Start Wizard 5-3Step 2 - System Parameters 5-3Step 3 - Channel Settings 5-7Step 4 - Tx Power and Antenna SettingsBackground 5-9Step 4 - Tx Power and AntennasSettings 5-9Step 5 - Hub Site Synchronization Settings5-16Step 6 - Services 5-16Step 7 - TDM Clock Configuration 5-27Link ID 4-11, 5-4, 8-26, 9-19, 9-20, 9-20Login 4-3Login ErrorsIncorrect IP Address 4-7Incorrect password 4-7Unsupported Device 4-6Login showing Community Options 4-4Login showing user types 4-5Manager Software 4-2Name 5-4Password 1-8, 9-20changing 5-5Post Configuration main window 7-13Post Installation main window 5-30Site names 5-4Link Budget Calculator, see LBC 9-8Link ID 4-11, 5-4, 8-26, 9-19, 9-20, 9-20Link Lockdescribed 8-11
RADWIN 2000 User Manual Release2.5.40 Index 4Enable 8-11Link SitePlanning 2-1Survey 2-1Stage 1 - Preliminary Survey 2-2Stage 2 - Physical Survey 2-3Additional Indoor Site Requirements 2-3Additional Outdoor Site Requirements2-3Stage 3 - RF Survey 2-4Login ErrorsIncorrect IP Address 4-7Incorrect password 4-7Unsupported Device 4-6loopbackactivating 9-3deactivate 9-5Local Internal 9-7Remote External 9-6Remote Internal 9-6MManagementAddresses 8-5and trap addresses 8-1Configuring the Site 8-2Screen, Telnet 8-27Manager SoftwareChange log on password 4-8Events Log 6-6Installing 4-1Main window 6-1Details pane 6-4Toolbar 6-2main window 4-6Monitor pane 6-5Ethernet Service 6-5Radio Interface, 6-5Radio signal strength 6-5Off-line functionality 4-8Status Bar 6-7ManualChapters by Audience 1-15Terminology 1-16MHSdescribed 12-1Installation Procedure 12-1, 12-1Installing 12-3Kit Contents 12-3Maintaining 12-9IDU Replacement 12-9ODU Replacement 12-10Port pinout B-2Primary and secondary links 12-2provides 12-2Switching Logic 12-10System Operation 12-14MIBAbout D-1Community String D-2Interface API D-1Parameters D-3Private D-2Private Parameters D-6Reference D-1Supported Variables from the RFC 1213 D-4TDM D-3Terminology D-1Traps D-23Monitored Hot Standby, see MHSOODU 1-9Available products 1-9Backup and restore software 8-24Bridge Modeaging time 8-16Connectorized 1-9Connectorized Antenna 1-8described 1-8, 1-8form factors 1-9Installation, Mast and Wall 17-1Integrated Antenna 1-8, 1-9Mounting Kit 17-1Package Contents 3-2Preloading IP address 19-1Products 1-9Replacing 9-20With integrated antenna 1-13PPackage, contents of 3-2PasswordLink 1-8, 9-20PC, Minimum Requirements 4-1PerformanceMonitor 9-2Performance Monitoring, set time interval 9-9PoEBasic PoE Device 1-11Described 1-11Installing a link using 3-12PoE device, see PoEPower over Ethernet, see PoEProtectionExternal Lightning Surge Suppressors 18-3GroundingAntenna cable 18-1IDUs 18-2ODUs 18-2Internal ESD Protection circuits 18-8
RADWIN 2000 User Manual Release2.5.40 Index 5QQoS 25-1disabling 25-4Overview 25-1setting up, ff 25-2RRadio Frame Pattern (RFP)General Considerations 10-8General considerations 10-8With HSS 10-7Without HSS 10-7Radio LinkAdditional Tools and Materials Required 3-5Air rates 5-11Connecting user equipment 3-12Hardware InstallationExternal Antennas 3-7Indoor 3-8Lightning protection 3-8Mounting U 3-9ODU 3-7Outdoor 3-7Outdoor connections 3-8Sequence 3-6Package Contents 3-2IDU 3-4ODU 3-2Package contentsExternal Antennas 3-5Radio Outdoor Unit, see ODURegional NoticeFrench Canadian G-1Replacing an ODU 9-20SSafety Practices iii-iv, 3-1Grounding 3-1Preventing overexposure to RF energy 3-1SecurityLink Lock 8-11Selecting channel 5-7SFPdevice C-1support, described C-1SiteConfigurationBackup Filesbackup to 8-24Backup filesrestore from 8-24Configuration with Telnet 8-25DialogChange Tx Power 8-3Ethernet Properties 8-15ConfiguringBridge 8-15Maximum information rate 8-19Ports Mode 8-17Ethernet PropertiesIDU Aging time 8-16Functions 8-2Inventory 8-8Menu bar 8-2Setting the date and time 8-13View Air Iinterface details 8-3VLAN Settings 8-6Lost or forgotten VLAN ID 8-7Priority number 8-7VLAN ID 8-7External Alarm Inputs 8-21Reset site 8-22Reset site to factory defaults 8-22Reset site, preserve current configuration8-22Security Features 8-9Community Strings 8-9Editing 8-10Forgotten paswwords 8-10Initial log on defaults 8-10Default Gateway 8-6IP address 8-6, 8-6Trap Destination 8-6Software UpgardeMultiple sites 15-3Single Site 15-2Software Upgrade 15-1Spectrum Viewdescribed 4-11using 23-1TTDM ServicesClock configuration 5-27Evaluation 5-26in Link Budget calculation 21-1Jitter Buffer 5-23Loopbacks 9-3modulation rate 5-23over internet with SFP C-1selection 5-20TDD in MIB D-3Telnet commands 8-26Throughput display 6-6Trap message 9-15Technical SpecificationsAir Interface, general A-1Configuration A-1EMC A-3, A-5, A-5, A-6, A-7Environmental A-3, A-4Mechanical A-2Power A-2, A-3, A-4, A-4, A-4, A-4, A-4, A-4Radio A-1
RADWIN 2000 User Manual Release2.5.40 Index 6Safety A-3, A-4Telnet configuration 8-25TDM 8-26Time Division Duplex 10-7Trap messages 9-3Trunk Portspinout B-2typical installation 3-6UUser equipment, connecting 5-7VVLANconfiguration 14-5Port Functionality 14-2QinQ 14-2tagging 14-1terminology 14-1VLAN for Ethernet services 8-17VLAN for Ethernet services, ff 13-1, 14-1, 25-1WWiring Specifications B-1AlarmConnectorIDU-C B-3ConnectorsUser Port B-2LANPorts B-2ODU-IDU Cable B-1PortsLAN B-2User Port Connectors B-2

Navigation menu